Transcript
ArresterWorks Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Characteristics Meet
6/23/2012 Jonathan Woodworth
ArresterFacts 037
Insulation Coordination Fundamentals
Insulation Coordination Fundamentals Transient overvoltages are a fact of life on power
the most complex forms, computer simulations
systems.
Arresters can be used to effectively
are highly recommended; however, for a good
control the most frequent type, which are caused
first approximation, system performance can be
by switching operations.
modeled using simple formula presented in IEC
lightning somewhat
are
Insulation co-ordination
more
difficult to mitigate, but those too can be successfully
Transients caused by
handled
with a judicious effort. How one protects the
Selection of the dielectric strength of equipment in relation to the operating voltages and overvoltages which can appear on the system for which the equipment is intended and taking into account the service environment and the characteristics of t he available preventing and protective devices.
60071-1,
60071-2
60071-4.
These
and three
standards are very well written,
very
understandable, and easy to use. They cover 99% of what a person needs to
insulation on a power system is very often an
know to perform a lightning or switching surge
economic decision.
insulation coordination study.
It would certainly not be
IEEE 1313.1 and
reasonable to insulate only for the operating
1313.2 are another excellent source for better
voltage and allow all transients to cause insulation
understanding this engineering practice. A third
failure. It is equally unreasonable to insulate for
and highly acclaimed reference is “Insulation
all transient events, if it were even possible.
Coordination of Power Systems” by Andrew
Therefore, a solution that makes a reasonable
Hileman. This 1999 publication is invaluable for
investment in insulation and protective equipment
the student that would like to understand some of
is the compromise most often taken.
the
This
carefully designed combination of insulators and
most
complex
concepts
in
insulation
coordination.
arresters is called insulation coordination. This Insulation
coordination
has
become
a
ArresterFacts
is
not
meant
to
be
a
well
comprehensive treatise on the subject, but
developed engineering practice. This practice is
instead a basic coverage of the fundamentals of
where the characteristics of the system, insulation
insulation
of all forms, and arresters of all forms cross paths.
engineer understand when a study needs to be
The task of coordinating the insulation withstand
done and what might be the benefits of such a
coordination
levels with the desired
Self-restoring Insulation
the system can be
Insulation which, after a short time, completely recovers its insulating properties after a disruptive discharge during test
different
if arresters are applied verses if they are not applied.
This
help
the
power
study.
performance levels of significantly
to
Non self-restoring insulation (60071-1)
Insulation Characteristics
All insulation has its limits of withstand capability.
Insulation which loses its insulating properties, or does not recover them completely, after a
coordinating task and arrester selection/locating task can be quite simple at times, and at others very complex. In Copyright ArresterWorks 2012
2
ArresterFacts 037
Insulation Coordination Fundamentals
Figure 1 – Insulation Withstand
Figure 2 – Types of Insulation
Because it is impossible to insulate high enough to withstand lightning surges, all insulators are
indirectly. All stations need connection to the rest
designed and tested to determine the level to
of the system via incoming and outgoing overhead
which it flashes over.
Insulation has two
conductors. The only exception to this would be
fundamental withstand characteristics: lightning
GIS or underground station, therefore all the
impulse
following pertains to overhead, air insulated
withstand
withstand.
These
and
switching
impulse
two
characteristics
are
substations only. If lighting strikes either incoming
graphically shown in Figure 1 lightning impulse
or outgoing lines within a span or two of the
withstand voltage (LIWV) and switching impulse
station, a surge is likely to enter the stations on
withstand voltage (SIWV). The LIWV characteristic
the conductors.
of external self-restoring insulation is universally tested and verified under dry conditions.
The
physical straight line length between the insulator terminals
is
the
most
significant
factor
in
determining these fast impulse characteristics. The SIWV of external self-restoring insulation is universally tested under wet conditions because this withstand characteristic is a function of the insulation’s creepage or leakage distance when wet.
The creepage distance is the distance
between the two terminals along the surface of the sheds.
