Packaged Rooftop Air Conditioners 27½ to 50 Ton - 60 Hz 23 to 42 Ton (81-148 kW) - 50 Hz Voyager™ Commercial with ReliaTel™ Controls
April 2004
RT-PRC007-EN
Introduction
Packaged Rooftop Air Conditioners Through the years, Trane has designed and developed the most complete line of Packaged Rooftop products available in the market today. Trane was the first to introduce the Micro—micro Micro—microelectronic electronic unit controls—and has continued to improve and revolutionalize this design concept. The ReliaTel control platform offers the same great features and functionality as the original Micro, with additional benefits for greater application flexibility. flexibility. The Voyager Voyager Commercial line offers 27½ to 50 ton 60 Hz and 23 to 42 ton 50 Hz models. Both 50 and 60 Hz models come in a choice of five sizes to meet the changing demands of the commercial rooftop market.
© 2004 American Standard Inc. All rights reserved
Trane customers demand products that provide exceptional reliability, meet stringent performance requirements, and are competitively priced. Trane delivers with Voyager Voyager Commercial. Voyager Commercial features f eatures cutting edge technologies: reliable 3-D ™ Scroll compressors, Trane Trane engineered ReliaTel controls, computer-aided run testing, and Integrated Comfort™ Systems. So, whether you’re the contractor, the engineer,, or the owner you can be certain engineer Voyager Commercial Products are built to meet your needs. It’s Hard Ha rd To Stop A Trane. ®
RT-PRC007-EN
Introduction
Packaged Rooftop Air Conditioners Through the years, Trane has designed and developed the most complete line of Packaged Rooftop products available in the market today. Trane was the first to introduce the Micro—micro Micro—microelectronic electronic unit controls—and has continued to improve and revolutionalize this design concept. The ReliaTel control platform offers the same great features and functionality as the original Micro, with additional benefits for greater application flexibility. flexibility. The Voyager Voyager Commercial line offers 27½ to 50 ton 60 Hz and 23 to 42 ton 50 Hz models. Both 50 and 60 Hz models come in a choice of five sizes to meet the changing demands of the commercial rooftop market.
© 2004 American Standard Inc. All rights reserved
Trane customers demand products that provide exceptional reliability, meet stringent performance requirements, and are competitively priced. Trane delivers with Voyager Voyager Commercial. Voyager Commercial features f eatures cutting edge technologies: reliable 3-D ™ Scroll compressors, Trane Trane engineered ReliaTel controls, computer-aided run testing, and Integrated Comfort™ Systems. So, whether you’re the contractor, the engineer,, or the owner you can be certain engineer Voyager Commercial Products are built to meet your needs. It’s Hard Ha rd To Stop A Trane. ®
RT-PRC007-EN
Contents
Introduction
2
Features and Benefits
4
Application Considerations
10
Selection Procedure
13
Model Number Description
17
General Data
19
Performance Data
26
Performance Adjustment Factors
RT-PRC007-EN
25
Controls
49
Electric Power
53
Dimension and Weights Weights
56
Mechanical Specifications
65
3
Features and Benefits
Standard Features Factory installed and commissioned ReliaTel™ controls • Trane 3-D™ Scroll Compressors • Dedicated downflow or horizontal configuration • CV orVAV control • Frostat™ coil frost protection on all units • Supply air overpressurization protection on VAV units • Supply airflow proving • Emergency stop input • Compressor lead-lag • Occupied-Unoccupied switching • Timed override activation • FC supply fans • UL and CSA listing on standard options • Two inch standard efficiency filters • Finish exceeds salt spray requirements of ASTM B117 • Sloped condensate drain pan • Cleanable, IAQ-enhancing, foil faced insulation on all interior surfaces exposed to the unit air stream Optional Features • Electric heat • Natural gas heat • LP gas heat (kit only) • Power Exhaust • Barometric Relief • High Efficiency 2”Throwaway Filters • High Efficiency 4”Throwaway Filters • High Efficiency supply fan motors
4
• Manual fresh air damper • Economizer with dry bulb control • Economizer with reference enthalpy control • Economizer with differential (comparative) enthalpy control • Inlet guide vanes on VAV units • Variable frequency drives on VAV units (with or without bypass) • Service Valves • Through-the-base electrical provision • Factory mounted disconnect with external handle (non-fused) • Factory powered 15A GFI convenience outlet • Field powered 15A GFI convenience outlet • Trane Communication Interface (TCI) • Ventilation Override • Hinged Service Access • Factory installed condenser coil guards • Black epoxy coated condenser coil • Sloped stainless steel evaporator coil drain pans • CO2 sensors for space comfort control (SCC) or discharge air control (DAC) LonTalk® Communication Interface (LCI-R) Clogged filter switch Discharge air temperature sensor (CV only) •
• •
RT-PRC007-EN
Features and Benefits
Trane 3-D™ Scroll Compressor Simple Design with 70% Fewer Parts Fewer parts than an equal capacity reciprocating compressor means significant reliability and efficiency benefits. The single orbiting scroll eliminates the need for pistons, connecting rods, wrist pins and valves. Fewer parts lead to increased reliability. Fewer moving parts, less rotating mass and less internal friction means greater efficiency than reciprocating compressors.
Proven Design Through Testing and Research With over twenty years of development and testing, Trane 3-D Scroll compressors have undergone more than
400,000 hours of laboratory testing and field operation. This work combined with over 25 patents makes Trane the worldwide leader in air conditioning scroll compressor technology.
The Trane 3-D Scroll provides important reliability and efficiency benefits. The 3-D Scroll allows the orbiting scrolls to touch in all three dimensions, forming a completely enclosed compression chamber which leads to increased efficiency. In addition, the orbiting scrolls only touch with enough force to create a seal; there is no wear between the scroll plates. The fixed and orbiting scrolls are made of high strength cast iron which results in less thermal distortion, less leakage, and higher efficiencies. The most outstanding feature of the 3-D Scroll compressor is that slugging will not cause failure. In a reciprocating compressor, however, the liquid or dirt can cause serious damage.
Low Torque Variation The 3-D Scroll compressor has a very smooth compression cycle; torque variations are only 30 percent of that produced by a reciprocating compressor. This means that the scroll compressor imposes very little stress on the motor resulting in greater reliability. Low torque variation reduces noise and vibration.
Suction Gas Cooled Motor Compressor motor efficiency and reliability is further optimized with the latest scroll design. Cool suction gas keeps the motor cooler for longer life and better efficiency.
One of two matched scroll plates — the distinguishing feature of the scroll compressor. RT-PRC007-EN
Chart illustrates low torque variation of 3-D Scroll compressor vs reciprocating compressor. 5
Features and Benefits
Quality and Reliability
Voyager with ReliaTel reduces the number of components required to operate the unit, thereby reducing possibilities for component failure.
As long as the unit has power and the “system on” LED is lit, Relia Tel is operational.The light indicates that the controls are functioning properly.
ReliaTel Makes Installing and Servicing Easy
ReliaTel features expanded diagnostic capabilities when utilized with Trane Integrated Comfort™ Systems.
ReliaTel eliminates the need for field installed anti-shortcycle timer and time delay relays. ReliaTel controls provide these functions as an integral part of the unit. The contractor no longer has to purchase these controls as options and pay to install them. The wiring of the low voltage connections to the unit and the zone sensors is as easy as 1-1, 2-2, and 3-3. This simplified system makes it easier for the installer to wire.
Easy to Install, Service and Maintain Because today’s owners are very costconscious when it comes to service and maintenance, the Trane Voyager was designed with direct input from service contractors.This valuable information helped to design a product that would get the serviceman off the job quicker and save the owner money. Voyager does this by offering: ReliaTel™ Controls (LCI-R)
ReliaTel Makes Testing Easy Reliael requires no special tools to run the Voyager unit through its paces. Simply place a jumper between Test 1 and Test 2 terminals on the Low Voltage Terminal Board and the unit will walk through its operational steps automatically. —The unit automatically returns control to the zone sensor after stepping through the test mode a single time, even if the jumper is left on the unit.
Some Zone Sensor options have central control panel lights which indicate the mode the unit is in and possible diagnostic information (dirty filters for example). Other ReliaTel Benefits The ReliaTel built-in anti-shortcycle timer, time delay relay and minimum “on” time control functions are factory tested to assure proper operation. ReliaTel softens electrical “spikes” by staging on fans, compressors and heaters. Intelligent Fallback is a benefit to the building occupant. If a component goes astray, the unit will continue to operate at predetermined temperature setpoint. Intelligent Anticipation is a standard ReliaTel feature. It functions continuously as ReliaTel and zone sensor(s) work together in harmony to provide much tighter comfort control than conventional electro-mechanical thermostats.
ReliaTel controls provide unit control for heating, cooling and ventilating utilizing input from sensors that measure outdoor and indoor temperature. Quality and Reliability are enhanced through ReliaTel control and logic: • prevents the unit from short cycling, considerably improving compressor life. • ensures that the compressor will run for a specific amount of time which allows oil to return for better lubrication, enhancing the reliability of the commercial compressor.
6
RT-PRC007-EN
Features and Benefits
Trane Communication Interface (TCI) TheTCI is available factory or field installed. When applied with ReliaTel, this module easily interfaces with theTrane Integrated Comfort™ System. Interoperability with LonTalk® (LCI-R) The LonTalk Communication (LCI-R) for Voyager Commercial offers a building automation control system with outstanding interoperability benefits. LonTalk, which is an industry standard, is an open, secure and reliable network communication protocol for controls, created by Echelon Corporation and adopted by the LonMark Interoperability Association. It has been adopted by several standards, such as: EIA-709.1, the Electronic Industries Alliance (EIA) Control Network Protocol Specification and ANSI/ ASHRAE 135, part of the American Society of Heating, Refrigeration, and AirConditioning Engineer’s BACnet control standard for buildings. Interoperability allows application or project engineers to specifiy the best products of a given type, rather than one individual supplier’s entire system. It reduces product training and installation costs by standardizing communications across products. Interoperable systems allow building managers to monitor and control Voyager Commercial equipment with a TraneTracer Summit™ or a 3rd party building automation system. It enables integration with many different building controls such as access/intrusion monitoring, lighting, fire and smoke devices, energy management, and a wide variety of sensors for temperature, pressure, humidity and occupancy CO2.
without a bypass option. Bypass control will simply provide full nominal airflow in the event of drive failure. VariTrac™ changeover-bypass VAV For light commercial applications, Trane offers constant volume (CV) Voyager Commercial models with a changeoverbypass VAV system. For the most advanced comfort management systems, count on Trane.
The system consists of: • Voyager™ Commercial VAV packaged rooftops • Up to 32 VariTrane™ VAV boxes with DDC (direct digital controls) • VariTrac™ Central Control Panel (CCP) with Operator Display (OD) The VariTrac Central Control Panel acts as a communications hub by coordinating the actions of the VAV rooftop and the VAV boxes. Single duct or fan powered VAV boxes are available, along with an option for factory-installed local heat. For more details, see VAV-SLM003-EN. Downflow and Horizontal Economizers The economizers come with three control options dry bulb, enthalpy and differential enthalpy. (Photo below shows the three fresh air hoods on the Horizontal Discharge Configuration).
Delivered VAV Trane provides true pressure independent variable air volume with Voyager Commercial delivered VAV.The system is auto-configured to reduce programming and set-up time on the job. Generally available only on sophisticated larger models, this Voyager Commercial system can economically handle comfort requirements for any zone in the facility.
For additional information on LonMark, visit www.lonmark.org or Echelon, www.echelon.com. Variable Frequency Drives (VFD) Variable Frequency Drives are factory installed and tested to provide supply fan motor speed modulation. VFD’s, as compared to inlet guide vanes or discharge dampers, are quieter, more efficient, and are eligible for utility rebates. TheVFD’s are available with or
RT-PRC007-EN
7
Features and Benefits
Forced Combustion Blower Negative Pressure Gas Valve Hot Surface Ignitor Drum and Tube Heat Exchanger
Outstanding Standard and Optional Components Drum and Tube Heat Exchanger The drum and tube heat exchanger is designed for increased efficiency and reliability and utilizes the same technology that has been incorporated into large commercial roof top units for over 20 years. The heat exchanger is manufactured using optional stainless, or standard aluminized, steel with stainless steel components for maximum durability.The requirement for cycle testing of heat exchangers is 10,000 cycles by ANSI Z21.47. This is the standard required by both UL and AGA for cycle test requirements.Trane requires the design to be tested to 2½ times this current standard.The drum and tube design has been tested and passed over 150,000 cycles which is over 15 times the current ANSI cycling requirements. The negative pressure gas valve will not allow gas flow unless the combustion blower is operating. This is one of the unique safety features of Voyager Commercial. The forced combustion blower supplies pre-mixed fuel through a single stainless steel burner screen into a sealed drum where ignition takes place. It is more reliable to operate and maintain than a multiple burner system.
8
The hot surface ignitor is a gas ignition device which doubles as a safety device utilizing a continuous test to prove the flame.The design is cycle tested at the factory for quality and reliability. All the gas/electric rooftops exceed all California seasonal efficiency requirements.They also perform better than required to meet the California NOx emission requirements. Excellent Part-Load Efficiency The unique design of the scroll compressor allows it to be applied in a passive parallel manifolded piping scheme, something that a “recip” just doesn’t do very well. When the unit begins stage back at part load it still has the full area and circuitry of its evaporator and condenser coils
available to transfer heat. In simple terms this means superior part-load efficiencies (IPLV) and lower unit operating costs. Rigorous Testing All of Voyager’s designs were rigorously rain tested at the factory to ensure water integrity. Actual shipping tests are performed to determine packaging requirements. Units are test shipped around the country. Factory shake and drop tested as part of the package design process to help assure that the unit will arrive at your job site in top condition. Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting lugs and rails hold up under stress. We perform a 100% coil leak test at the factory.The evaporator and condenser coils are leak tested at 200 psig and pressure tested to 450 psig. All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected immediately. Every unit receives a 100% unit run test before leaving the production line to make sure it lives up to rigorous Trane requirements.
RT-PRC007-EN
Features and Benefits
Power Exhaust Option
Easy to Install
FC Fans with Inlet Guide Vanes
Provides exhaust of the return air when using an economizer to maintain proper building pressurization. Great for relieving most building overpressurization problems.
Contractors look for lower installation (jobsite) costs. Voyager’s conversionless units provide many time and money saving features.
Trane’s forward-curved fans with inlet guide vanes pre-rotate the air in the direction of the fan wheel, decreasing static pressure and horsepower, essentially unloading the fan wheel. The unloading characteristics of a Trane FC fan with inlet guide vanes result in superior part load performance.
Conversionless Units The dedicated design units (either downflow or horizontal) require no panel removal or alteration time to convert in the field — a major cost savings during installation.
Improved Airflow U-shaped airflow allows for improved static capabilities.The need for high static motor conversion is minimized and saves the time normally spent changing to high static oversized motors.
Single Point Power A single electrical connection powers the unit.
Trane factory built roof curbs Available for all units.
Added Efficiency Low Ambient Cooling All Voyager Commercial units have cooling capabilities down to 0 F as standard.
Horizontal Discharge with Power Exhaust Option
One of Our Finest Assets Trane Commercial Sales Engineers are a support group that can assist you with: — Product — Application — Service — Training — Special Applications — Specifications — Computer Programs and more
RT-PRC007-EN
9
Application Considerations
Exhaust Air Options
60 Hz
amounts of outdoor air into the building. If, however, building pressure is not of a critical nature, the non-modulating exhaust fan may be sized for more than 50 percent of design supply airflow. Consult Table PD-16 for specific exhaust fan capabilities with Voyager Commercial units.
3
Barometric Relief Dampers
5 Bhp must be multiplied by the air density ratio to obtain the actual operating bhp.
Voyager Commercial rooftop units offer two types of exhaust systems:
Barometric relief dampers consist of gravity dampers which open with increased building pressure. As the building pressure increases, the pressure in the unit return section also increases, opening the dampers and relieving air. Barometric relief may be used to provide relief for single story buildings with no return ductwork and exhaust requirements less than 25 percent.
1
Altitude Corrections
Power exhaust fan.
The rooftop performance tables and curves of this catalog are based on standard air (.075 lbs/ft). If the rooftop airflow requirements are at other than standard conditions (sea level), an air density correction is needed to project accurate unit performance.
From Figure PD-1, the air density ratio is 0.86.
When is it necessary to provide building exhaust? Whenever an outdoor air economizer is used, a building generally requires an exhaust system. The purpose of the exhaust system is to exhaust the proper amount of air to prevent over or underpressurization of the building. A building may have all or part of its exhaust system in the rooftop unit. Often, a building provides exhaust external to the air conditioning equipment. This external exhaust must be considered when selecting the rooftop exhaust system.
2 Barometric relief dampers.
Application Recommendations Power Exhaust Fan The exhaust fan option is a dual, nonmodulating exhaust fan with approximately half the air-moving capabilities of the supply fan system. The experience of The Trane Company is that a non-modulating exhaust fan selected for 40 to 50 percent of nominal supply cfm can be applied successfully. The power exhaust fan generally should not be selected for more than 40 to 50 percent of design supply airflow. Since it is an on/off nonmodulating fan, it does not vary exhaust cfm with the amount of outside air entering the building. Therefore, if selected for more than 40 to 50 percent of supply airflow, the building may become underpressurized when economizer operation is allowing lesser
10
Figure PD-1 shows the air density ratio at various temperatures and elevations. Trane rooftops are designed to operate between 40 and 90 degrees Fahrenheit leaving air temperature. The procedure to use when selecting a supply or exhaust fan on a rooftop for elevations and temperatures other than standard is as follows:
1 First, determine the air density ratio using Figure PD-1.
2 Divide the static pressure at the nonstandard condition by the air density ratio to obtain the corrected static pressure.
Use the actual cfm and the corrected static pressure to determine the fan rpm and bhp from the rooftop performance tables or curves.
4 The fan rpm is correct as selected.
In order to better illustrate this procedure, the following example is used: Consider a 30-ton rooftop unit that is to deliver 11,000 actual cfm at 1.50 inches total static pressure (tsp), 55 F leaving air temperature, at an elevation of 5,000 ft.
1
2 Tsp=1.50 inches/0.86=1.74 inches tsp.
3 From the performance tables: a 30-ton rooftop will deliver 11,000 cfm at 1.74 inches tsp at 668 rpm and 6.93 bhp.
4 The rpm is correct as selected — 668 rpm.
5 Bhp = 6.93 x 0.86 = 5.96 . Compressor MBh, SHR, and kw should be calculated at standard and then converted to actual using the correction factors in Table PD-2. Apply these factors to the capacities selected at standard cfm so as to correct for the reduced mass flow rate across the condenser. Heat selections other than gas heat will not be affected by altitude. Nominal gas capacity (output) should be multiplied by the factors given in Table PD-3 before calculating the heating supply air temperature.
RT-PRC007-EN
Application Considerations
Exhaust Air Options When is it necessary to provide building exhaust? Whenever an outdoor air economizer is used, a building generally requires an exhaust system.The purpose of the exhaust system is to exhaust the proper amount of air to prevent over or underpressurization of the building. A building may have all or part of its exhaust system in the rooftop unit. Often, a building provides exhaust external to the air conditioning equipment.This external exhaust must be considered when selecting the rooftop exhaust system. Voyager™ Commercial rooftop units offer two types of exhaust systems:
1 Power exhaust fan
2 Barometric relief dampers
Application Recommendations Power Exhaust Fan The exhaust fan option is a dual, nonmodulating exhaust fan with approximately half the air-moving capabilities of the supply fan system. The experience of Trane is that a nonmodulating exhaust fan selected for 40 to 50 percent of nominal supply cfm can be applied successfully. The power exhaust fan generally should not be selected for more than 40 to 50 percent of design supply airflow. Since it is an on/off non-modulating fan, it does not vary exhaust cfm with the amount of outside air entering the building. Therefore, if selected for more than 40 to 50 percent of supply airflow, the building may become under-pressurized when economizer operation is allowing lesser amounts of outdoor air into the building. If, however, building pressure is
RT-PRC007-EN
not of a critical nature, the non-modulating exhaust fan may be sized for more than 50 percent of design supply airflow.
Barometric Relief Dampers Barometric relief dampers consist of gravity dampers which open with increased building pressure. As the building pressure increases, the pressure in the unit return section also increases, opening the dampers and relieving air. Barometric relief may be used to provide relief for single story buildings with no return ductwork and exhaust requirements less than 25 percent.
Altitude Corrections The rooftop performance tables and curves of this catalog are based on standard air (.075 lb/ft) (.034 kg/cm). If the rooftop airflow requirements are at other than standard conditions (sea level), an air density correction is needed to project accurate unit performance. Figure PD-1 shows the air density ratio at various temperatures and elevations. Trane rooftops are designed to operate between 40 and 90°F (4.4 and 32.2°C) leaving air temperature. The procedure to use when selecting a supply or exhaust fan on a rooftop for elevations and temperatures other than standard is as follows:
1 First, determine the air density ratio using Figure PD-1.
2 Divide the static pressure at the nonstandard condition by the air density ratio to obtain the corrected static pressure. 3 Use the actual cfm and the corrected static pressure to determine the fan rpm and bhp from the rooftop performance tables or curves.
50 Hz
4 The fan rpm is correct as selected.
5 Bhp must be multiplied by the air density ratio to obtain the actual operating bhp. In order to better illustrate this procedure, the following example is used: Consider a 29-ton (105 kW) rooftop unit that is to deliver 9,160 actual cfm (4323 L/ s) at 1.50 inches total static pressure (tsp) (38 mm, 373 Pa), 55°F (12.8°C) leaving air temperature, at an elevation of 5,000 ft (1524 m).
1 From Figure PD-1, the air density ratio is 0.86.
2 Tsp = 1.50 inches/0.86 = 1.74 inches tsp. 374/.86 = 434 Pa.
3 From the performance tables: a 29-ton (105 kW) rooftop will deliver 9,160 cfm at 1.74 inches tsp 4323 L/s at 434 Pa) at 651 rpm and 5.51 bhp (4.11 kW).
4 The rpm is correct as selected – 651 rpm.
5 Bhp = 5.51 x 0.86 = 4.74 bhp actual. kW = 4.11 x 0.86 = 3.5 kW Compressor MBh, SHR, and kW should be calculated at standard and then converted to actual using the correction factors in Table PD-2. Apply these factors to the capacities selected at standard cfm so as to correct for the reduced mass flow rate across the condenser. Heat selections other than gas heat will not be affected by altitude. Nominal gas capacity (output) should be multiplied by the factors given inTable PD-3 before calculating the heating supply air temperature.
11
Application Considerations
Acoustical Considerations
Proper placement of rooftops is critical to reducing transmitted sound levels to the building. The ideal time to make provisions to reduce sound transmissions is during the design phase. And the most economical means of avoiding an acoustical problem is to place the rooftop(s) away from acoustically critical areas. If possible, rooftops should not be located directly above areas such as: offices, conference rooms, executive office areas and classrooms. Instead, ideal locations might be over corridors, utility rooms, toilets or other areas where higher sound levels directly below the unit(s) are acceptable. Several basic guidelines for unit placement should be followed to minimize sound transmission through the building structure: 1
Never cantilever the compressor end of the unit. A structural cross member must support this end of the unit. 2
Locate the unit center of gravity which is close to, or over, a column or main support beam. 3
If the roof structure is very light, roof joists must be replaced by a structural shape in the critical areas described above. 4
If several units are to be placed on one span, they should be staggered to reduce deflection over that span.
50/60 Hz
transmission, since this depends on the response of the roof and building members to the sound and vibration of the unit components. However, the guidelines listed above are experienceproven guidelines which will help reduce sound transmissions.
1
Clearance Requirements
To assure proper diffusion of exhaust air before contact with the outside air intake of adjacent unit.
The recommended clearances identified with unit dimensions should be maintained to assure adequate serviceability, maximum capacity and peak operating efficiency. A reduction in unit clearance could result in condenser coil starvation or warm condenser air recirculation. If the clearances shown are not possible on a particular job, consider the following: Do the clearances available allow for major service work such as changing compressors or coils? Do the clearances available allow for proper outside air intake, exhaust air removal and condenser airflow? If screening around the unit is being used, is there a possibility of air recirculation from the exhaust to the outside air intake or from condenser exhaust to condenser intake? Actual clearances which appear inadequate should be reviewed with a local Trane sales engineer.
To reduce span deflection if more than one unit is placed on a single span. Reducing deflection discourages sound transmission. 2
Duct Design
It is important to note that the rated capacities of the rooftop can be met only if the rooftop is properly installed in the field. A well designed duct system is essential in meeting these capacities. The satisfactory distribution of air throughout the system requires that there be an unrestricted and uniform airflow from the rooftop discharge duct. This discharge section should be straight for at least several duct diameters to allow the conversion of fan energy from velocity pressure to static pressure. However, when job conditions dictate elbows be installed near the rooftop outlet, the loss of capacity and static pressure may be reduced through the use of guide vanes and proper direction of the bend in the elbow. The high velocity side of the rooftop outlet should be directed at the outside radius of the elbow rather than the inside.
When two or more units are to be placed side by side, the distance between the units should be increased to 150 percent of the recommended single unit clearance. The units should also be staggered for two reasons:
It is impossible to totally quantify the effect of building structure on sound
12
RT-PRC007-EN
Selection Procedure
Selection of Trane commercial air conditioners is divided into five basic areas:
1 Cooling capacity
2 Heating capacity
3 Air delivery
4 Unit electrical requirements
5 Unit designation
60 Hz
b 2” Hi-efficiency throwaway filters.
c
Step 4 — Determine total required unit cooling capacity:
Exhaust fan.
d
Required capacity = total peak load + O.A. load + supply air fan motor heat.
Economizer cycle. Step 1 — A summation of the peak cooling load and the outside air ventilation load shows: 27.75 tons + 1.52 tons = 29.27 required unit capacity. From Table 18-2, 30-ton unit capacity at 80 DB/ 67 WB, 95 F entering the condenser and 12,000 total peak supply cfm, is 30.0 tons. Thus, a nominal 30-ton unit is selected.
1
Step 2 — Having selected a nominal 30ton unit, the supply fan and exhaust fan motor bhp must be determined.
Summer design conditions — 95 DB/
Supply Air Fan:
76 WB, 95 F entering air to condenser.
Determine unit static pressure at design supply cfm:
Factors Used In Unit Cooling Selection:
2 Summer room design conditions — 76 DB/66 WB.
External static pressure
1.20 inches
Heat exchanger
.14 inches
3
(Table PD-14)
Total peak cooling load — 321 MBh (27.75 tons).
High efficiency filter 2”
4
Economizer
Total peak supply cfm — 12,000 cfm.
(Table PD-14)
5
Unit total static pressure
External static pressure — 1.0 inches.
Using total cfm of 12,000 and total static pressure of 1.50 inches, enter Table PD-12. Table PD-12 shows 7.27 bhp with 652 rpm.
6 Return air temperatures — 80 DB/66 WB.
7 Return air cfm — 4250 cfm.
8
.09 inches
(Table PD-14)
Step 5 — Determine unit capacity: From Table PD-4 unit capacity at 81.5 DB. 67 WB entering the evaporator, 12000 supply air cfm, 95 F entering the condenser is 361 MBh (30.1 tons) 279 sensible MBh. Step 6 — Determine leaving air temperature: Unit sensible heat capacity, corrected for supply air fan motor heat 279 - 20.6 = 258.4 MBh. Supply air dry bulb temperature difference = 258.4 MBh ÷ (1.085 x 12,000 cfm) = 19.8 F. Supply air dry bulb: 81.5 - 19.8 = 61.7.
1.50 inches
Btu/lb leaving enthalpy = h (ent WB) = 31.62
Step 3 — Determine evaporator coil entering air conditions. Mixed air dry bulb temperature determination.
Aluminized heat exchanger — high heat module.
Approximate wet bulb mixture temperature:
Unit accessories include:
Capacity = 321 + 18.23 + 20.6 = 359.8 MBh (30 tons)
Unit enthalpy difference = 361 ÷ (4.5 x 12,000) = 6.7
a
9
From Figure SP-1, the supply air fan motor heat for 7.27 bhp = 20.6 MBh.
.076 inches
Using the minimum percent of OA (1,200 cfm ÷ 12,000 cfm = 10 percent), determine the mixture dry bulb to the evaporator. RADB + %OA (OADB RADB) = 80 + (0.10) (95 - 80) = 80 + 1.5 = 81.5F
Outside air ventilation cfm and load — 1200 cfm and 18.23 MBh (1.52 tons).
A psychrometric chart can be used to more accurately determine the mixture temperature to the evaporator coil.
Leaving enthalpy = 31.62 Btu/lb 6.7 Btu/lb = 24.9 Btu/lb. From Table PD-1, the leaving air wet bulb temperature corresponding to an enthalpy of 24.9 Btu/lb = 57.5. Leaving air temperatures = 61.7 DB/57.5 WB
RAWB + OA (OAWB - RAWB) = 66 + (0.10) (76-66) = 68 + 1 = 67 F.
RT-PRC007-EN
13
Selection Procedure
Heating capacity selection:
1 Winter outdoor design conditions—5 F.
2 Total return air temperature — 72 F.
3 Winter outside air minimum ventilation load and cfm — 1,200 cfm and 87.2 MBh.
4 Peak heating load 225 MBh. Utilizing unit selection in the cooling capacity procedure. Mixed air temperature = RADB + %O.A. (OADB - RADB) = 72 + (0.10) (0-72) = 64.8 F. Supply air fan motor heat temperature rise = 20,600 BTU ÷ (1.085 x 12,000) cfm = 1.6 F. Mixed air temperature entering heat module = 64.8 + 1.6 = 66.4 F. Total winter heating load = peak heating + ventilation load - total fan motor heat = 225 + 87.2 - 20.6 = 291.6 MBh.
Electric Heating System Unit operating on 480/60/3 power supply. From Table PD-9, kw may be selected for a nominal 30-ton unit operating on 480volt power. The high heat module — 90 KW or 307 MBh will satisfy the winter heating load of 291.6 MBh.
60 Hz
Table PD-9 also shows an air temperature rise of 23.6 F for 12,000 cfm through the 90 kw heat module. Unit supply temperature at design heating conditions = mixed air temperature + air temperature rise = 66.4 + 23.6 = 90 F.
Natural Gas Heating System Assume natural gas supply — 1000 Btu/ ft3. From Table PD-11, select the high heat module (486 MBh output) to satisfy 291.6 at unit cfm. Table PD-11 also shows air temperature rise of 37.3 F for 12,000 cfm through heating module.
The supply air fan motor selected in the previous cooling capacity determination example was 7.27 bhp with 652 rpm. Thus, the supply fan motor selected is 7.5 hp. To select the drive, enterTable PD-15 for a 30-ton unit. Select the appropriate drive for the applicable rpm range. Drive selection letter C with a range of 650 rpm, is required for 652 rpm. Where altitude is significantly above sea level, use Table PD-2 and PD-3, and Figure PD1 for applicable correction factors.
Unit Electrical Requirements
Unit supply temperature design heating conditions = mixed air temperature + air temperature rise = 66.4 + 37.3 = 103.7 F.
Selection procedures for electrical requirements for wire sizing amps, maximum fuse sizing and dual element fuses are given in the electrical service selection of this catalog.
Air Delivery Procedure
Unit Designation
Supply air fan bhp and rpm selection. Unit supply air fan performance shown in Table PD-12 includes pressure drops for dampers and casing losses. Static pressure drops of accessory components such as heating systems, and filters if used, must be added to external unit static pressure for total static pressure determination.
After determining specific unit characteristics utilizing the selection procedure and additional job information, the complete unit model number can be developed using the model number nomenclature page.
B STANDARD MOTOR C HIGH EFFICIENCY MOTOR
Figure SP-1 — Fan Motor Heat 120 110 100
H B M 90 T 80 A E H 70 R O 60 T O 50 M N 40 A F 30 20 10
0 0
5
10
15
20
25
30
35
40
MOTOR BRAKE HORSE POWER
14
RT-PRC007-EN
Selection Procedure
Selection of Trane commercial air conditioners is divided into five basic areas: 1 Cooling capacity 2 Heating capacity 3 Air delivery 4 Unit electrical requirements 5 Unit designation
Factors Used In Unit Cooling Selection: 1 Summer design conditions – 95 DB/ 76 WB (35/24.4°C), 95°F (35°C) entering air to condenser. 2 Summer room design conditions – 76 DB/66 WB (24.4/18.9°C). 3 Total peak cooling load – 270 MBh (79 kW) (22.5 tons). 4 Total peak supply cfm – 10,000 cfm (4720 L/s). 5 External static pressure – 1.0 inches wc (249 Pa). 6 Return air temperatures – 80 DB/66°F WB (26.7/18.9°C). 7 Return air cfm – 3540 cfm (1671 L/s). 8 Outside air ventilation cfm and load – 1000 cfm and 15.19 MBh (1.27 tons or 4.45 kW) 472 L/s. 9 Unit accessories include: a Aluminized heat exchanger – high heat module. b 2” Hi-efficiency throwaway filters. c Exhaust fan. d Economizer cycle.
RT-PRC007-EN
50 Hz
Step 1 – A summation of the peak cooling load and the outside air ventilation load shows: 22.5 tons + 1.27 tons = 23.77 (79 kW + 4.45 kW = 83.45) required unit capacity. FromTable PD-18, 25 ton (89 kW) unit capacity at 80 DB/67 WB (27/ 19°C), 95°F entering the condenser and 10,000 total peak supply cfm (4720 L/s), is YC/TC/TE*305.
Step 4 – Determine total required unit cooling capacity: Required capacity = total peak load + O.A. load + supply air fan motor heat.
Step 2 – Having selected the correct unit, the supply fan and exhaust fan motor bhp must be determined.
Step 5 – Determine unit capacity: FromTable PD-18 unit capacity at 81.5 DB/67 WB entering the evaporator, 10,000 supply air cfm, 95°F (35°C) entering the condenser about 304 MBh (89 kW) with 235 MBh (68.8 kW) sensible.
Supply Air Fan: Determine unit static pressure at design supply cfm: External static pressure 1.24 inches (310 Pa) Heat exchanger (Table PD-27) .12 inches (30 Pa) High efficiency filter 2” (25 mm) (Table PD-27) .07 inches (17 Pa) Economizer (Table PD-27) .07 inches (17 Pa) Unit total static pressure 1.50 inches (374 Pa) Using total cfm of 10,000 (4720 L/s) and total static pressure of 1.50 inches (38 mm), enterTable PD-25.Table PD-25 shows 5.35 bhp (4 kW) with 616 rpm.
Step 3 – Determine evaporator coil entering air conditions. Mixed air dry bulb temperature determination. Using the minimum percent of OA (1,000 cfm ÷ 10,000 cfm = 10 percent), determine the mixture dry bulb to the evaporator. RADB + % OA (OADB - RADB) = 80 + (0.10) (95 - 80) = 80 + 1.5 = 81.5°F [26.7 + 1.5 = 28°C).
From Chart SP-1, the supply air fan motor heat for 5.35 bhp = 15 MBh. Capacity = 270 + 15 + 15 = 300 MBh (89 kW)
Step 6 – Determine leaving air temperature: Unit sensible heat capacity, corrected for supply air fan motor heat 235 - 15 = 220 MBh (64.4 kW). Supply air dry bulb temperature difference = 220 MBh ÷ (1.085 x 10,000 cfm) = 20.2°F (-6.6°C) Supply air dry bulb: 81.5-20.2 = 61.3 (16.3°C) Unit enthalpy difference = 305.6 ÷ (4.5 x 10,000) = 6.76 Btu/lb leaving enthalpy = h (ent WB) = 31.62 Leaving enthalpy = 31.62 Btu/lb 6.76 Btu/lb = 24.86 Btu/lb. From Table PD-1, the leaving air wet bulb temperature corresponding to an enthalpy of 24.8 Btu/lb = 57.5. Leaving air temperatures = 61.3 DB/57.5 WB (16.3/14.2°C).
Approximate wet bulb mixture temperature: RAWB + OA (OAWB - RAWB) = 66 + (0.10) (76-66) = 68 + 1 = 67°F. A psychrometric chart can be used to more accurately determine the mixture temperature to the evaporator coil.
15
Selection Procedure
1 Winter outdoor design conditions – 0°F (17.7°C). 2 Total return air temperature – 72°F (22.2°C). 3 Winter outside air minimum ventilation load and cfm – 1,000 cfm and 87.2 MBh. 4 Peak heating load 150 MBh. Utilizing unit selection in the cooling capacity procedure. Mixed air temperature = RADB + % O.A. (OADB - RADB) = 72 + (0.10) (0-72) = 64.8°F. Supply air fan motor heat temperature rise = 20,600 Btu ÷ (1.085 x 10,000) cfm = 1.9°F. Mixed air temperature entering heat module = 64.8 + 1.9 = 66.7°F. Total winter heating load = peak heating + ventilation load - total fan motor heat = 150 + 87.2 - 15 = 222.2 MBh.