Figure 3 – Backflash into Protected Substation
Substations Insulation Coordination for Lightning Surges
Substations are subjected to two types of
Even well shielded transmission lines can allow a very fast rising surge to enter a nearby station if
overvoltages that can and do stress the insulation
there is a backflash to the conductor during a
throughout the station. Even if the station is well
switching or lightning surge (Figure 3);
shielded, lightning surges can enter the station
Copyright ArresterWorks 2012
3
ArresterFacts 037
Insulation Coordination Fundamentals
however, owing to the high insulation withstand
incoming lines to the station. Fortunately, in this
on systems above 245kV, back-flashovers are less
case, more lines make it harder to flashover
probable then on systems below 245kv and are
insulators in the substation, but at the same time
rare on systems at 500 kV and above.
more lines also increase to probability of an
Fast rising surges on an incoming conductor have
incoming surge. Both these factors are used in the
a high probability of flashing over insulation in the
formulas used to determine proper coordination.
substation if there are no arresters. amplitude
of
the
incoming
surge
will
The be
Separation Distance
approximately equal to the flashover level of the
Separation
distance
is
a
very
important
backflashed insulator.
If the only mitigation is an
consideration in the protection of substations and
arrester at the transformer, it will protect the
insulation coordination of substations. Arresters
transformer if properly coordinated with the
will limit or clamp a fast rising surge according to
transformer insulation. The arrester may protect
their own clamping characteristics immediately in
equipment on the surge side to some extent. In
the vicinity of the arrester; however, as the
this coordination scenario, the probability of its
protected insulation is moved away from the
occurrence is quite low over the expected life of
arrester, it is less and less protected from fast
the transformer, which is probably 30-40 years;
rising surges as described in scenario 1 above
however, if the proper arrester is not located near
(note there are no separation distance issues for
the transformer, it only takes one occurrence to
slow rising surges from switching sources). This
cause a failure of the expensive asset in the circuit.
reduced protection is due again to the effects of traveling waves and reflections. For this reason,
Another important part of this coordination
the
location
and
distance
scenario is the state of the circuit breaker. If the
insulation points in the
between
critical
breaker is in the open position, it will become an endpoint on the circuit.
Because endpoints
represent a significant change in impedance to the circuit, the voltage will be reflected and cause a doubling effect at the breaker.
This voltage
doubling effect (see traveling wave theory) will cause the breaker insulator to flashover causing yet another path for power current to flow to ground.
This voltage doubling effect can also
occur if the breaker is momentarily open and a second lightning surge arrives along the original surge path to find the breaker open. Due to these two potential open breaker scenarios, it is advisable to apply arresters at the line entrance of the station to eliminate the voltage doubling at the breaker and certain breaker bushing flashover. Yet another variable to consider in substation coordination for lightning is the number of
Figure 4 – Separation Distance
substation need to be well known before a proper insulation coordination study can be completed. Of course, the non-selfrestoring insulation of the transformer is generally the insulation of highest
Copyright ArresterWorks 2012
4
ArresterFacts 037
Insulation Coordination Fundamentals
consideration for separation distance issues. The
rejection
surges need attention.
formula for determining the farthest distance
inductive and capacitive currents need particular
between an arrester and the transformer is found
attention
in the stated references above as well as in IEC
experience pre-strike or restrike. In this case, the
60099-5. As it turns out, the higher the system
range of 2% voltages is 2-2.5pu.
when
the
Switching
associated
breakers
voltage, the shorter the allowable separation distances become because the ratio of the
There are two coordination methods used in the
transformer
practice
withstand
voltage
and
system
voltages is reduced.
of
insulation
coordination.
The
deterministic method is used exclusively when applied to non-selfrestoring insulation. When
Substation Insulation Coordination for Switching
coordinating self-restoring insulation, statistical
Surges
(also known as probabilistic) methods are almost
Switching surges are of concern only on systems
universally used.
245kV and above. The magnitudes of switching
these two methods is that in the deterministic
surges for systems below 245kV generally do not
method, absolute maximum and minimum values
exceed 1.5pu of the system phase to ground
are coordinated.
voltage.