Electric Heating System Unit operating on 415 power supply. FromTable PD-22, kW may be selected forTC*305 unit to satisfy the winter heating load.The 67 kW module will do the job.
16
Table PD-22 also shows an air temperature rise of 21.2°F for 10,000 cfm through the 67 kW heat module. Unit supply temperature at design heating conditions = mixed air temperature + air temperature rise = 66.7 + 21.2 = 87.9°F.
Natural Gas Heating System Assume natural gas supply – 1000 Btu/ft3. From Table PD-24, select the low heat module (243 MBh output) to satisfy 222 at unit cfm. Table PD-25 also shows air temperature rise of 37.3°F for 10,000 cfm through heating module. Unit supply temperature design heating conditions = mixed air temperature + air temperature rise = 66.7 + 37.3 = 104.0°F.
Air Delivery Procedure Supply air fan bhp and rpm selection. Unit supply air fan performance shown in Table PD-25 includes pressure drops for dampers and casing losses. Static pressure drops of accessory components such as heating systems, and filters if used, must be added to external unit static pressure for total static pressure determination.
50 Hz
To select the drive, enterTable PD-28 for a 305 unit. Select the appropriate drive for the applicable rpm range. Drive selection letter E with a range of 625 rpm, is required for 616 rpm. Where altitude is significantly above sea level, useTable PD-2 and PD-3, and Figure PD-1 for applicable correction factors.
Unit Electrical Requirements Selection procedures for electrical requirements for wire sizing amps, maximum fuse sizing and dual element fuses are given in the electrical service selection of this catalog. Unit Designation After determining specific unit characteristics utilizing the selection procedure and additional job information, the complete unit model number can be developed using the model number nomenclature page.
The supply air fan motor selected in the previous cooling capacity determination example was 5.35 bhp with 616 rpm. Thus, the supply fan motor selected is 7.5 hp.
RT-PRC007-EN
Model Number Description
YC 12
D 3
480 456
A 7
4 8
H 9
A 1 10 11
A 4 12 13
F 14
D 1 A 15 16 17
60 Hz
0 0 0 0 0 0 0 18 19 20 21 22 23 24
Digit 1, 2 — Unit Function
Digit 13 — Supply Fan Motor, HP
TC = DX Cooling, No Heat TE = DX Cooling, Electric Heat YC = DX Cooling, Natural Gas Heat
1 = 7.5 Hp Std. Eff. 2 = 10 Hp Std. Eff. 3 = 15 Hp Std. Eff. 4 = 20 Hp Std. Eff. 5 = 7.5 Hp Hi. Eff. 6 = 10 Hp Hi. Eff. 7 = 15 Hp Hi. Eff. 8 = 20 Hp Hi. Eff.
Digit 3 — Unit Airflow Design D = Downflow Configuration H = Horizontal Configuration
Digit 4, 5, 6 — Nominal Cooling Capacity 330 = 27½ Tons 360 = 30 Tons 420 = 35 Tons 480 = 40 Tons 600 = 50 Tons
Digit 7 — Major Development Sequence A = First
Digit 8 — Power Supply (See Note 1) E = 208/60/3 F = 230/60/3 4 = 460/60/3 5 = 575/60/3
Digit 9 — Heating Capacity (See Note 4) 0 L H J
= = = =
No Heat (TC only) Low Heat (YC only) High Heat (YC only) Low Heat-Stainless Steel Gas Heat Exchangers (YC only) K = High Heat-Stainless Steel Gas Heat Exchanger (YC only) Note: When second digit is “E” for Electric Heat, the following values apply in the ninth digit. A = 36 KW B = 54 KW C = 72 KW D = 90 KW E = 108 KW
= = = = = = =
550 RPM 600 RPM 650 RPM 700 RPM 750 RPM 790 RPM 800 RPM
H = J = K = L = M= N =
1 = Constant Volume 2 = VAV Supply Air Temperature Control w/o Inlet Guide Vanes 3 = VAV Supply Air Temperature Control w/Inlet Guide Vanes 4 = VAV Supply Air Temperature Control w/Variable Frequency Drive w/o Bypass 5 = VAV Supply Air Temperature Control w/Variable Frequency Drive and Bypass Note: Zone sensors are not included with option and must be ordered as a separate accessory.
500 RPM 525 RPM 575 RPM 625 RPM 675 RPM 725 RPM
Digit 15 — Fresh Air Selection A B C D
= = = =
E = F = G = H =
0 0 05 27 28 29
Digit 16 — System Control
Digit 14 — Supply Air Fan Drive Selections (See Note 3) A B C D E F G
0 0 25 26
No Fresh Air 0-25% Manual Damper 0-100% Economizer, Dry Bulb Control 0-100% Economizer, Reference Enthalpy Control 0-100% Economizer, Differential Enthalpy Control “C” Option and Low Leak Fresh Air Damper “D” Option and Low Leak Fresh Air Damper “E” Option and Low Leak Fresh Air Damper
Digit 17 - 29 — Miscellaneous A = Service Valves (See Note 2) B = Through the Base Electrical Provision C = Non-Fused Disconnect Switch with External Handle D = Factory-Powered 15A GFI Convenience Outlet and Non-Fused Disconnect Switch with External Handle E = Field-Powered 15A GFI Convenience Outlet F = Trane Communication Interface (TCI) H = Hinged Service Access J = Condenser Coil Guards K = LCI (LonTalk) L = Special M = Stainless Steel Drain Pans N = Black Epoxy Coated Condenser Coil P = Discharge Temperature Sensor R = Clogged Filter Switch
Digit 10 Design Sequence A = First
Digit 11 — Exhaust 0 = None 1 = Barometric Relief (Available w/Economizer only) 2 = Power Exhaust Fan (Available w/Economizer only)
Digit 12 — Filter A = Standard 2” Throwaway Filters B = High Efficiency 2” Throwaway Filters C = High Efficiency 4” Throwaway Filters
Notes: 1. All voltages are across the line starting only. 2. Option includes Liquid, Discharge, Suction Valves. 3. Supply air fan drives A thru G are used with 27½-35 ton units only and drives H thru N are used with 40 & 50 ton units only. 4. Electric Heat KW ratings are based upon voltage ratings of 240/480/600 V. Voltage offerings are as follows (see table PD-9 for additional information):
Tons 27½ to 35 40 and 50
Voltage 240 480 600 240 480 600
36 x x
54 x x x x x x
KW 72
90
x x
x x
x x
x x
108
x x
5. The service digit for each model number contains 29 digits; all 29 digits must be referenced.
RT-PRC007-EN
17
Model Number Description
YC
D
500
A
C
H
A
12
3
456
7
8
9
10 11
Digits 1, 2 – Unit Function TC = DX Cooling, No Heat TE = DX Cooling, Electric Heat YC = DX Cooling, Natural Gas Heat Digit 3 – Unit Airflow Design D = Downflow Configuration H = Horizontal Configuration Digits 4, 5, 6 – Nominal Cooling Capacity 275 = 22.9Tons (82 kW) 305 = 25.4Tons (89 kW) 350 = 29.2Tons (105 kW) 400 = 33.3 Tons (120 kW) 500 = 41.7 Tons (148 kW) Digit 7 – Major Development Sequence A = First B = Second, Etc. Digit 8 – Power Supply (See Note 1) C = 380/50/3 D = 415/50/3 Digit 9 – Heating Capacity (See Note 4) 0 = No Heat (TC only) L = Low Heat (YC only) H = High Heat (YC only) Note: When second digit is “E” for Electric Heat, the following values apply in the ninth digit. 380V / 415V A = 23 27 kW B = 34 40 kW C = 45 54 kW D = 56 67 kW E = 68 81 kW Digit 10 – Design Sequence A = First
1
A
4
12 13
F
D
1
A
14
15 16 17
50 Hz
0
0
0
0
0
0
0
18 19 20 21 22 23 24
Digit 11 – Exhaust 0 = None 1 = Barometric Relief (Available w/Economizer only) 2 = Power Exhaust Fan (Available w/Economizer only) Digit 12 – Filter A = Standard 2” (51 mm) Throwaway Filters B = High Efficiency 2” (51 mm) Throwaway Filters C = High Efficiency 4” (102 mm) Throwaway Filters Digit 13 – Supply Fan Motor, HP 1 = 7.5 Hp Std. Eff. (5.6 kW) 2 = 10 Hp Std. Eff. (7.5 kW) 3 = 15 Hp Std. Eff. (11.2 kW) 4 = 20 Hp Std. Eff. (14.9 kW) Digit 14 – Supply Air Fan Drive Selections (See Note 3) A = 458 H = 417 B = 500 J = 437 C = 541 K = 479 D = 583 L = 521 E = 625 M = 562 F = 658 N = 604 G = 664 Digit 15 – Fresh Air Selection A = No Fresh Air B = 0-25% Manual Damper C = 0-100% Economizer, Dry Bulb Control D = 0-100% Economizer, Reference Enthalpy Control E = 0-100% Economizer, Differential Enthalpy Control F = “C” Option and Low Leak Fresh Air Damper G = “D” Option and Low Leak Fresh Air Damper H = “E” Option and Low Leak Fresh Air Damper
0
0
25 26
0
0
05
27 28 29
Digit 16 – System Control 1 = Constant Volume 2 = VAV Supply AirTemperature Control w/o Inlet Guide Vanes 3 = VAV Supply AirTemperature Control w/Inlet Guide Vanes Note: Zone sensors are not included with option and must be ordered as a separate accessory. Digit 17-29 – Miscellaneous A = Service Valves (See Note 2) B = Through the Base Electrical Provision C = Non-Fused Disconnect Switch with External Handle D = Factory-Powered 15A GFI Convenience Outlet and Non-Fused Disconnect Switch with External Handle E = Field-Powered 15A GFI Convenience Outlet F = Trane Communication Interface (TCI) G = Ventilation Override H = Hinged Service Access J = Condenser Coil Guards K = Special L = Special M = Stainless Steel Drain Pans N = Black Epoxy Coated Condenser Coil P = Discharge Temperature Sensor R = Clogged Filter Switch
Notes: 1. All voltages are across-the-line starting only. 2. Option includes Liquid, Discharge, Suction Valves. 3. Supply air fan drives A thru G are used with 22.9-29.2 ton (82-105 kW) units only and drives H thru N are used with 33.3 and 41.7 ton (120-148 kW) units only. 4. Electric Heat kW ratings are based upon voltage ratings of 380/415 V. Heaters A, B, C, D are used with 22.9-29.2 ton (82105 kW) units only and heaters B, C, D, E are used with 33.3-41.7 ton (1 20-148 kW) units only. 5. The service digit for each model number contains 29 digits; all 29 digits must be referenced.
18
RT-PRC007-EN
General Data
60 Hz
Table GD-1 — General Data — 27½ - 30 Tons 27½Ton Cooling Performance1 Nominal Gross Capacity Natural Gas Heat2 Heating Input (BTUH) First Stage Heating Output (BTUH) First Stage Steady State Efficiency (%)3 No. Burners No. Stages Gas Supply Pressure (in. w.c.) Natural or LP (minimum/maximum) Gas Connection Pipe Size (in.) Electric Heat KW Range5 Capacity Steps: Compressor Number/Type Size (Nominal) Unit Capacity Steps (%) Motor RPM Outdoor Coil — Type Tube Size (in.) OD Face Area (sq. ft.) Rows/Fins Per Inch Indoor Coil — Type Tube Size (in.) OD Face Area (sq. ft.) Rows/Fins Per Foot Refrigerant Control No. of Circuits Drain Connection No./Size (in) Type Outdoor FanType No. Used/Diameter DriveType/No. Speeds CFM No. Motors/HP/RPM Indoor Fan Type No. Used Diameter/Width (in) DriveType/No. Speeds No. Motors/HP Motor RPM Motor Frame Size Exhaust FanType No. Used/Diameter (in) DriveType/No. Speeds/Motors Motor HP/RPM Motor Frame Size Filters — Type Furnished No./ Recommended Size (in)6 Refrigerant Charge (Lbs of R-22)4 Minimum Outside Air Temperature For Mechanical Cooling
30Ton
329,000
363,000
Low 350,000 250,000 283,500 202,500 81.00 1 2
High 600,000 425,000 486,000 344,500 81.00 2 2
Low 350,000 250,000 283,500 202,500 81.00 1 2
High 600,000 425,000 486,000 344,500 81.00 2 2
2.5/14.0 3 / 4
2.5/14.0 1
2.5/14.0 3 / 4
2.5/14.0 1
27-905 2
27-905 2
2/Scroll 10/15 100/40 3450 Lanced 3 / 8 51.33 2/16 Hi-Performance 1 / 2 31.67 2/180 TXV 1 1/1.25 PVC Propeller 3/28.00 Direct/1 24,800 3/1.10/1125 FC 1 22.38/22.00 Belt/1 1/7.50/10.00 1760 213/215T Propeller 2/26.00 Direct/2/2 1.0/1075 48 Throwaway 16/16 x 20 x 2 46.00
2/Scroll 15 100/50 3450 Lanced 3 / 8 51.33 2/16 Hi-Performance 1 / 2 31.67 2/180 TXV 1 1/1.25 PVC Propeller 3/28.00 Direct/1 24,800 3/1.10/1125 FC 1 22.38/22.00 Belt/1 1/7.50/10.00 1760 213/215T Propeller 2/26.00 Direct/2/2 1.0/1075 48 Throwaway 16/16 x 20 x 2 46.60
0F
0F
Notes: 1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. Rated and tested in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93. 2. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 4,500 feet. 3. Steady State Efficiency is rated in accordance with DOE test procedures. 4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. 5. Maximum KW @ 208V = 41, @ 240V = 54. For Electric heat KW range per specific voltage, see table PD-10. 6. Filter dimensions listed are nominal. For actual filter and rack sizes see the Unit Installation, Operation, Maintenance Guide.
RT-PRC007-EN
19
General Data
60 Hz
Table GD-2— General Data — 35-40 Ton 35Ton Cooling Performance1 Nominal Gross Capacity Natural Gas Heat2 Heating Input (BTUH) First Stage Heating Output (BTUH) First Stage Steady State Efficiency (%)3 No. Burners No. Stages Gas Supply Pressure (in. w.c.) Natural or LP (minimum/maximum) Gas Connection Pipe Size (in.) Electric Heat KW Range5 Capacity Steps: Compressor Number/Type Size (nominal) Unit Capacity Steps (%) Motor RPM Outdoor Coil — Type Tube Size (in.) OD Face Area Rows/Fins Per Inch Indoor Coil — Type Tube Size (in.) OD Face Area (sq. ft.) Rows/Fins Per Foot Refrigerant Control No. of Circuits Drain Connection No./Size (in) Type Outdoor Fan Type No. Used/Diameter DriveType/No. Speeds CFM No. Motors/HP/RPM Indoor FanType No. Used Diameter/Width (in) DriveType/No. Speeds No. Motors/HP Motor RPM Motor Frame Size Exhaust FanType No. Used/Diameter (in) DriveType/No. Speeds/Motors Motor HP/RPM Motor Frame Size Filters — Type Furnished No./Recommended Size (in)6 Refrigerant Charge (Lbs of R-22)4 Minimum Outside Air Temperature For Mechanical Cooling
40Ton
417,000
513,000
Low 350,000 250,000 283,500 202,500 81.00 1 2
High 600,000 425,000 486,000 344,500 81.00 2 2
Low 400,000 300,000 324,000 243,000 81.00 1 2
High 800,000 600,000 648,000 486,000 81.00 2 2
2.5/14.0 3 / 4
2.5/14.0 1
2.5/14.0 3 / 4
2.5/14.0 1
27-905 2
41-1085 2
2/Scroll 15 100/50 3450 Lanced 3 / 8 51.33 2/16 Hi-Performance 1 / 2 31.67 3/180 TXV 1 1/1.25 PVC Propeller 3/28.00 Direct/1 24,800 3/1.10/1125 FC 1 22.38/22.00 Belt/1 1/7.50/10.00/15.00 1760 213/215/254T Propeller 2/26.00 Direct/2/2 1.0/1075 48 Throwaway 16/16 x 20 x 2 51.50
3/Scroll 15/15/10 100/60/40 3450 Lanced 3 / 8 69.79 2/16 Hi-Performance 1 / 2 37.50 3/180 TXV 2 1/1.25 PVC Propeller 4/28.00 Direct/1 31,700 4/1.10/1125 FC 1 25.00/25.00 Belt/1 1/10.00/15.00 1760 215/254T Propeller 2/26.00 Direct/2/2 1.0/1075 48 Throwaway 17/16 x 20 x 2 26.00/47.10 per circuit
0F
0F
Notes: 1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. Rated and tested in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93. 2. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 4,500 feet. 3. Steady State Efficiency is rated in accordance with DOE test procedures. 4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. 5. Maximum KW @ 208V = 41, @ 240V = 54. For Electric heat KW range per specific voltage, see table PD-10. 6. Filter dimensions listed are nominal. For actual filter and rack sizes see the Unit Installation, Operation, Maintenance Guide.
20
RT-PRC007-EN
General Data
Table GD-3— General Data — 50 Ton
Table GD-4 — Economizer Outdoor Air Damper Leakage (Of Rated Airflow)
50Ton Cooling Performance1 Nominal Gross Capacity Natural Gas Heat2 Heating Input (BTUH) First Stage Heating Output (BTUH) First Stage Steady State Efficiency (%)3 No. Burners No. Stages Gas Supply Pressure (in. w.c.) Natural or LP (minimum/maximum) Gas Connection Pipe Size (in.) Electric Heat KW Range5 Capacity Steps: Compressor Number/Type Size (nominal) Unit Capacity Steps (%) Motor RPM Outdoor Coil — Type Tube Size (in.) OD Face Area (sq. ft.) Rows/Fins Per Inch Indoor Coil —Type Tube Size (in.) OD Face Area (sq. ft.) Rows/Fins Per Foot Refrigerant Control No. of Circuits Drain Connection No./Size (in) Type Outdoor FanType No. Used/Diameter DriveType/No. Speeds CFM No. Motors/HP/RPM Indoor FanType No. Used Diameter/Width (in) DriveType/No. Speeds No. Motors/HP Motor RPM Motor Frame Size Exhaust FanType No. Used/Diameter (in) DriveType/No. Speeds/Motors Motor HP/RPM Motor Frame Size Filters — Type Furnished No./Recommended Size (in)6 Refrigerant Charge (Lbs of R-22)4 Minimum Outside Air Temperature For Mechanical Cooling
RT-PRC007-EN
∆P Across Dampers (In. WC)
616,000 Low 400,000 300,000 324,000 243,000 81.00 1 2
High 800,000 600,000 648,000 486,000 81.00 2 2
2.5/14.0
2.5/14.0
3
/ 4
60 Hz
Standard Optional “Low Leak”
0.5 (In.) 1.5 % 0.5 %
1.0 (In.) 2.5 % 1.0 %
Note: Above data based on tests completed in accordance with AMCA Standard 575.
1 41-1085 2 3/Scroll 14 100/67/33 3450 Lanced 3 / 8 69.79 2/16 Hi-Performance 1 / 2 37.50 4/164 TXV 2 1/1.25 PVC Propeller 4/28.00 Direct/1 31,700 4/1.10/1125 FC 1 25.00/25.00 Belt/1 1/10.00/15.00/20.00 1760 215/254/256T Propeller 2/26.00 Direct/2/2 1.0/1075 48 Throwaway 17/16 x 20 x 2 25.70/54.30 per circuit 0F
Notes: 1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. Rated and tested in accordance with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93. 2. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 4,500 feet. 3. Steady State Efficiency is rated in accordance with DOE test procedures. 4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. 5. Maximum KW @ 208V = 41, @ 240V = 54. For Electric heat KW range per specific voltage, see table PD-10. 6. Filter dimensions listed are nominal. For actual filter and rack sizes see the Unit Installation, Operation, Maintenance Guide.
21
General Data
50 Hz
Table GD-5 – General Data – 23-25 Tons
Cooling Performance1 Nominal Gross Capacity - Btu (kW) System Power - kW Compressor Number/Type Size (Nominal Tons) Unit Capacity Steps (%) Motor rpm Natural Gas Heat2 Heating Input - Btu (kW) First Stage Heating Output - Btu (kW) First Stage Steady State Efficiency(%) 3 No. Burners/No. Stages Gas Connect Pipe Size - in. (mm) Outdoor Coil - Type Tube Size OD - in. (mm) Face Area - sq ft (sq m) Rows/Fins Per Inch Indoor Coil - Type-Performance Tube Size OD - in. (mm) Face Area - sq ft (sq m) Rows/Fins Per Foot Refrigerant Control PVC Drain Connect No./Size - in. (mm) Outdoor Fan Type No. Used Diameter - in. (mm) DriveType/No. Speeds cfm ( L/s) No. Motors (rpm) Motor- hp (kW) Indoor Fan Type/No. Used Diameter - in. (mm) Width - in. (mm) DriveType No. Speeds/No. Motors Motor - hp (kW) Motor rpm/Frame Size Filters - Type Furnished/No. Recommended Size - in. (mm) Refrigerant Type Factory Charge - lb (kg) 4
TC/YC/TE*275 (23Tons)
TC/YC/TE*305 (25Tons)
277,000 (81.1) 24.9
303,000 (88.7) 28.6 kW
2/Scroll 10/15 100/40 2875
2/Scroll 15/15 100/50 2875
Low 290,000 (85.0) 250,000 (73.3 kW) 243,000 (69.0) 202,500 (59.4 kW)
High 500,000 (147) 425,000 (125 kW) 405,000 (119) 344,250 (101 kW)
81 1/2 0.75 (19) Lanced 0.375 (10) 51.3 (4.8) 2/16 Hi Performance 0.500 (13) 31.7 (2.9) 2/180 TXV 1/1.25 (1/32) Propeller 3 28.0 (711) Direct/1 20,450 (9650) 3 (940) 0.75 (0.56) FC/1 22.4 (568) 22.0 (559) Belt 1/1 7.5 (5.6) 1460/213T Throwaway Yes/16 16X 20 X2 (406X 508 X51)
Low 290,000 (85.0) 250,000 (73.3 kW) 243,000 (69.0) 202,500 (59.4 kW)
High 500,000 (147) 425,000 (125 kW) 405,000 (119) 344,250 (101 kW)
81 1/2 0.75 (19) Lanced 0.375 (10) 51.3 (4.8) 2/16 Hi Performance 0.500 (13) 31.7 (2.9) 2/180 TXV 1/1.25 (1/32) Propeller 3 28.0 (711) Direct/1 20,450 (9650) 3 (940) 0.75 (0.56)
FC/1
22.4 (568) 22.0 (559) Belt 1/1 7.5 (5.6) 1460/213T Throwaway Yes/16 16x20x2 (406X 508x51)
R-22
R-22
44.5 (20.2)
45 (20.4)
Notes: 1. Cooling Performance is rated at 95°F (35°C) ambient, 80°F (27°C) entering dry bulb, 67°F (19°C) entering wet bulb. Gross capacity does not include the effect of fan motor heat. 2. Heating Performance Limit settings and ratings data were established and approved under laboratory test conditions using American National Standards. 3. Steady State Efficiency is rated in accordance with DOE test procedures. 4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
22
RT-PRC007-EN
General Data
50 Hz
Table GD-6 – General Data – 29-33 Tons
Cooling Performance1 Nominal Gross Capacity(Btu) System Power - kW Compressor Nu Number/Type Size (Nominal Tons) Unit Capacity Steps (%) Mo M otor rpm Natural Gas Heat2 Heating Input - Btu (kW) First Stage Heating Output - Btu (kW) First Stage Steady State Efficiency(%)3 No. Burners/No. Stages Gas Connect Pipe Size - in. (mm) Outdoor Coil - Type Tube Size OD - in. (mm) Face Area - sq ft (sq m) Rows/Fins Per Inch Indoor Coil - Type Tube Size - in. (mm) OD Face Area - sq ft (sq m) Rows/Fins Per Foot Re R efrigerant Control PVC Drain Connect No./Size - in. (mm) Outdoorr Fan Type Outdoo No. Used Diameter - in. (mm) DriveType/No. Speeds cf c fm (L/s) No. Motors (rpm) Motor - hp (kW) Indoor Fan Type/No. Used Us ed Diameter - in. (mm) Width - in. (mm) DriveType No. Speeds/No. Motors Motor - hp (kW) Motor rpm/Frame Size Filters - Type Furnished/No. Recommended Size - in. (mm) Refrigerant Type Factory Charge Ciruit 1 - lb lb (kg) 4 Factory Charge Circuit 2 - lb (kg)
TC/YC/TE*350 (29Tons)
TC/YC/TE*400 (33Tons)
353,000 (103.4 kW) 32.55
435,000 (127.4 kW) 42.6
2/Scroll 15/15 100/50 2875
3/Scroll 15/15/10 100/60/40 2875
Low 290,000 (85.0) 250,000 (73.3 kW) 243,000 (69.0) 202,500 (59.4 kW)
High 500,000 (147) 425,000 (125 kW) 405,000 (119) 344,250 (101 kW)
81 1/2 0.75 (19) Lanced 0.375 (10) 51.3 (4.8) 2/16 Hi-Performance 0.500 (13) 31.7 (2.9) 2/180 TXV 1/1.25 (1/32) Propeller 3 28.0 (711) Direct/1 20,400 (9650) 3 (940) 0.75 (0.56) FC/1 22.4 (568) 22.0 (559) Belt 1/1 7.5 (5.6) 1460/213T Throwaway Yes/16 16x20x2 (406x508x51)
Low 335,000 (98.2) 300,000 (87.9 kW) 271,350 (80.0) 243,500 (71.4 kW)
High 670,000 (196) 600,000 (176 kW) 542,700 (159) 486,000 (166 kW)
81 1/2 0.75 (19) Lanced 0.375 (10) 69.8 (6.5) 2/16 Hi-Performance 0.500 (13) 37.5 (3.5) 3/180 TXV 1/1.25 (1/32) Propeller 4 28.0 (711) Direct/1 26,200 (12,400) 4 (940) 0.75 (0.56) FC/1 25.0 (635) 25.0 (635) Belt 1/1 10.0 (7.5) 1460/215T Throwaway Yes/17 16X 20 X2 (406X 508 X51)
R-22
R-22
50 (22.7) –
26.4 (12) 47.8 (21.7)
Notes: 1. Cooling Performance is rated at 95°F (35°C) ambient, 80°F (27°C) entering dry bulb, 67°F (19°C) entering wet bulb. Gross capacity does not include the effect of fan motor heat. 2. Heating Performance Limit settings and ratings data were established and approved under laboratory test conditions using American National Standards. 3. Steady State Efficiency is rated in accordance with DOE test procedures. 4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
RT-PRC007-EN
23
General Data
50 Hz
Table GD-7 – General Data – 43 Tons TC/YC/TE*500 (42Tons) Cooling Performance 1 Nominal Gross Capacity - Btu (kW) System Power - kW Compressor Nu Number/Type Size (Nominal Tons) Unit Capacity Steps (%) Motor rpm Natural Gas Heat2 Heating Input - Btu (kW) First Stage Heating Output - Btu (kW) First Stage Steady State Efficiency(%)3 No. Burners/No. Stages Gas Connect Pipe Size - in. (mm) Outdoor Coil - Type Tube Size OD - in. (mm) Face Area - sq ft (sq m) Rows/Fins Per Inch Indoor Coil - Type Tube Size OD - in. (mm) Face Area - sq ft (sq m) Rows/Fins Per Foot Refrigerant Control PVC Drain Connect No./Size - in. (mm) Outdoorr Fan Type Outdoo No. Used Diameter - in. (mm) DriveType/No. Speeds cfm (L/s) No. Motors (rpm) Motor - hp (kW) Indoor Fan Type/No. Used Diameter - in. (mm) Width - in. (mm) DriveType No. Speeds/No. Motors Motor hp Motor rpm/Frame Size Filters - Type Type Fu Furnished/No. Recommended Size - in. (mm) Refrigerant Type Factory Charge Circuit 1 - lb (kg) 4 Factory Charge Circuit 1 - (kg)
520,000 (152) 50.9 3/Scroll 14/14/14 100/67/33 2875 Low 335,000 (98.2) 300,000 (87.9 kW) 271,350 (79.5) 243,500 (71.4 kW)
High 670,000 (196) 600,000 (176 kW) 542,700 (159) 486,000 (166 kW)
81 1/2 0.75 (19) Lanced 0.375 (10) 69.8 (6.5) 2/16 Hi-Performance 0.500 (13) 37.5 (3.5) 4/164 TXV 1/1.25 (1/32) Propeller 4 28.0 (711) Direct/1 26,200 (12,400) 4 (940) 0.75 (0.56) FC/1 25.0 (635) 25.0 (635) Belt 1/1 10.0 (7.5 kW) 1460/215T Throwaway Yes/17 16x20x2 (406x508x51) R-22 26.0 (11 (11.8) .8) 53.2 (24.1)
Notes: 1. Cooling Performance is rated at 95°F (35°C) ambient, 80°F (27°C) entering dry bulb, 67°F (19°C) entering wet bulb. Gross capacity does not include the effect of fan motor heat. 2. Heating Performance Limit settings and ratings data were established and approved under laboratory test conditions using American National Standards. 3. Steady State Efficiency is rated in accordance with DOE test procedures. 4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
Table GD-8 – Economizer Outdoor Air Damper Leakage (Of Rated Airflow)
St S tandard Optional “Low Leak”
∆P Across Dampers (In. wc) (Pa) 0.5 In. (124.5 Pa) 1.0 In. (249 Pa) 1.5% 2.5% 0.5% 1.0%
Note: Above data based on tests completed in accordance with AMCA Standard 575.
24
RT-PRC007-EN
Performance Adjustment Factors
Table PD-1 – Enthalpy of Saturated Air Wet Bulb Temperature °F °C 40 4.4 41 5.0 42 5.5 43 6.1 44 6.7 45 7.2 46 7.8 47 8.3 48 8.9 49 9.4 50 10.0 51 10.6 52 11.1 53 11.7 54 12.2 55 12.8 56 13.3 57 13.9 58 14.4 59 15.0 60 15.6 61 16.1 62 16.7 63 17.2 64 17.8 65 18.3 66 18.9 67 19.4 68 20.0 69 20.6 70 21.1 71 21.7 72 22.2 73 22.8 74 23.3 75 23.9
Figure PD-1 – Air Density Ratios
Btu Per lb 15.23 15.70 16.17 16.66 17.15 17.65 18.16 18.68 19.21 19.75 20.30 20.86 21.44 22.02 22.62 23.22 23.84 24.48 25.12 25.78 26.46 27.15 27.85 28.57 29.31 30.06 30.83 31.62 32.42 33.25 34.09 34.95 35.83 36.74 37.66 38.61
Table PD-2 – Cooling Capacity Altitude Correction Factors
Cooling Capacity Multiplier KW Correction Multiplier (Compressors) SHR Correction Multiplier Maximum Condenser Ambient
Sea Level
1000 (304.8)
2000 (609.6)
3000 (914.4)
1.00
0.99
0.99
0.98
1.00
1.01
1.02
1.00
.98
115°F (4 (46.1°C)
114°F (45.6°C)
Altitude ft. (m) 4000 (1219.2)
5000 (1524.0)
6000 (1828.8)
7000 (2133.6)
0.97
0.96
0.95
0.94
1.03
1.04
1.05
1.06
1.07
.95
.93
.91
.89
.87
.85
113°F (45.0°C)
112°F (4 (44.4°C)
111°F (4 (43.9°C)
110°F (4 (43.3°C)
109°F (4 (42.8°C)
108°F (4 (42.2°C)
Note: SHR = Sensible Heat Ratio
Table PD-3 – Gas Heating Capacity Altitude Correction Factors
Capacity Multiplier
Sea Le LevelTo 20 2000 (Sea (S ea Leve LevellTo 609.6 609.6)) 1.00
2000To 2500 (609 (6 09.9 .9To 762.0 762.0)) .92
2501To 35 3500 (762 (7 62.3 .3To 1066. 1066.8) 8) .88
Altitude ft. (m) 3501To 45 4500 (106 (1 067 7.1To 16 1674 74.4 .4)) .84
4501To 55 5500 (137 (1 371 1.9To 1675. 1675.4) 4) .80
5501To 65 6500 (167 (1 676. 6.7 7 To 1981 1981.2 .2)) .76
6501To 7500 (198 (1 981 1.5To 2286. 2286.0) 0) .72
Note: Correction factors are per AGA Std 221.30 – 1964, Part VI, 6.12. Local codes may supersede.
RT-PRC007-EN
25
Performance Data
60 Hz
Table PD-4 — 27½ Ton Gross Cooling Capacities (MBh) Ambient Temperature — Deg F 95 105 Entering Wet BulbTemperature — Deg F 67 73 61 67
85 Ent DB CFM
61
67
73
61
115 73
61
73 TGC SHC
TGC SHC TGC SHC TGC SHC
75 80 85 90
291 294 301 317
228 268 301 317
323 324 325 328
185 220 258 297
358 359 360 361
130 171 210 248
278 281 290 306
221 261 290 306
309 310 311 315
174 212 251 290
343 343 344 345
123 164 203 241
265 268 278 294
213 253 278 294
295 296 297 301
167 205 243 283
327 327 329 330
116 157 196 234
251 255 266 282
206 246 266 282
279 280 282 286
159 197 236 275
310 311 312 313
109 149 188 226
75 80 85 90
299 302 314 331
242 286 314 331
331 332 334 338
189 232 275 319
367 367 368 369
133 178 221 264
285 290 302 319
235 279 302 319
316 318 319 324
182 225 268 312
351 351 352 354
126 171 215 256
272 276 290 306
227 272 290 306
301 303 305 310
175 217 260 304
334 335 336 337
119 164 208 249
257 261 277 293
219 261 277 293
286 287 289 293
168 209 252 293
316 317 319 320
112 157 201 241
75 10000 80 85 90
305 310 325 343
255 304 325 343
337 339 341 346
197 244 291 340
373 374 375 376
136 185 233 279
292 297 313 330
248 297 313 330
322 324 326 332
190 237 284 332
357 358 359 360
129 178 226 271
277 283 300 317
240 283 300 317
307 308 311 317
183 229 276 317
339 341 342 343
122 171 219 264
263 270 287 304
232 270 287 304
291 292 295 303
176 221 268 303
322 323 324 326
115 164 212 256
75 11000 80 85 90
311 316 335 353
268 316 335 353
343 344 347 353
205 255 307 353
379 380 381 383
139 192 245 293
297 304 322 340
260 304 322 340
327 329 332 340
198 248 300 340
362 363 364 366
132 185 237 286
282 291 309 327
253 291 309 327
311 191 313 240 317 292 327 327
344 345 347 349
125 178 230 278
268 278 295 313
245 278 295 313
295 297 301 312
183 232 284 312
326 327 329 331
117 170 220 270
75 12100 80 85 90
316 325 344 364
281 325 344 364
348 349 353 363
223 268 324 363
384 385 387 388
142 199 254 309
302 312 331 350
274 312 331 350
332 334 338 350
216 260 317 350
366 368 369 372
135 192 246 301
287 299 317 336
266 299 317 336
316 318 322 336
348 350 352 354
128 185 239 294
272 285 303 321
258 285 303 321
299 301 306 321
200 244 301 321
330 331 333 336
121 176 231 286
9000
208 252 309 336
TGC SHC
67
TGC SHC TGC SHC TGC SHC
8000
TGC SHC TGC SHC TGC SHC
TGC SHC
(F)
Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total gross capacity. 3. SHC = Sensible heat capacity.
Table PD-5— 30 Ton Gross Cooling Capacities (Mbh) AmbientTemperature — Deg F 95 105 Entering Wet BulbTemperature — Deg F 67 73 61 67
85 Ent DB CFM
61
67
73
61
115 73
61 TGC SHC
67
73 TGC SHC
TGC SHC TGC SHC TGC SHC
TGC SHC TGC SHC TGC SHC
75 80 85 90
323 326 335 352
255 299 335 352
358 359 361 364
207 245 288 332
397 398 399 400
144 190 234 276
309 313 323 340
247 291 323 340
343 344 346 349
194 237 280 324
380 381 382 383
137 182 227 269
295 298 310 327
239 283 310 327
327 328 330 334
186 229 272 316
362 363 364 365
129 175 219 261
279 284 297 313
230 275 297 313
310 311 313 318
178 221 264 308
344 345 345 347
122 167 210 252
75 10000 80 85 90
331 335 347 366
268 317 347 366
366 367 369 374
210 257 304 353
405 406 407 408
147 197 246 292
316 321 334 353
260 309 334 353
350 351 353 358
202 249 296 345
387 388 389 391
140 189 238 284
301 306 321 339
252 301 321 339
333 335 337 342
194 241 288 337
369 370 371 372
132 182 230 276
286 290 307 325
243 290 307 325
316 318 320 324
186 232 280 324
350 351 352 353
125 174 222 267
75 11000 80 85 90
337 343 358 378
281 335 358 378
372 374 376 382
218 269 321 374
411 412 413 415
150 204 257 306
322 328 345 364
273 327 345 364
356 357 360 367
210 261 312 366
393 394 395 397
143 196 249 298
307 312 331 350
265 312 331 350
339 340 343 349
202 252 304 349
374 375 377 378
135 188 241 290
291 298 316 335
256 298 316 335
321 323 326 334
194 244 296 334
355 356 357 359
127 180 233 282
75 12000 80 85 90
343 348 368 388
294 348 368 388
378 379 382 388
225 280 336 388
417 418 419 421
153 210 268 321
328 334 354 374
285 334 354 374
361 362 366 374
218 272 328 374
398 399 401 402
145 203 260 313
312 321 340 359
277 321 340 359
343 345 349 359
210 263 320 359
379 380 382 383
138 195 252 304
295 306 325 343
268 306 325 343
325 327 331 343
201 255 311 343
359 360 362 364
129 187 244 296
75 13200 80 85 90
349 357 378 399
308 357 378 399
383 385 389 399
246 293 354 399
422 423 425 427
156 218 278 337
333 343 364 384
300 343 364 384
366 368 372 384
238 285 346 384
403 405 406 408
149 210 270 329
317 329 349 369
291 329 349 369
348 350 355 369
229 276 338 369
383 385 387 389
141 202 261 321
300 314 333 353
283 314 333 353
329 332 337 352
221 268 329 352
363 365 366 369
133 194 253 312
9000
TGC SHC TGC SHC TGC SHC
TGC SHC
(F)
Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total gross capacity. 3. SHC = Sensible heat capacity.