This is due to the fact that the line
residual voltage of an arrester for a slow front
capacitance, length, and voltage are not of high
surge is coordinated and compared to the
enough values to result in challenging surges.
minimum withstand level of transformer switching
There are numerous sources of slow front
impulse withstand level.
switching surges in substations. Circuit breakers
statistical method in determining the flashover
or switching devices are involved in all forms of
rate of the 25 self-restoring post insulators in the
this surge. Fault and fault clearing overvoltages
substation the probability of flashover, occurrence
are generated in the unfaulted phase when the
and magnitude of the surge are used in the
fault is first initiated and when the voltage is re-
calculation.
established.
distribution representing the overall switching
The basic difference between
For example, the maximum
The
When using the
results
are
a
probability
surge flashover rate Arrester Characteristics and Substation Insulation Coordination
Arresters are a fundamental part of insulation coordination in the substation. universally Figure 5 – 2% Switching Surge Statistical Level
Switching surge statistical level is known as the 2% voltage (see figure 5) and range from 1-2 per unit of the crest phase to ground voltage if they are mitigated with pre-insertion resistors or arresters; however, if they are not mitigated, their levels can easily exceed 2.0pu. When energization and re-energization surges are mitigated, load
to
protect
the
They are used non-selfrestoring
insulation of power transformers.
As stated
above, the coordination of non-selfrestoring insulation is accomplished using the deterministic method. This is because there are no acceptable test methods that can determine the probability of disruptive discharge in oil/paper insulation systems. Therefore, the only option is to accept the deterministic approach.
Copyright ArresterWorks 2012
5
ArresterFacts 037
Insulation Coordination Fundamentals
Arresters applied in substations characterized by
co-ordination withstand voltage, it should be kept
three voltages relative to insulation coordination:
in mind that most adverse conditions from a
the arrester operating voltage (Uc or MCOV),
strength point of view (i.e. low absolute humidity,
lightning impulse protective level (LIPL) and
low air pressure and high temperature) do not
switching impulse protective level (SIPL). They are
usually occur simultaneously. In addition, at a
shown in Figure 6.
given site, the corrections applicable for humidity and ambient temperature variations cancel each other for all intents and purposes. Therefore, t he estimation of the strength can usually be based on the average ambient conditions at the location. When contamination from salt or industrial pollution is present, the response of external insulation to power-frequency voltages becomes
Figure 6 – Arrester Protective Characteristics
For non-self restoring insulation, a deterministic comparison is completed. After the insulation and arrester characteristics are determined, they are then coordinated to insure that there is ample safety margin between them. The comparative graph is shown in Figure 7 and is referred to as the Margin of Protection.
Figure 7 – Non-Self Restoring Margin
important and may dictate longer creepage or Environmental Effects on Insulation Coordination
leakage distances.
This type of contamination
Flashover voltages for air gaps depend on the
does not adversely affect lightning and fast front
moisture content and density of the air. Insulation
withstand levels. Flashover of insulation generally
strength increases with absolute humidity up to
occurs when the surface is contaminated and
the point where condensation forms on the
becomes wet due to light rain, snow, dew or fog
insulator surfaces. Because insulation strength
without a significant washing effect.
decreases with decreasing air density, longer strike distance is required to attain the same
Transmission Line Insulation Coordination
flashover voltage at 2000m elevation than at 100
Transmission line insulation coordination is also
meters above sea level. A detailed description of
separated into two categories; lightning and
the effects of air density and absolute humidity
switching. The performance assessment methods
are given in IEC 60-1 or IEEE Std 4 for different
are based on expected lightning and switching
types of voltage stresses. When determining the
overvoltages and their corresponding insulation
Copyright ArresterWorks 2012
6
ArresterFacts 037
Insulation Coordination Fundamentals
levels. Since line insulation is self-recovering, their
Switching impulse studies need only be considered
performances are usually determined by the
for lines exceeding 245kV. For lines below this
statistical method.
level, the switching surge magnitudes do not overstress normal insulation configurations. For
The practices outlined in substation insulation
levels above 245kV, the stresses can be significant.
coordination also apply to line coordination. The Switching Surge Flashover Rate (SSFOR) is The sum of the back flashover rate (BFR) and
determined by numerical integration of the stress-
shielding
strength relationship. The stress in this case is the
failure
rate
(SFR)
determine
the
flashover rate (FOR) which is expressed in
switching
flashovers/100km/year.
overvoltage (SOV) quantified by a probability
The back flashover rate
is the most significant
impulse
Shielding Failure Rate (SFR)
voltage
or
distribution.