26
RT-PRC007-EN
Performance Data
60 Hz
Table PD-6 — 35 Ton Gross Cooling Capacities (Mbh) Ambient Temperature — Deg F 95 105 Entering Wet BulbTemperature — Deg F 67 73 61 67
85 Ent DB CFM
(F)
61
67
73
61
115 73
61 TGC SHC
67
73
TGC SHC
TGC SHC
TGC SHC TGC SHC TGC SHC
TGC SHC TGC SHC TGC SHC
TGC SHC TGC SHC TGC SHC
75 10500 80 85 90
377 383 398 419
310 367 398 419
416 417 420 426
240 296 351 409
459 460 461 462
166 224 281 336
361 366 383 404
301 359 383 404
398 399 402 408
231 287 343 400
438 439 440 442
158 216 272 327
343 350 368 388
291 349 368 388
379 380 383 388
223 278 333 388
417 418 419 421
150 207 263 317
325 332 352 371
282 332 352 371
359 360 364 371
214 268 324 371
396 397 397 399
141 198 254 308
75 12000 80 85 90
387 393 415 437
332 393 415 437
425 427 431 437
258 315 379 437
468 469 470 472
171 236 300 361
370 378 399 421
322 378 399 421
406 408 412 421
249 306 370 421
447 448 449 451
162 227 290 352
352 362 383 404
313 362 383 404
387 388 393 404
240 297 361 404
425 426 427 430
154 218 281 342
334 346 366 386
303 346 366 386
366 368 373 386
231 288 351 386
403 404 405 408
145 209 271 333
75 13000 80 85 90
393 402 425 448
346 402 425 448
430 432 437 448
261 328 397 448
473 475 476 478
173 243 312 377
375 387 409 431
337 387 409 431
411 413 418 431
253 319 388 431
452 453 454 457
165 234 303 368
357 370 392 413
327 370 392 413
391 393 399 413
244 310 378 413
429 430 432 435
156 225 294 359
339 353 374 395
317 353 374 395
370 372 379 395
234 300 369 395
406 408 409 412
147 216 285 349
75 14000 80 85 90
398 410 434 458
360 410 434 458
435 437 443 457
270 341 414 457
478 479 480 484
176 250 324 393
380 394 417 440
351 394 417 440
415 417 423 440
261 332 405 440
456 457 458 462
167 241 315 384
362 378 400 422
341 378 400 422
395 397 404 422
252 322 396 422
433 434 436 440
159 232 306 375
343 360 381 403
331 360 381 403
373 376 381 403
243 312 381 403
410 411 413 417
150 223 297 365
75 14400 80 85 90
400 413 437 461
365 413 437 461
436 439 445 461
272 346 421 461
479 481 482 486
177 253 326 400
382 397 420 443
356 397 420 443
416 419 426 443
263 336 412 443
457 459 460 464
168 244 317 390
364 380 402 425
346 380 402 425
396 399 406 425
254 327 402 425
434 436 437 442
160 235 308 381
345 363 384 406
337 363 384 406
375 378 384 406
244 317 384 406
411 412 414 419
151 226 298 371
Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total gross capacity. 3. SHC = Sensible heat capacity.
Table PD-7 — 40 Ton Gross Cooling Capacities (Mbh) Ambient Temperature — Deg F 95 105 Entering Wet BulbTemperature — Deg F 67 73 61 67
85 Ent DB CFM
(F)
61
67
73
61
115 73
61 TGC SHC
67
73
TGC SHC
TGC SHC
TGC SHC TGC SHC TGC SHC
TGC SHC TGC SHC TGC SHC
TGC SHC TGC SHC TGC SHC
75 12000 80 85 90
460 466 480 506
365 432 480 506
510 511 515 521
288 351 415 480
565 566 567 568
202 269 333 398
439 445 461 487
353 419 461 487
486 487 491 498
276 338 402 468
539 540 541 543
190 257 322 385
416 423 441 467
340 406 441 467
462 463 467 475
263 325 390 455
512 513 515 517
178 244 309 373
393 401 421 445
327 393 421 445
436 438 442 450
250 312 376 442
484 486 487 489
166 232 297 360
75 14000 80 85 90
476 484 506 535
396 473 506 535
525 526 532 541
304 378 453 529
580 581 582 585
208 284 359 432
453 463 486 514
383 461 486 514
500 502 508 518
291 365 440 517
553 554 556 559
196 272 347 420
430 438 465 492
370 438 465 492
474 477 482 492
279 352 427 492
525 526 528 531
184 260 335 407
406 417 443 470
357 417 443 470
448 450 457 469
266 339 414 469
496 497 499
172 248 321
75 15000 80 85 90
482 489 518 547
411 489 518 547
530 533 539 546
317 391 471 546
586 587 588 591
211 292 372 449
459 469 497 525
398 469 497 525
505 508 514 525
305 379 458 525
558 560 561 565
199 280 360 437
436 448 475 503
385 448 475 503
479 482 489 503
292 530 187 366 531 268 445 533 346 503 537 424
411 426 453 480
371 426 453 480
452 456 463 480
279 352 432 480
75 16000 80 85 90
488 499 528 558
425 499 528 558
536 539 546 558
321 405 489 558
591 592 593 597
213 299 383 466
465 478 507 536
412 478 507 536
510 513 521 536
309 392 477 536
563 565 566 571
202 287 371 453
441 457 485 513
399 457 485 513
484 487 495 513
296 534 189 379 536 275 463 538 358 513 543 440
416 434 461 489
385 434 461 489
456 460 469 489
282 365 450 489
75 17600 80 85 90
497 513 543 574
448 513 543 574
543 547 555 574
335 425 518 574
598 599 601 606
217 311 401 492
473 491 521 551
435 491 521 551
517 521 530 551
322 412 505 551
570 572 574 579
206 299 389 479
449 469 498 527
422 469 498 527
490 495 504 527
308 541 193 399 543 286 492 545 376 527 551 466
424 408 446 446 474 474
462 295 467 385 474 474
Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total gross capacity. 3. SHC = Sensible heat capacity.
RT-PRC007-EN
27
Performance Data
60 Hz
Table PD-8 — 50 Ton Gross Cooling Capacities (MBh) 85 Ent DB CFM
61
67
73
61
AmbientTemperature — Deg F 95 105 Entering Wet BulbTemperature — Deg F 67 73 61 67
115 73
67
73
TGC SHC
61
TGC SHC
TGC SHC
327 614 216 409 616 303 494 618 389 574 622 471
475 414 487 487 517 517 547 547
524 312 527 394 534 479 547 547
566 570 578 597
344 437 534 597
625 627 629 634
222 320 414 507
486 445 506 506 538 538
533 328 538 422 547 518
476 541 574 608
570 575 584 607
356 451 553 607
629 632 634 640
224 327 426 525
491 460 514 514 547 547
538 340 543 436 553 537
525 549 583 617
491 549 583 617
575 580 590 617
362 465 572 617
633 636 639 645
227 335 438 543
496 475 522 522 555 555
542 345 547 449 559 556
530 557 591 626
506 557 591 626
579 584 596 626
371 478 591 626
637 640 643 650
230 343 450 560
501 490 529 529 563 563
545 353 551 463 562 562
(F)
TGC SHC TGC SHC TGC SHC
TGC SHC TGC SHC TGC SHC
TGC SHC TGC SHC TGC SHC
75 15000 80 85 90
556 459 614 356 679 244 565 547 616 439 680 331 590 590 622 524 682 417 623 623 631 611 684 500
529 444 585 342 647 230 539 533 588 424 649 318 567 567 593 509 651 403 599 599 604 597 654 486
502 429 511 511 542 542 574 574
555 558 564 574
75 17000 80 85 90
570 581 615 650
491 627 373 691 250 581 630 468 693 348 615 637 564 694 443 650 649 649 698 536
543 557 590 624
476 557 590 624
597 601 608 624
359 453 549 624
659 661 662 667
236 334 429 522
515 532 565 597
460 532 565 597
75 18000 80 85 90
576 591 626 661
506 633 386 696 252 591 636 482 698 355 626 644 583 699 455 661 661 661 703 554
548 566 601 635
491 566 601 635
602 606 615 635
371 467 568 635
663 666 668 673
239 342 441 540
520 541 574 608
75 19000 80 85 90
581 600 636 671
522 638 391 701 255 600 642 495 702 363 636 651 602 704 467 671 671 671 709 571
554 575 610 645
507 575 610 645
607 611 621 645
377 480 587 645
668 670 673 678
241 350 453 557
75 20000 80 85 90
587 609 645 681
537 642 400 705 257 609 647 509 707 371 645 657 621 708 479 681 681 681 714 589
559 583 619 654
522 583 619 654
611 616 627 654
386 494 606 654
672 674 677 683
244 357 465 575
Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total gross capacity. 3. SHC = Sensible heat capacity.
28
RT-PRC007-EN
Performance Data
60 Hz
Table PD-9 — Electric Heat Air Temperature Rise KW Input 36 54 72 90 108
Total MBH 123 184 246 307 369
8000 14.2 21.2 28.3 35.4 —
9000 12.6 18.9 25.2 31.5 —
10000 11.3 17.0 22.6 28.3 —
11000 10.3 15.4 20.6 25.7 —
12000 9.4 14.2 18.9 23.6 28.3
Cfm 14000 8.1 12.1 16.2 20.2 24.3
13000 8.7 13.1 17.4 21.8 26.1
15000 7.6 11.3 15.1 18.9 22.6
16000 — 10.6 14.2 17.7 21.2
17000 — 10.0 13.3 16.7 20.0
18000 — 9.4 12.6 15.7 18.9
19000 — 8.9 11.9 14.9 17.9
20000 — 8.5 11.3 14.2 17.0
Notes: 1. Air temperature rise = (KW x 3413)/(scfm x 1.085). 2. All heaters on constant volume units provide 2 increments of capacity. All VAV units provide 1 step of heating capacity. 3. Air temperature rise in this table are based on heater operating at 240, 480 or 600 volts.
Table PD-10 — Available Electric Heat KW Ranges Nominal Unit Size Tons
Nominal Voltage 208
240
480
600
27½
27-41
36-54
36-90
54-90
30.0
27-41
36-54
36-90
54-90
35.0
27-41
36-54
36-90
54-90
40.0
41
54
54-108 54-108
50.0
41
54
54-108 54-108
Notes: 1. KW ranges in this table are based on heater operating at 208, 240, 480, and 600 volts.
(
)
2. For other than rated voltage, KW = Applied Voltage 2 x Rated KW. Rated Voltage 3. Electric heaters up to 54 KW are single element heaters, those above 54 KW are dual element heaters.
Table PD-11 — Natural Gas Heating Capacities Tons
Unit Model No. YCD/YCH330**L
27½-35
YCD/YCH360**L
Heat Input MBH (See Note 1)
Heating Output MBH (See Note 1)
Air Temp. Rise, F
350,000/250,000
283,500/202,500
10-40
600,000/425,000
486,000/344,500
25-55
YCD/YCH420**L YCD/YCH330**H 27½-35
YCD/YCH360**H YCD/YCH420**H YCD/YCH480**L
40-50
YCD/YCH600**L YCD/YCH480**H
400,000/300,000
324,000/243,000
5-35
40-50
YCD/YCH600**H
800,000/600,000
648,000/486,000
20-50
Note: 1. Second stage is total heating capacity. Second Stage/First Stage.
RT-PRC007-EN
29
Performance Data
60 Hz
Table PD-12 — Supply Fan Performance — 27½ - 35 Ton Static Pressure (in. wg)1 0.25
0.50
0.75
1.00
1.25
SCFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
8000
308
1.17
372
1.62
427
2.09
475
2.55
8500
317
1.33
381
1.82
436
2.33
480
2.77
9000
326
1.51
391
2.04
443
2.55
489
9500
337
1.72
401
2.28
451
2.80
10000
349
1.96
411
2.54
459
10500
363
2.22
421
2.82
468
11000
376
2.52
430
3.11
11500
390
2.83
438
12000
404
3.18
12500
417
3.55
13000
431
13500
1.50
1.75
2.00
2.25
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
525
3.11
574
3.75
620
4.42
661
5.09
701
5.77
528
3.34
574
3.97
620
4.66
662
5.36
702
6.08
3.08
532
3.58
577
4.22
620
4.91
663
5.64
703
6.40
498
3.39
537
3.87
580
4.50
621
5.18
663
5.93
703
6.70
3.09
506
3.69
545
4.25
584
4.81
624
5.48
664
6.23
703
7.02
3.40
513
3.98
555
4.65
589
5.17
628
5.84
666
6.56
703
7.34
479
3.74
521
4.33
563
5.03
598
5.63
633
6.22
670
6.95
706
7.73
3.41
489
4.10
530
4.72
570
5.38
607
6.11
639
6.68
674
7.37
709
8.14
447
3.74
499
4.48
538
5.13
578
5.79
615
6.56
648
7.22
679
7.83
713
8.59
457
4.10
509
4.88
549
5.58
586
6.24
623
7.00
657
7.78
687
8.42
718
9.10
3.95
468
4.50
518
5.30
559
6.04
594
6.73
630
7.45
665
8.30
696
9.04
724
9.69
445
4.39
479
4.92
526
5.73
569
6.53
604
7.26
638
7.98
673
8.82
705
9.68
733
10.38
14000
459
4.85
490
5.39
535
6.19
579
7.04
614
7.81
647
8.56
680
9.35
713
10.26
742
11.09
14500
473
5.35
503
5.90
544
6.68
588
7.59
624
8.40
656
9.18
688
9.96
720
10.86
751
11.78
Table PD-12 — Supply Fan Performance — 27½ - 35 Ton Continued 2.50
Static Pressure (in. wg)1 2.75
3.00
SCFM
RPM
BHP
RPM
BHP
RPM
8000
738
6.48
773
7.18
805
BHP 7.88
8500
739
6.82
774
7.54
807
8.28
9000
740
7.16
775
7.92
809
8.70
9500
740
7.48
776
8.30
810
9.12
10000
742
7.86
777
8.68
812
9.54
10500
742
8.20
777
9.05
812
9.94
11000
741
8.56
777
9.43
812
10.35
11500
743
8.95
777
9.83
812
10.78
12000
747
9.43
780
10.30
812
11.21
12500
750
9.90
783
10.79
814
11.70
13000
755
10.45
786
11.30
817
12.22
13500
760
11.04
790
11.88
821
12.81
14000
768
11.79
795
12.52
824
13.39
14500
778
12.59
803
13.30
829
14.10
Notes: 1. Supply fan performance table includes internal resistance of rooftop. For total static pressure determination, system external static must be added to appropriate component static pressure drops, (evaporator coil, filters, optional economizer, optional heating system, optional roof curb). 2. The pressure drop from the supply fan to the space cannot exceed 2.25”. 3. Maximum air flow for 27½ ton — 12,100 cfm, 30 ton — 13,200 cfm, 35 ton — 14,400 cfm. 4. Maximum motor horsepower for 27½ ton — 10 hp, 30 ton — 10 hp, 35 ton — 15 hp.
30
RT-PRC007-EN
Performance Data
60 Hz
Table PD-13 — Supply Fan Performance — 40 and 50 Ton Static Pressure (in. wg)1 0.25
0.50
0.75
1.00
1.25
1.50
1.75
2.00
2.25
SCFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
12000 13000 14000 15000
307 324 341 359
2.29 2.79 3.35 3.99
353 368 384 401
2.86 3.40 4.03 4.77
394 407 422 437
3.45 4.06 4.74 5.48
436 446 457 471
4.11 4.73 5.42 6.24
471 482 494 504
4.75 5.43 6.19 6.99
509 515 525 537
5.43 6.13 6.93 7.82
543 550 556 566
6.14 6.87 7.69 8.62
575 582 589 595
6.89 7.65 8.49 9.42
606 612 619 625
7.63 8.44 9.32 10.27
16000
376
4.72
418
5.60
452
6.32
485
7.14
515
7.92
548
8.77
578
9.65
604
10.49
632
11.36
17000
394
5.53
434
6.50
468
7.26
500
8.12
529
8.97
558
9.79
589
10.73
616
11.65
641
12.54
18000
413
6.42
451
7.48
485
8.34
515
9.18
544
10.11
571
10.99
598
11.89
628
12.88
654
13.87
19000
431
7.42
469
8.55
501
9.53
530
10.37
559
11.34
585
12.29
611
13.22
637
14.17
665
15.24
20000
449
8.52
486
9.72
518
10.83
547
11.69
573
12.66
600
13.69
625
14.70
648
15.64
675
16.71
Table PD-13 — Supply Fan Performance — 40 and 50 Ton Continued Static Pressure (in. wg)1 2.50
2.75
3.00
3.25
3.50
SCFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
12000
640
8.45
670
9.25
700
10.03
727
10.81
755
11.61
13000
640
9.23
671
10.12
701
10.98
729
11.85
756
12.69
14000
647
10.16
674
11.04
700
11.89
729
12.85
757
13.79
15000
653
11.14
680
12.05
706
12.97
731
13.89
757
14.86
16000
659
12.23
687
13.16
713
14.14
738
15.10
762
16.10
17000
666
13.45
694
14.42
719
15.37
744
16.39
768
17.39
18000
677
14.81
700
15.76
726
16.78
751
17.77
774
18.81
19000
690
16.29
711
17.27
734
18.29
758
19.34
782
20.41
20000 Notes:
701
17.83
724
18.91
745
19.94
765
20.99
788
22.12
1. Supply fan performance table includes internal resistance of rooftop. For total static pressure determination, system external static must be added to appropriate component static pressure drops, (evaporator coil, filters, optional economizer, optional heating system, optional roof curb). 2. The pressure drop from the supply fan to the space cannot exceed 2.50”. 3. Maximum air flow for 40 ton — 17,600 cfm, 50 ton — 20,000 cfm. 4. Maximum motor horsepower for 40 ton — 15 hp, 50 ton — 20 hp.
RT-PRC007-EN
31
Performance Data Supply Fan Performance
Figure PD-2 — Supply Fan Performance — 27½ - 35 Ton 4.0
60 Hz
27-35T M F C O W 0 % 5
8 0 0 R P M
3.5
M F C O W % 6 0
7 0 0 R P M
3.0
M C F O W % 7 0
2.5
F M O C W % 8 0
6 0 0 R P M
) C W n I ( e r u 2.0 s e r P c i t a t S
1 5 H P
5 0 0 R P M
1.5
1 0 H P
4 0 0 R P M
1.0
F M O C W % 9 0
7 . 5 H P 5 H P 3 H P
0.5
0.0 0
2000
4000
6000
8000
10000
12000
14000
16000
18000
20000
22000
24000
26000
Volumetric Airflow Rate(CFM)
Figure PD-3 — Supply Fan Performance — 40 and 50 Ton
Supply Fan Performance 40 and 50 Ton
5 M F C O W 0 % 4
8 0 0 R P M
4
M F C O W % 5 0
F M O C W % 6 0
7 5 0 R P M 7 0 0 R P M
) 3 C W n I ( e r u s e r P c i t a 2 t S
6 5 0 R P M
F M O C W % 7 0
6 0 0 R P M 5 5 0 R P M
2 0 H P
5 0 0 R P M 4 5 0 R P M 4 0 0 R P M 3 5 0 R P M 3 0 0 R P M
1
1 5 H P
7 . 5 H P
F M C W O % 8 0
1 0 H P
C F M W O 9 0 %
0 0
2000
4000
6000
8000
10000
12000
14000
16000
18000
20000
22000
24000
26000
28000
Volumetric Airflow Rate(CFM)
32
RT-PRC007-EN
Performance Data
60 Hz
Table PD-14 — Component Static Pressure Drops (in. W.G.) 1 Filters 2
Heating System Nominal CFM Tons Std Air 8000 9000 27½ 10000 11000 12000 9000 10000 30 11000 12000 13000 10500 11500 35 12500 13500 14500 12000 13000 14000 40 15000 16000 17000 15000 16000 50 17000 18000 19000 20000
Gas Heat Low High 0.08 0.06 0.1 0.08 0.13 0.1 0.15 0.12 0.18 0.14 0.1 0.08 0.13 0.1 0.15 0.12 0.18 0.14 0.21 0.16 0.14 0.11 0.17 0.13 0.2 0.15 0.23 0.18 0.26 0.2 0.01 0.03 0.01 0.04 0.02 0.05 0.02 0.05 0.02 0.06 0.02 0.07 0.02 0.05 0.02 0.06 0.02 0.07 0.03 0.08 0.03 0.08 0.03 0.09
3
Electric Heat 1 Element 2 Element 0.05 0.06 0.07 0.07 0.08 0.09 0.1 0.11 0.12 0.13 0.07 0.07 0.08 0.09 0.1 0.11 0.12 0.13 0.14 0.15 0.09 0.1 0.11 0.12 0.13 0.14 0.15 0.16 0.18 0.19 0.08 0.13 0.1 0.15 0.11 0.18 0.13 0.2 0.15 0.23 0.17 0.26 0.13 0.2 0.15 0.23 0.17 0.26 0.19 0.29 0.21 0.32 0.23 0.36
ID Coil Dry Wet 0.09 0.11 0.11 0.14 0.13 0.17 0.16 0.19 0.18 0.22 0.11 0.14 0.13 0.17 0.16 0.19 0.18 0.22 0.2 0.25 0.22 0.27 0.25 0.31 0.29 0.35 0.32 0.4 0.36 0.45 0.2 0.25 0.23 0.29 0.26 0.33 0.29 0.36 0.32 0.4 0.36 0.44 0.39 0.48 0.43 0.54 0.48 0.59 0.52 0.65 0.57 0.74 0.62 0.77
Throwaway 2" 0.08 0.09 0.1 0.12 0.13 0.09 0.1 0.12 0.14 0.15 0.11 0.13 0.14 0.15 0.17 0.1 0.12 0.13 0.14 0.15 0.17 0.14 0.15 0.17 0.18 0.19 0.2
High Eff. Filters Inlet Guide 2” 4” Vanes Economizer 0.12 0.11 0.05 0.04 0.14 0.13 0.07 0.04 0.16 0.15 0.08 0.05 0.2 0.17 0.1 0.06 0.21 0.2 0.12 0.07 0.14 0.13 0.07 0.04 0.16 0.15 0.08 0.05 0.2 0.17 0.1 0.06 0.23 0.21 0.12 0.07 0.26 0.23 0.14 0.09 0.18 0.16 0.09 0.06 0.21 0.19 0.11 0.07 0.24 0.21 0.13 0.08 0.26 0.23 0.15 0.1 0.3 0.27 0.18 0.11 0.19 0.17 0.04 0.07 0.23 0.2 0.05 0.08 0.25 0.22 0.05 0.09 0.28 0.24 0.06 0.1 0.31 0.27 0.07 0.11 0.35 0.3 0.08 0.12 0.28 0.24 0.06 0.1 0.31 0.27 0.07 0.11 0.35 0.3 0.08 0.12 0.38 0.33 0.09 0.14 0.42 0.35 0.1 0.16 0.45 0.38 0.11 0.18
Notes: 1. Static pressure drops of accessory components must be added to external static pressure to enter fan selection tables. 2. Throwaway filter option limited to 300 ft/min face velocity. 3. Electric Heaters 36-54 KW contain 1 element; 72-108 KW 2 elements.
RT-PRC007-EN
33
Performance Data
60 Hz
Table PD-15 — Supply Air Fan Drive Selections 7.5 HP Nominal Tons
27½T
10 HP
RPM
Drive No
550
A
600
B
650
C
RPM
700
D
750*
E
700
700
D
750
750
E
650
650
C
700
700
D
700 750
30T
550
A
600
B
650
C
600
35T
40T
50T
15 HP Drive No
RPM
20 HP Drive No
RPM
Drive No
725
N
B
790
790**
F
800
800*
G
625
625
L
675
675
M
725
725
N
625
625
L
675
675
M
500
500
H
525
525
J
575
575
K
525
525
J
575
575
K
725 Note: *For YC gas/electrics only. **For TC and TE Cooling only and with electric heat units only.
34
RT-PRC007-EN
Performance Data
60 Hz
Table PD-16— Power Exhaust Fan Performance Exhaust Airflow (Cfm)
External Static Pressure — Inches of Water High Speed Med Speed Low Speed ESP ESP ESP
3500
0.900
—
—
4000
0.860
—
—
4500
0.820
—
—
5000
0.780
—
0.400
5500
0.745
—
0.380
6000
0.700
—
0.360
6500
0.660
—
0.330
7000
0.610
0.400
0.300
7500
0.560
0.365
0.260
8000
0.505
0.330
0.215
8500
0.445
0.300
0.170
9000
0.385
0.255
0.120
9500
0.320
0.210
0.070
10000
0.255
0.165
0.020
10500
0.190
0.125
—
11000
0.125
0.060
—
11500
0.065
0.000
—
12000
0.005
—
—
Notes: 1. Performance in table is with both motors operating. 2. High speed = both motors on high speed. Medium speed is one motor on high speed and one on low speed. Low speed is both motors on low speed. 3. Power Exhaust option is not to be applied on systems that have more return air static pressure drop than the maximum shown in the table for each motor speed tap.
RT-PRC007-EN
35
Performance Data
Table PD-17 – 23 Ton Gross Cooling Capacities (MBh)
50 Hz
(I-P) AmbientTemperature – °F
85
cfm 6900
7500
8000
9000
10000
Ent DB (°F)
61 TGC SHC
95
67 TGC SHC
73 TGC SHC
61 TGC SHC
105 115 Entering Wet BulbTemperature – °F 67 73 61 67 73 61 67 TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
73 TGC SHC
75 80 85 90
247 249 256 270
195 229 256 270
274 275 276 279
158 187 221 255
304 304 305 306
110 145 179 212
235 238 247 260
188 223 247 260
262 263 264 267
152 181 215 249
290 291 292 293
104 139 173 206
224 227 236 250
182 216 236 250
249 250 251 254
146 174 208 242
276 277 278 279
98 133 167 199
211 214 225 239
175 209 225 239
235 236 237 241
139 167 201 235
261 262 263 264
91 126 160 193
75 80 85 90
251 254 264 279
203 241 264 279
279 280 281 284
164 195 231 269
309 310 310 311
112 150 186 222
240 243 254 268
197 235 254 268
266 267 269 272
158 189 225 262
295 296 297 298
106 144 180 216
228 232 243 257
190 228 243 257
253 254 256 260
152 182 218 255
280 281 282 283
100 137 173 209
215 218 232 246
183 218 232 246
239 240 242 246
145 175 211 246
265 266 267 268
93 131 166 202
75 80 85 90
255 259 270 285
210 250 270 285
282 283 285 289
168 201 240 279
313 313 314 315
113 153 192 230
243 247 260 274
204 244 260 274
269 271 272 277
162 195 233 273
298 299 300 301
107 147 186 223
231 235 249 263
197 235 249 263
256 257 259 263
155 188 227 263
283 284 285 287
101 141 179 217
218 223 237 251
190 223 237 251
241 243 245 251
149 181 219 251
267 269 270 271
95 134 172 210
75 80 85 90
261 265 281 297
224 265 281 297
288 289 292 296
171 213 257 296
319 320 321 322
116 161 203 245
249 255 270 285
217 255 270 285
275 276 279 285
165 207 250 285
304 305 306 308
110 154 198 238
236 243 258 274
210 243 258 274
261 262 265 0
159 200 243 0
289 290 291 293
104 148 192 232
223 231 246 261
203 231 246 261
246 247 251 261
152 193 236 261
272 274 275 277
97 141 182 225
75 80 85 90
266 274 290 307
236 274 290 307
293 295 298 306
179 225 273 306
324 325 326 328
119 167 216 260
254 263 279 295
230 263 279 295
280 281 285 295
173 218 266 295
309 310 311 313
113 161 207 253
241 251 267 282
223 251 267 282
265 267 271 282
166 211 259 282
293 294 296 298
106 155 200 246
227 239 254 269
215 239 254 269
250 252 256 269
159 204 252 269
276 278 279 281
99 148 193 239
Notes: 1.ll capacities shown are gross and hav e not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total gross capacity. 3. SHC = Sensible heat capacity.
Table PD-17a – 82 kW (23 Tons) Gross Cooling Capacity (kW) (SI) Ambient Temperature – °C 35.0 40.6 46.1 Entering Wet Bulb Temperature – °C 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 29.4
L/s
Ent DB (°C)
23.9 3260 26.7 29.4 32.2
72.4 73.0 75.0 79.1
57.1 67.1 75.0 79.1
80.3 80.6 80.9 81.8
46.3 89.1 32.2 54.8 89.1 42.5 64.8 89.4 52.5 74.7 89.7 62.1
68.9 69.8 72.4 76.2
55.1 65.4 72.4 76.2
76.8 77.1 77.4 78.2
44.5 53.0 63.0 73.0
85.0 85.3 85.6 85.9
30.5 40.7 50.7 60.4
65.6 66.5 69.2 73.3
53.3 73.0 42.8 80.9 28.6 63.3 73.3 51.0 81.2 39.0 69.2 73.6 61.0 81.5 48.9 73.3 74.4 70.9 81.8 58.3
61.8 62.7 65.9 70.0
51.3 61.3 65.9 70.0
68.9 69.2 69.5 70.6
40.7 48.9 58.9 68.9
76.5 76.8 77.1 77.4
26.8 36.9 46.9 56.6
23.9 3540 26.7 29.4 32.2
73.6 74.4 77.4 81.8
59.5 70.6 77.4 81.8
81.8 82.1 82.4 83.2
48.1 90.6 32.8 57.1 90.9 44.0 67.7 90.9 54.5 78.8 91.1 65.1
70.3 71.2 74.4 78.5
57.7 68.9 74.4 78.5
78.0 78.2 78.8 79.7
46.3 55.4 65.9 76.8
86.5 86.7 87.0 87.3
31.1 42.2 52.8 63.3
66.8 68.0 71.2 75.3
55.7 74.1 44.5 82.1 29.2 66.8 74.4 53.3 82.4 40.2 71.2 75.0 63.9 82.6 50.7 75.3 76.2 74.7 82.9 61.3
63.0 63.9 68.0 72.1
53.6 63.9 68.0 72.1
70.0 70.3 70.9 72.1
42.5 51.3 61.8 72.1
77.7 78.0 78.2 78.5
27.3 38.4 48.6 59.2
23.9 3780 26.7 29.4 32.2
74.7 75.9 79.1 83.5
61.5 73.3 79.1 83.5
82.6 82.9 83.5 84.7
49.2 91.7 33.1 58.9 91.7 44.8 70.3 92.0 56.3 81.8 92.3 67.4
71.2 72.4 76.2 80.3
59.8 71.5 76.2 80.3
78.8 79.4 79.7 81.2
47.5 57.1 68.3 80.0
87.3 87.6 87.9 88.2
31.4 43.1 54.5 65.4
67.7 68.9 73.0 77.1
57.7 75.0 45.4 82.9 29.6 68.9 75.3 55.1 83.2 41.3 73.0 75.9 66.5 83.5 52.5 77.1 77.1 77.1 84.1 63.6
63.9 65.4 69.5 73.6
55.7 65.4 69.5 73.6
70.6 71.2 71.8 73.6
43.7 53.0 64.2 73.6
78.2 78.8 79.1 79.4
27.7 39.3 50.4 61.5
23.9 4250 26.7 29.4 32.2
76.5 77.7 82.4 87.0
65.6 77.7 82.4 87.0
84.4 84.7 85.6 86.7
50.1 93.5 34.0 62.4 93.8 47.2 75.3 94.1 59.5 86.7 94.4 71.8
73.0 74.7 79.1 83.5
63.6 74.7 79.1 83.5
80.6 80.9 81.8 83.5
48.4 60.7 73.3 83.5
89.1 89.4 89.7 90.3
32.2 45.1 58.0 69.8
69.2 71.2 75.6 80.3
61.5 76.5 46.6 84.7 30.5 71.2 76.8 58.6 85.0 43.4 75.6 77.7 71.2 85.3 56.3 80.3 0.0 0.0 85.9 68.0
65.4 67.7 72.1 76.5
59.5 67.7 72.1 76.5
72.1 72.4 73.6 76.5
44.5 56.6 69.2 76.5
79.7 80.3 80.6 81.2
28.5 41.3 53.3 65.9
23.9 4720 26.7 29.4 32.2
78.0 80.3 85.0 90.0
69.2 80.3 85.0 90.0
85.9 86.5 87.3 89.7
52.5 95.0 34.9 65.9 95.2 48.9 80.0 95.5 63.3 89.7 96.1 76.2
74.4 77.1 81.8 86.5
67.4 77.1 81.8 86.5
82.1 82.4 83.5 86.5
50.7 63.9 78.0 86.5
90.6 90.9 91.1 91.7
33.1 47.2 60.7 74.1
70.6 73.6 78.2 82.6
65.4 77.7 48.6 85.9 31.1 73.6 78.2 61.8 86.2 45.4 78.2 79.4 75.9 86.7 58.6 82.6 82.6 82.6 87.3 72.1
66.5 70.0 74.4 78.8
63.0 70.0 74.4 78.8
73.3 73.9 75.0 78.8
46.6 59.8 73.9 78.8
80.9 81.5 81.8 82.4
29.1 43.4 56.6 70.0
Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total gross capacity. 3. SHC = Sensible heat capacity.
36
RT-PRC007-EN
Performance Data
Table PD-18 – 25 Ton Gross Cooling Capacities (MBh)
50 Hz
(I-P) Ambient Temperature – °F
85
cfm 7500
8000
9000
10000
11000
Ent DB (°F)
61 TGC SHC
95
67 TGC SHC
73 TGC SHC
61 TGC SHC
105 115 Entering Wet BulbTemperature – °F 67 73 61 67 73 61 67 TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
73 TGC SHC
75 80 85 90
270 273 280 295
212 249 280 295
300 301 302 304
172 204 240 277
332 333 334 335
120 158 195 231
258 261 269 284
205 243 269 284
286 287 289 292
166 197 233 270
318 318 319 320
114 152 189 224
245 248 258 272
198 235 258 272
272 273 275 278
159 190 226 263
302 303 304 305
107 145 182 217
231 235 246 260
190 228 246 260
257 258 260 264
152 183 218 255
285 286 287 288
100 138 174 209
75 80 85 90
274 277 286 302
219 259 286 302
304 305 306 309
177 210 249 288
336 337 338 339
122 162 201 239
262 265 275 291
212 252 275 291
290 291 293 296
171 203 242 281
321 322 323 324
115 155 194 232
248 252 264 279
205 245 264 279
276 277 278 282
164 196 234 274
305 306 307 308
109 149 187 224
234 239 251 266
197 237 251 266
260 261 263 268
157 189 227 266
289 289 290 292
102 141 179 217
75 80 85 90
281 285 298 314
233 277 298 314
311 312 314 318
187 223 265 309
344 344 345 347
125 169 212 254
268 273 287 303
226 270 287 303
297 298 300 305
181 216 258 302
328 329 330 331
118 163 205 247
254 259 274 290
218 259 274 290
281 283 285 290
174 208 251 290
311 312 314 315
112 156 198 240
240 246 261 277
210 246 261 277
266 267 270 277
167 200 243 277
294 295 296 298
105 148 190 232
75 80 85 90
287 291 308 325
246 291 308 325
316 318 320 325
197 234 281 325
349 350 351 353
128 176 223 269
274 280 296 313
238 280 296 313
302 303 306 313
189 227 274 313
333 334 336 337
121 169 216 262
260 267 283 300
231 267 283 300
286 288 291 300
181 220 267 300
316 318 319 321
114 162 208 254
245 254 270 286
223 254 270 286
270 272 275 286
174 212 259 286
298 300 301 303
107 155 200 246
75 80 85 90
292 300 317 335
258 300 317 335
321 323 326 335
204 246 297 335
354 355 357 358
130 183 233 283
279 288 305 322
251 288 305 322
306 308 312 322
197 238 290 322
338 339 340 342
124 176 226 276
264 275 291 309
243 275 291 309
290 292 296 308
190 231 282 308
320 322 323 325
117 169 218 268
249 261 277 294
235 261 277 294
274 276 280 294
182 223 275 294
302 303 305 308
110 161 210 261
Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total gross capacity. 3. SHC = Sensible heat capacity.