switching Strength is
cause of outage on
The shielding failure rate is the number of strikes
the
transmission lines.
that terminate on the phase conductors. If the
withstand voltage (CFO).
voltage produced by a strike to the phase
IEC
The fast rising surge
conductors exceeds the line CFO (critical flashover
1313.2 define this process
associated with a back
voltage), flashover occurs.
in detail.
flashover
switching 60071-2
impulse and
IEEE
seldom
makes it to the substation due to corona effects;
If arresters are used to mitigate the SSFOR, the
however, fault current and breaker operation
evaluation method is modified to accommodate
resulting from the back flashover is felt over the
the change in the SOV since it will no longer be a
entire length of the system.
normal
switching
surge
is
Often times, a
experienced
immediately
distribution
but
instead
truncated
distribution.
following a lightning caused flashover. Distribution
Another
significant
Back Flashover Rate (BFR)
Systems
Insulation Coordination
often
The back flashover rate is the number of lightning
The practice of distribution
involved in lightning
strikes that terminate on towers or shield wires and
system
insulation
flashover
result in insulator flashover The current impulse
coordination
is
coordination
the
raises the tower voltage, in turn this generates a
limited; however, there are
elevations.
voltage across the line insulation. If the voltage
some
The critical flashover
across the line insulators exceeds the insulation
deterministic practices that
voltage
strength, a back flashover can be expected from the
are quite important.
tower onto the phase conductor.
margin
variable
system
is
(CFO) of a
line insulator can be reduced by as much
very
of
calculations
very specific The
protection for
some
as 20% at higher elevations. Since transmission
system configurations can determine when to and
lines often traverse high elevations, this factor
when not to use arresters.
must be considered. For higher elevations, the
underground circuits where voltage doubling is
insulators may be lengthened or arrester may be
common, a margin of protection calculation can
applied. Both are excellent means of mitigation.
reveal that applying an arrester only at the riser
For instance, on
pole for systems above 25kV can be a problem. When this is the case, an open point arrester is Copyright ArresterWorks 2012
7
ArresterFacts 037
Insulation Coordination Fundamentals
recommended to provide a lower risk of cable
Another factor that can have major impact on
failure.
insulation coordination on distribution systems is long lead lengths on arresters.
Long leads can
On ineffectively grounded or delta distribution
effectively render an arrester unable to protect
systems, a close check of the margin of protection
non-self-restoring
can often show that there is little margin
equipment.
insulation
of
distribution
compared to well grounded systems. This is due to the fact that higher rated arresters are applied
Conclusion
to these circuits to give them ample overvoltage
In this brief overview of insulation coordination
withstand capability.
By raising the operating
fundamentals, it can be seen that the many
voltage of the arrester, the clamping voltage is
variables involved in this engineering exercise can
also increased and the margin between the
make this task quite complicated. However, using
transformer’s
this method to optimize the use of arresters can
withstand
curve
and
arrester’s
clamping curve is decreased.
result in significant insulation savings on all systems.
ArresterFacts are a compilation of facts about arresters to assist all stakeholders in the application and
understanding of arresters. All ArresterFacts assume a base knowledge of surge protection of power systems; however, we always welcome the opportunity to assist a student in obtaining their goal, so please call if you have any questions. Visit our library of ArresterFacts for more reading on topics of interest to those involved in the protection of power system at: About the author: Jonathan started his career after receiving his Bachelor's degree in Electronic Engineering from The Ohio Institute of Technology, at Fermi National Accelerator Laboratory in Batavia, IL. As an Engineering Physicist at Fermi Lab, he was an integral member of the high energy particle physics team in search of the elusive quark . Wishing to return to his home state, he joined the design engineering team at McG raw Edison (later Cooper Power Systems) in Olean, New York. During his tenure at Cooper, he was involved in the design, development, and manufacturing of arresters. He served as Engineering Manager as well as Arrester Marketing Manager during that time. Jonathan has been active for the last 30 years in the IEEE and IEC standard associations. Jonathan is inventor/co-inventor on five US patents. Jonathan received his MBA from St. Bonaventure University.
Jonathan Woodworth ArresterWorks’
Principle Engineer www.arresterworks.com
[email protected] +1.716.307.2431
Copyright ArresterWorks 2012
8