Table PD-18a – 89 kW (25 Tons) Gross Cooling Capacity (kW) (SI) Ambient Temperature – °C 35.0 40.6 46.1 Ent Entering Wet Bulb Temperature – °C DB 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 (°C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 29.4
L/s
23.9 3540 26.7 29.4 32.2
79.1 80.0 82.1 86.5
62.1 87.9 50.4 73.0 88.2 59.8 82.1 88.5 70.3 86.5 89.1 81.2
97.3 97.6 97.9 98.2
35.2 46.3 57.1 67.7
75.6 76.5 78.8 83.2
60.1 71.2 78.8 83.2
83.8 48.6 84.1 57.7 84.7 68.3 85.6 79.1
93.2 93.2 93.5 93.8
33.4 44.5 55.4 65.6
71.8 72.7 75.6 79.7
58.0 68.9 75.6 79.7
79.7 80.0 80.6 81.5
46.6 55.7 66.2 77.1
88.5 88.8 89.1 89.4
31.4 42.5 53.3 63.6
67.7 68.9 72.1 76.2
55.7 66.8 72.1 76.2
75.3 75.6 76.2 77.4
44.5 53.6 63.9 74.7
83.5 83.8 84.1 84.4
29.3 40.4 51.0 61.3
23.9 3780 26.7 29.4 32.2
80.3 81.2 83.8 88.5
64.2 89.1 51.9 75.9 89.4 61.5 83.8 89.7 73.0 88.5 90.6 84.4
98.5 98.8 99.1 99.4
35.8 47.5 58.9 70.0
76.8 77.7 80.6 85.3
62.1 73.9 80.6 85.3
85.0 50.1 85.3 59.5 85.9 70.9 86.7 82.4
94.1 94.4 94.7 95.0
33.7 45.4 56.9 68.0
72.7 73.9 77.4 81.8
60.1 71.8 77.4 81.8
80.9 81.2 81.5 82.6
48.1 57.4 68.6 80.3
89.4 89.7 90.0 90.3
31.9 43.7 54.8 65.6
68.6 70.0 73.6 78.0
57.7 69.5 73.6 78.0
76.2 76.5 77.1 78.5
46.0 55.4 66.5 78.0
84.7 84.7 85.0 85.6
29.9 41.3 52.5 63.6
23.9 4250 26.7 29.4 32.2
82.4 83.5 87.3 92.0
68.3 91.1 54.8 81.2 91.4 65.4 87.3 92.0 77.7 92.0 93.2 90.6
100.8 100.8 101.1 101.7
36.6 49.5 62.1 74.4
78.5 80.0 84.1 88.8
66.2 79.1 84.1 88.8
87.0 87.3 87.9 89.4
53.0 63.3 75.6 88.5
96.1 96.4 96.7 97.0
34.6 47.8 60.1 72.4
74.4 75.9 80.3 85.0
63.9 75.9 80.3 85.0
82.4 82.9 83.5 85.0
51.0 61.0 73.6 85.0
91.1 91.4 92.0 92.3
32.8 45.7 58.0 70.3
70.3 72.1 76.5 81.2
61.5 72.1 76.5 81.2
78.0 78.2 79.1 81.2
48.9 86.2 30.8 58.6 86.5 43.4 71.2 86.7 55.7 81.2 87.3 68.0
23.9 4720 26.7 29.4 32.2
84.1 85.3 90.3 95.2
72.1 92.6 57.7 102.3 37.5 85.3 93.2 68.6 102.6 51.6 90.3 93.8 82.4 102.9 65.4 95.2 95.2 95.2 103.5 78.8
80.3 82.1 86.7 91.7
69.8 82.1 86.7 91.7
88.5 88.8 89.7 91.7
55.4 66.5 80.3 91.7
97.6 97.9 98.5 98.8
35.5 49.5 63.3 76.8
76.2 78.2 82.9 87.9
67.7 78.2 82.9 87.9
83.8 84.4 85.3 87.9
53.0 64.5 78.2 87.9
92.6 93.2 93.5 94.1
33.4 47.5 61.0 74.4
71.8 74.4 79.1 83.8
65.4 74.4 79.1 83.8
79.1 79.7 80.6 83.8
51.0 62.1 75.9 83.8
87.3 87.9 88.2 88.8
31.4 45.4 58.6 72.1
23.9 5190 26.7 29.4 32.2
85.6 87.9 92.9 98.2
75.6 94.1 59.8 103.7 38.1 87.9 94.7 72.1 104.0 53.6 92.9 95.5 87.0 104.6 68.3 98.2 98.2 98.2 104.9 82.9
81.8 84.4 89.4 94.4
73.6 84.4 89.4 94.4
89.7 90.3 91.4 94.4
57.7 99.1 69.8 99.4 85.0 99.6 94.4 100.2
36.3 51.6 66.2 80.9
77.4 80.6 85.3 90.6
71.2 80.6 85.3 90.6
85.0 85.6 86.7 90.3
55.7 67.7 82.6 90.3
93.8 94.4 94.7 95.2
34.3 49.5 63.9 78.5
73.0 76.5 81.2 86.2
68.9 76.5 81.2 86.2
80.3 80.9 82.1 86.2
53.3 65.4 80.6 86.2
88.5 88.8 89.4 90.3
32.2 47.2 61.5 76.5
Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total gross capacity. 3. SHC = Sensible heat capacity.
RT-PRC007-EN
37
Performance Data
50 Hz
Table PD-19 – 29 Ton Gross Cooling Capacities (MBh) (I-P) AmbientTemperature – °F 85
cfm 8750
9000
10000
11000
12000
Ent DB (°F)
61 TGC SHC
95
67 TGC SHC
73 TGC SHC
61 TGC SHC
105 115 Entering Wet BulbTemperature – °F 67 73 61 67 73 61 67 TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
73 TGC SHC
75 80 85 90
318 323 336 353
260 309 336 353
352 353 355 359
204 249 296 344
389 389 390 391
141 189 237 283
304 309 323 340
252 301 323 340
336 337 339 344
197 241 288 336
371 372 373 374
133 182 229 275
288 294 309 326
244 293 309 326
319 320 322 328
189 233 280 328
352 353 354 355
125 174 221 267
272 278 294 311
235 278 294 311
301 302 305 311
181 224 271 311
332 333 334 336
118 166 212 258
75 80 85 90
320 325 339 357
264 314 339 357
354 354 357 362
207 252 301 350
391 391 392 393
141 191 240 287
306 311 326 344
256 306 326 344
337 338 341 346
199 244 293 342
372 373 374 376
134 184 232 279
290 295 312 329
248 295 312 329
320 321 324 329
192 236 284 329
353 354 355 357
126 176 224 271
273 280 297 314
239 280 297 314
302 303 306 314
183 227 276 314
334 335 335 337
118 168 215 262
75 80 85 90
327 332 351 370
279 332 351 370
360 361 364 370
217 266 319 370
397 398 399 401
144 199 252 305
312 319 337 356
271 319 337 356
343 345 348 355
209 258 311 355
378 380 380 382
137 191 244 296
296 304 322 340
263 304 322 340
326 327 331 340
201 249 303 340
359 360 361 363
129 183 236 288
279 289 307 325
254 289 307 325
307 309 313 324
193 241 294 324
338 340 341 343
121 175 227 279
75 80 85 90
333 341 361 381
294 341 361 381
365 367 371 381
227 279 338 381
402 404 405 407
147 207 264 321
318 328 347 366
286 328 347 366
348 350 354 366
219 271 330 366
383 385 386 388
139 199 256 313
301 313 332 350
277 313 332 350
330 332 337 350
211 262 321 350
363 365 366 369
132 191 248 305
284 297 316 334
268 297 316 334
311 313 319 334
203 254 312 334
342 344 345 348
124 183 239 296
75 80 85 90
338 350 370 391
308 350 370 391
370 372 377 391
236 292 356 391
407 408 410 413
150 214 276 338
322 336 355 376
300 336 355 376
352 354 360 375
228 284 347 375
387 389 390 394
142 206 268 330
306 320 340 359
291 320 340 359
334 336 342 359
220 275 339 359
367 369 370 374
134 198 259 321
288 304 323 342
282 304 323 342
314 317 323 342
210 266 323 342
346 347 349 353
126 190 250 312
Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2 . TG C = Tota l gross capa cit y. 3. SHC = Sensible heat capacity.
Table PD-19a – 105 kW (29 Ton) Gross Cooling Capacity (kW) (SI) Ambient Temperature – °C 35.0 40.6 46.1 Entering Wet Bulb Temperature – °C 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 29.4
L/s
Ent DB (°C)
23.9 93.2 76.2 4130 26.7 94.7 90.6 29.4 98.5 98.5 32.2 103.5 1 03.5
103.2 59.8 103.5 73.0 104.0 86.7 105.2 1 00.8
114.0 114.0 114.3 114.6
41.3 89.1 73.9 98.5 55.4 90.6 88.2 98.8 69.5 94.7 94.7 99.4 82.9 99.6 99.6 100.8
23.9 93.8 77.4 4250 26.7 95.2 92.0 29.4 99.4 99.4 32.2 104.6 1 04.6
103.7 60.7 103.7 73.9 104.6 88.2 106.1 1 02.6
114.6 114.6 114.9 115.2
23.9 95.8 81.8 4720 26.7 97.3 97.3 29.4 102.9 102.9 32.2 108.4108.4
105.5 63.6 105.8 78.0 106.7 93.5 108.4 108.4
23.9 97.6 86.2 5190 26.7 99.9 99.9 29.4 105.8 1 05.8 32.2 111.7 111.7 23.9 99.1 90.3 5660 26.7 102.6 102.6 29.4 108.4108.4 32.2 114.6 114.6
57.7 70.6 84.4 98.5
108.7 109.0 109.3 109.6
39.0 84.4 71.5 53.3 86.2 85.9 67.1 90.6 90.6 80.6 95.5 95.5
93.5 93.8 94.4 96.1
55.4 103.2 68.3 103.5 82.1 103.7 96.1 1 04.0
36.6 51.0 64.8 78.2
79.7 81.5 86.2 91.1
68.9 81.5 86.2 91.1
88.2 88.5 89.4 91.1
53.0 65.6 79.4 91.1
97.3 97.6 97.9 98.5
34.6 48.6 62.1 75.6
41.3 89.7 75.0 98.8 58.3 56.0 91.1 89.7 99.1 71.5 70.3 95.5 95.5 99.9 85.9 84.1 100.8 1 00.8 101.4 100.2
109.0 39.3 85.0 72.7 93.8 56.3 103.5 36.9 109.3 53.9 86.5 86.5 94.1 69.2 103.7 51.6 109.6 68.0 91.4 91.4 95.0 83.2 104.0 65.6 110.2 81.8 96.4 96.4 96.4 96.4 1 04.6 79.4
80.0 82.1 87.0 92.0
70.0 82.1 87.0 92.0
88.5 88.8 89.7 92.0
53.6 66.5 80.9 92.0
97.9 98.2 98.2 98.8
34.6 49.2 63.0 76.8
116.3 116.6 116.9 117.5
42.2 91.4 79.4 100.5 61.3 58.3 93.5 93.5 101.1 75.6 73.9 98.8 98.8 102.0 91.1 89.4 104.3104.3 104.0 104.0
110.8 111.4 111.4 112.0
40.2 86.7 77.1 95.5 58.9 105.2 37.8 56.0 89.1 89.1 95.8 73.0 105.5 53.6 71.5 94.4 94.4 97.0 88.8 105.8 69.2 86.7 99.6 99.6 99.6 99.6106.4 84.4
81.8 84.7 90.0 95.2
74.4 84.7 90.0 95.2
90.0 90.6 91.7 95.0
56.6 99.1 70.6 99.6 86.2 99.9 95.0 100.5
35.5 51.3 66.5 81.8
107.0 66.5 107.6 81.8 108.7 99.1 111.7 111.7
117.8 118.4 118.7 119.3
43.1 93.2 83.8 60.7 96.1 96.1 77.4 101.7 1 01.7 94.1 107.3 107.3
102.0 64.2 102.6 79.4 103.7 96.7 107.3 107.3
112.2 112.8 113.1 113.7
40.7 88.2 81.2 96.7 61.8 106.4 58.3 91.7 91.7 97.3 76.8 107.0 75.0 97.3 97.3 98.8 94.1 1 07.3 91.7 102.6 102.6 102.6 102.6 108.1
38.7 56.0 72.7 89.4
83.2 87.0 92.6 97.9
78.5 87.0 92.6 97.9
91.1 91.7 93.5 97.9
59.5 74.4 91.4 97.9
100.2 100.8 101.1 102.0
36.3 53.6 70.0 86.7
108.4 69.2 109.0 85.6 110.5 104.3 114.6 114.6
119.3 119.6 120.2 121.0
44.0 94.4 87.9 103.2 66.8 62.7 98.5 98.5 103.7 83.2 80.9 104.0 104.0 105.5 101.7 99.1 110.2 110.2 109.9 109.9
113.4 114.0 114.3 115.5
41.6 60.4 78.5 96.7
39.3 84.4 82.6 92.0 61.5 58.0 89.1 89.1 92.9 78.0 75.9 94.7 94.7 94.7 94.7 94.1100.2 100.2 100.2 100.2
101.4 101.7 102.3 103.5
36.9 55.7 73.3 91.4
89.7 85.3 97.9 64.5 107.6 93.8 93.8 98.5 80.6 108.1 99.6 99.6 100.2 99.4108.4 105.2 105.2 105.2105.2 109.6
Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2 . TG C = Tota l gross capa cit y. 3. SHC = Sensible heat capacity.
38
RT-PRC007-EN
Performance Data
50 Hz
Table PD-20 – 33 Ton Gross Cooling Capacities (MBh) (I-P) Ambient Temperature – °F 85
cfm 10000
11000
12000
13000
14600
Ent DB (°F)
61 TGC SHC
95
67 TGC SHC
73 TGC SHC
61 TGC SHC
105 115 Entering Wet BulbTemperature – °F 67 73 61 67 73 61 67 TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
73 TGC SHC
75 80 85 90
389 394 405 428
307 362 405 428
433 434 436 441
242 295 349 404
480 481 482 483
171 227 281 335
370 375 389 411
296 351 389 411
412 413 416 421
231 284 338 393
457 458 460 461
160 216 271 324
350 355 371 393
284 339 371 393
390 391 394 400
220 272 326 381
433 434 436 437
149 205 259 312
328 334 352 373
272 327 352 373
366 368 371 377
208 260 314 369
407 409 410 412
138 193 248 300
75 80 85 90
398 404 420 444
323 384 420 444
441 442 446 452
252 309 369 429
488 490 491 492
174 235 295 353
378 384 402 426
311 372 402 426
419 421 425 431
241 298 357 418
465 466 468 469
163 224 284 342
357 364 384 407
299 361 384 407
397 398 402 410
230 286 345 406
440 441 443 445
152 213 272 330
335 342 364 387
287 342 364 387
373 374 379 386
218 274 333 386
414 415 417 419
141 201 261 318
75 80 85 90
405 413 433 457
338 405 433 457
448 450 454 462
262 323 388 454
495 497 498 500
177 243 308 370
385 391 415 439
327 391 415 439
426 428 432 439
251 312 376 439
471 473 474 477
166 232 297 359
364 372 396 419
315 372 396 419
403 405 410 419
240 300 364 419
446 448 449 452
155 221 285 347
341 352 375 398
302 352 375 398
378 380 386 398
228 288 352 398
419 421 422 426
144 209 272 335
75 80 85 90
412 419 445 470
353 419 445 470
454 456 461 470
272 337 407 470
501 503 503 507
180 251 320 387
391 401 426 450
342 401 426 450
432 434 439 450
261 325 395 450
477 479 480 483
169 240 308 376
370 382 406 430
329 382 406 430
408 410 416 430
249 313 383 430
451 453 454 458
158 228 297 364
347 361 385 408
317 361 385 408
383 386 392 408
237 301 370 408
424 426 428 432
146 217 284 352
75 80 85 90
421 434 461 487
377 434 461 487
462 465 472 487
287 358 436 487
509 510 512 516
184 263 339 414
400 415 441 467
365 415 441 467
439 442 449 467
276 346 424 467
484 486 488 492
173 252 327 403
378 395 420 445
353 395 420 445
415 418 426 445
264 334 412 445
458 460 462 466
162 240 315 391
355 374 398 423
340 374 398 423
389 393 401 423
252 322 399 423
430 432 434 440
150 229 303 379
Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total gross capacity. 3. SHC = Sensible heat capacity.
Table PD-20a – 120 kW (33 Ton) Gross Cooling Capacity (kW) (SI) Ambient Temperature – °C 29.4
35.0
40.6 46.1 Entering Wet BulbTemperature – °C 19.4 22.8 16.1 19.4 22.8 16.1 19.4 TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
Ent DB (°C)
16.1 TGC SHC
19.4 TGC SHC
23.9 4720 26.7 29.4 32.2
114.0 90.0 115.5 106.1 118.7 118.7 125.4125.4
126.9 70.9 127.2 86.5 127.8 102.3 129.2 118.4
140.7 141.0 141.3 141.6
50.1 66.5 82.4 98.2
108.4 86.7 109.9102.9 114.0 114.0 120.5 120.5
120.7 67.7 121.0 83.2 121.9 99.1 123.4 115.2
23.9 26.7 29.4 32.2
116.6 94.7 118.4 112.5 123.1123.1 130.1 130.1
129.2 73.9 129.5 90.6 130.7 108.1 132.5 125.7
143.0 51.0 143.6 68.9 143.9 86.5 144.2 103.5
110.8 91.1 112.5 109.0 117.8 117.8 124.8 124.8
122.8 70.6 136.3 47.8 104.6 87.6 123.4 87.3 136.6 65.6 106.7 105.8 124.6 104.6 137.2 83.2 112.5 112.5 126.3 122.5 137.5 100.2 119.3 119.3
116.3 67.4 1 29.0 116.6 83.8 129.2 117.8 101.1129.8 120.2 119.0 130.4
23.9 5660 26.7 29.4 32.2
118.7 99.1 121.0 118.7 126.9126.9 133.9 133.9
131.3 76.8 131.9 94.7 133.1 113.7 135.4 133.1
145.1 51.9 145.7 71.2 145.9 90.3 146.5 108.4
112.8 95.8 114.6 114.6 121.6 121.6 128.7 128.7
124.8 73.6 138.0 48.6 125.4 91.4 138.6 68.0 126.6 110.2 138.9 87.0 128.7 128.7 139.8 105.2
106.7 92.3 109.0 109.0 116.1 116.1 122.8 122.8
118.1 70.3 130.7 45.4 99.9 88.5 110.8 66.8 118.7 87.9 131.3 64.8 103.2 103.2 111.4 84.4 120.2 106.7 131.6 83.5 109.9 109.9 113.1 103.2 122.8 122.8 132.5 101.7 116.6 116.6 116.6 116.6
122.8 42.2 123.4 61.3 123.7 79.7 124.8 98.2
52.8 73.6 93.8 113.4
114.6 100.2 117.5 117.5 124.8124.8 131.9 131.9
126.6 127.2 128.7 131.9
49.5 70.3 90.3 110.2
108.4 96.4 112.0 112.0 119.0 119.0 126.0 126.0
119.6 73.0 132.2 46.3 101.7 92.9 112.2 120.2 91.7 132.8 66.8 105.8 105.8 113.1 121.9 112.2 133.1 87.0 112.8 112.8 114.9 126.0 126.0 134.2 106.7 119.6 119.6 119.6
124.3 124.8 125.4 126.6
149.2 53.9 149.5 77.1 150.1 99.4 151.2 121.3
117.2 107.0 121.6 121.6 129.2129.2 136.9 136.9
128.7 80.9 141.8 50.7 129.5 101.4 142.4 73.9 131.6 124.3 143.0 95.8 136.9 136.9 144.2 118.1
110.8 103.5 115.8 115.8 123.1 123.1 130.4 130.4
121.6 77.4 134.2 47.5 104.0 99.6 114.0 73.9 122.5 97.9 134.8 70.3 109.6 109.6 115.2 94.4 124.8 120.7 135.4 92.3 116.6 116.6 117.5 116.9 130.4 130.4 136.6 114.6 124.0 124.0 124.0 124.0
L/s
5190
22.8 TGC SHC
23.9 120.7103.5 133.1 79.7 146.8 6140 26.7 122.8 122.8 133.6 98.8 147.4 29.4 130.4130.4 135.1 119.3 147.4 32.2 137.7 137.7 137.7 137.7 148.6 23.9 123.4 110.5 6890 26.7 127.2 127.2 29.4 135.1135.1 32.2 142.7 142.7
135.4 84.1 136.3 104.9 138.3 127.8 142.7 142.7
16.1 TGC SHC
76.5 95.2 115.8 131.9
133.9 134.2 134.8 135.1
139.8 140.4 140.7 141.6
46.9 63.3 79.4 95.0
102.6 83.2 104.0 99.4 108.7 108.7 115.2 115.2
114.3 114.6 115.5 117.2
64.5 126.9 79.7 127.2 95.5 127.8 111.7128.1
43.7 96.1 79.7 107.3 60.1 97.9 95.8 107.9 75.9 103.2 103.2 108.7 91.4 109.3 109.3 110.5
61.0 76.2 92.0 108.1
22.8 TGC SHC 119.3 40.4 119.9 56.6 120.2 72.7 120.7 87.9
44.5 98.2 84.1 109.3 63.9 121.3 41.3 62.4 100.2 100.2 109.6 80.3 121.6 58.9 79.7 106.7 106.7 111.1 97.6 122.2 76.5 96.7 113.4 113.4 113.1 113.1 122.8 93.2
69.5 88.2 108.4 119.6
42.8 63.6 83.2 103.2
126.0 44.0 126.6 67.1 127.2 88.8 129.0 111.1
Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total gross capacity. 3. SHC = Sensible heat capacity.
RT-PRC007-EN
39
Performance Data
50 Hz
Table PD-21 – 42 Ton Gross Cooling Capacities (MBh) (I-P) AmbientTemperature – °F 85
cfm 12500
13500
14500
15500
16500
Ent DB (°F)
61 TGC SHC
95
67 TGC SHC
73 TGC SHC
61 TGC SHC
105 115 Entering Wet BulbTemperature – °F 67 73 61 67 73 61 67 TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
73 TGC SHC
75 80 85 90
469 476 498 526
385 459 498 526
519 521 525 533
298 369 440 513
574 576 578 580
206 279 351 421
446 454 477 504
372 446 477 504
494 495 500 508
286 355 427 500
546 548 550 552
193 267 338 408
421 428 455 482
358 428 455 482
467 469 474 481
272 342 413 481
517 519 521 523
180 254 325 394
395 406 432 458
344 406 432 458
438 441 446 458
259 328 399 458
486 488 489 493
167 240 311 380
75 80 85 90
476 485 511 540
402 481 511 540
526 528 533 543
309 383 460 539
582 583 585 588
209 288 365 440
453 462 489 518
388 462 489 518
500 502 508 517
296 370 447 517
553 555 556 560
196 275 351 427
428 440 467 494
374 440 467 494
472 475 481 494
283 356 433 494
523 525 526 530
183 262 338 413
401 416 443 470
360 416 443 470
444 447 453 469
269 342 419 469
491 — — —
170 — — —
75 80 85 90
483 494 523 553
418 494 523 553
532 535 541 552
319 398 480 552
588 590 591 595
211 296 378 458
459 472 501 530
404 472 501 530
506 509 515 530
306 384 467 530
558 561 562 567
199 283 364 445
434 449 477 506
390 449 477 506
478 481 488 506
293 371 453 506
528 530 532 537
186 270 351 431
407 425 453 480
375 425 453 480
448 452 459 480
279 356 439 480
— — — —
— — — —
75 80 85 90
489 504 534 564
433 504 534 564
538 541 548 564
329 412 500 564
593 595 597 602
214 304 390 476
465 482 511 541
420 482 511 541
511 514 522 541
316 399 487 541
563 566 568 573
202 291 377 463
439 458 487 516
406 458 487 516
482 486 494 516
302 385 473 516
532 535 537 542
189 278 363 449
412 434 462 490
391 434 462 490
452 457 465 490
289 370 458 490
— — — —
— — — —
75 80 85 90
495 513 544 575
449 513 544 575
543 546 554 575
339 426 520 575
598 600 603 608
217 312 403 494
470 491 521 551
435 491 521 551
515 519 528 551
326 413 506 551
568 570 573 578
204 299 390 481
444 467 496 526
421 467 496 526
486 491 500 526
312 399 492 526
536 539 542 548
191 286 376 467
417 441 470 —
406 441 470 —
456 461 470 —
295 384 470 —
— — — —
— — — —
Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total gross capacity. 3. SHC = Sensible heat capacity.
Table PD-21a – 148 kW (42 Ton) Gross Cooling Capacity (kW) (SI) Ambient Temperature – °C 35.0 40.6 46.1 Entering Wet Bulb Temperature – °C 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC 29.4
L/s 5900
6370
6840
7320
7790
Ent DB (°C) 75 80 85 90
137 140 146 154
113 135 146 154
152 87 153 108 154 129 156 150
168 60 169 82 169 103 170 123
131 133 140 148
109 131 140 148
145 145 147 149
84 104 125 147
160 161 161 162
57 78 99 120
123 125 133 141
105 125 133 141
137 80 152 53 137 100 152 74 139 121 153 95 141 141 153 115
116 119 127 134
101 119 127 134
128 129 131 134
76 96 117 134
142 143 143 144
49 70 91 111
75 80 85 90
140 142 150 158
118 141 150 158
154 91 155 112 156 135 159 158
171 61 171 84 171 107 172 129
133 135 143 152
114 135 143 152
147 147 149 152
87 108 131 152
162 163 163 164
57 81 103 125
125 129 137 145
110 129 137 145
138 83 153 54 139 104 154 77 141 127 154 99 145 145 155 121
118 122 130 138
106 122 130 138
130 131 133 137
79 100 123 137
144 — — —
50 — — —
75 80 85 90
142 145 153 162
123 145 153 162
156 93 157 117 159 141 162 162
172 62 173 87 173 111 174 134
135 138 147 155
118 138 147 155
148 149 151 155
90 113 137 155
164 164 165 166
58 83 107 130
127 132 140 148
114 132 140 148
140 86 155 55 141 109 155 79 143 133 156 103 148 148 157 126
119 125 133 141
110 125 133 141
131 132 135 141
82 104 129 141
— — — —
— — — —
75 80 85 90
143 148 156 165
127 148 156 165
158 96 159 121 161 147 165 165
174 63 174 89 175 114 176 140
136 141 150 159
123 141 150 159
150 151 153 159
93 117 143 159
165 166 166 168
59 85 110 136
129 134 143 151
119 134 143 151
141 89 156 55 142 113 157 81 145 139 157 106 151 151 159 132
121 127 135 144
115 127 135 144
132 134 136 144
85 108 134 144
— — — —
— — — —
75 80 85 90
145 150 159 169
132 150 159 169
159 99 160 125 162 152 169 169
175 64 176 91 177 118 178 145
138 144 153 161
127 144 153 161
151 152 155 161
96 121 148 161
166 167 168 169
60 88 114 141
130 137 145 154
123 137 145 154
142 91 157 56 122 119 134 144 117 158 84 129 129 135 147 144 159 110 138 138 138 154 154 161 137 — — —
86 113 138 —
— — — —
— — — —
Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat. 2. TGC = Total gross capacity. 3. SHC = Sensible heat capacity.
40
RT-PRC007-EN
Performance Data
50 Hz
Table PD-22 – Electric Heat Air Temperature Rise (°F) Heater Input (kW) 26.9 40.4 53.8 67.3 80.7
Total MBh 92 138 184 230 276
7000 12.1 18.2 24.2 30.2 –
8000 10.6 15.9 21.2 26.5 –
9000 9.4 14.1 18.8 23.5 –
10000 8.5 12.7 16.9 21.2 25.4
11000 7.7 11.6 15.4 19.2 23.1
(I-P)
CFM 12000 7.1 10.6 14.1 17.6 21.2
13000 – 9.8 13.0 16.3 19.5
14000 – 9.1 12.1 15.1 18.1
15000 – 8.5 11.3 14.1 16.9
16000 – 7.9 10.6 13.2 15.9
17000 – 7.5 10.0 12.5 14.9
Notes: 1. Air temperature rise = (kW x 3413)/(scfm x 1.085). 2. All heaters on constant volume units provide 2 increments of capacity. 3. Air temperature rise in this table are based on heater operating at 415 volts.
Table PD-22a – Electric Heat Air Temperature Rise (Degrees Celsius) Heater Input (kW) 26.9 40.4 53.8 67.3 80.7
3300 6.8 10.2 13.6 17.0 —
3780 5.9 8.9 11.9 14.8 —
4250 5.3 7.9 10.5 13.2 —
4720 4.7 7.1 9.5 11.9 14.2
5190 4.3 6.5 8.6 10.8 13.0
L/s 5660 4.0 5.9 7.9 9.9 11.9
6140 — 5.5 7.3 9.1 11.0
6610 — 5.1 6.8 8.5 10.2
(SI)
7080 — 4.8 6.3 7.9 9.5
7550 — 4.5 5.9 7.4 8.9
8020 — 4.2 5.6 7.0 8.4
Notes: 1. Air temperature rise in this table are based on heater operating at 415 volts. 2. All heaters on constant volume units provide 2 increments of capacity.
Table PD-23 – Available Electric Heat kW Ranges Nominal Unit Size Tons 22.9 25.0 29.2 33.3 42.7
Nominal Voltage (V) 380 23-56 23-56 23-56 34-68 34-68
415 27-67 27-67 27-67 40-81 40-81
Notes: 1. kW ranges in this table are based on heater operating at nominal voltages 380 or 415.
Table PD-24 – Natural Gas Heating Capacities Tons 22.9-29.2
22.9-29.2 33.3-42.7 33.3-42.7
Unit Model No. YCD/YCH275**L YCD/YCH300**L YCD/YCH350**L YCD/YCH275**H YCD/YCH300**H YCD/YCH350**H YCD/YCH400**L YCD/YCH500**L YCD/YCH400**H YCD/YCH500**H
Heat Input MBh (kW) (See Note 1)
Heating Output MBh (kW) (See Note 1)
AirTemp. Rise, °F (°C)
290,000 (85)
243,000 (69)
10-40 (-12.2 , 4.4)
500,000 (147)
405,000 (119)
25-55 (-3.9 , 12.8)
335,000 (98)
271,350 (80)
5-35 (-15 , 1.6)
670,000 (196)
542,700 (159)
20-50 (-6.7 , 10)
Note: 1. Total heating capacity.
RT-PRC007-EN
41
Performance Data
50 Hz
Table PD-25 – Supply Fan Performance – 23-29 Ton (I-P)
scfm
0.25 rpm bhp
0.50 rpm bhp
0.75 rpm bhp
Static Pressure (in. wg) 1.00 1.25 rpm bhp rpm bhp
rpm
bhp
1.75 rpm bhp
2.00 rpm bhp
2.25 rpm bhp
6670 7085 7500 7915 8330 8745 9160 9575 9990 10405 10820 11235 11650 12065
283 291 299 306 313 321 330 339 349 360 371 383 394 405
351 358 364 371 378 386 394 403 411 419 426 434 441 449
410 413 418 425 433 439 445 452 459 467 475 483 492 500
469 469 472 475 478 484 492 499 505 511 518 525 532 540
573 574 574 574 574 574 577 580 583 588 595 603 610 616
3.20 3.37 3.55 3.72 3.89 4.08 4.30 4.53 4.80 5.09 5.46 5.85 6.25 6.61
617 619 619 620 620 620 620 622 624 628 631 634 642 649
659 660 661 661 662 663 664 663 663 665 668 671 675 680
696 698 699 701 702 702 703 703 703 703 705 707 710 714
0.80 0.90 1.02 1.14 1.27 1.42 1.58 1.76 1.95 2.17 2.41 2.66 2.93 3.23
1.18 1.31 1.43 1.58 1.75 1.93 2.12 2.32 2.54 2.77 3.00 3.25 3.51 3.79
1.58 1.70 1.86 2.05 2.25 2.43 2.62 2.84 3.08 3.34 3.62 3.90 4.21 4.53
2.08 2.21 2.35 2.51 2.69 2.92 3.18 3.44 3.68 3.92 4.20 4.50 4.83 5.18
524 524 524 524 527 530 533 538 545 552 560 566 572 578
2.63 2.78 2.92 3.08 3.26 3.45 3.67 3.93 4.24 4.57 4.90 5.19 5.51 5.83
1.50
3.78 3.98 4.18 4.38 4.58 4.79 4.99 5.22 5.49 5.77 6.07 6.41 6.84 7.30
4.37 4.59 4.82 5.04 5.27 5.51 5.74 5.96 6.21 6.49 6.80 7.13 7.50 7.90
4.96 5.22 5.46 5.73 5.99 6.24 6.50 6.76 7.02 7.28 7.59 7.90 8.26 8.67
Table PD-25 – Supply Fan Performance – 23-29 Ton (I-P) Continued Static Pressure (in. wg) scfm
rpm
2.50 bhp
6670 7085 7500 7915 8330 8745 9160 9575 9990 10405 10820 11235 11650 12065
733 735 736 737 739 740 740 740 741 742 741 742 745 747
5.60 5.86 6.13 6.40 6.70 6.99 7.25 7.54 7.83 8.14 8.41 8.74 9.11 9.47
2.75 rpm bhp
3.00 rpm bhp
767 769 771 772 773 775 776 777 776 777 777 778 778 779
800 802 803 806 807 808 809 810 811 812 812 812 812 811
6.23 6.52 6.82 7.10 7.41 7.73 8.06 8.38 8.65 8.99 9.31 9.63 9.96 10.34
6.88 7.18 7.49 7.83 8.16 8.49 8.83 9.17 9.51 9.86 10.21 10.55 10.89 11.24
Table PD-25a – Supply Fan Performance – 82-105 kW (SI)
(L/s)
62.9 rpm (kW)
124.1 rpm (kW)
186.2 rpm (kW)
Static Pressure (Pascals) 248.3 310.4 372.5 rpm (kW) rpm (kW) rpm (kW)
434.6 rpm (kW)
496.7 rpm (kW)
558.8 rpm (kW)
3148 3344 3539 3735 3931 4127 4323 4519 4715 4910 5106 5302 5498 5694
283 291 299 306 313 321 330 339 349 360 371 383 394 405
351 358 364 371 378 386 394 403 411 419 426 434 441 449
410 413 418 425 433 439 445 452 459 467 475 483 492 500
469 469 472 475 478 484 492 499 505 511 518 525 532 540
617 619 619 620 620 620 620 622 624 628 631 634 642 649
659 660 661 661 662 663 664 663 663 665 668 671 675 680
696 698 699 701 702 702 703 703 703 703 705 707 710 714
0.59 0.67 0.76 0.85 0.95 1.06 1.18 1.31 1.45 1.62 1.80 1.98 2.19 2.41
0.88 0.98 1.07 1.18 1.30 1.44 1.58 1.73 1.89 2.06 2.24 2.42 2.62 2.83
1.17 1.27 1.39 1.53 1.68 1.81 1.95 2.12 2.30 2.49 2.70 2.91 3.14 3.38
1.55 1.65 1.75 1.87 2.01 2.18 2.37 2.56 2.74 2.93 3.13 3.36 3.60 3.87
524 524 524 524 527 530 533 538 545 552 560 566 572 578
1.96 2.07 2.18 2.29 2.43 2.58 2.74 2.93 3.17 3.40 3.65 3.87 4.11 4.35
573 574 574 574 574 574 577 580 583 588 595 603 610 616
2.39 2.52 2.64 2.77 2.90 3.04 3.21 3.38 3.58 3.79 4.07 4.37 4.66 4.93
2.82 2.97 3.12 3.26 3.41 3.57 3.72 3.89 4.09 4.31 4.53 4.78 5.10 5.44
3.26 3.42 3.59 3.76 3.93 4.11 4.28 4.45 4.63 4.84 5.07 5.32 5.59 5.89
3.70 3.89 4.07 4.27 4.46 4.65 4.84 5.04 5.23 5.43 5.66 5.89 6.16 6.46
Notes: 1. Supply fan performance table includes internal resistance of rooftop. For total static pressure determination, system external static must be added to appropriate component static pressure drops, (evaporator coil, filters, optional economizer, optional heating system, optional roof curb). 2. The pressure drops from the supply fan to the space should not exceed 2.25” (558.8 Pa) positive. 3. Maximum air flow 23 ton (80 kW) is 4756 L/s, 25 ton is 5190 L/s, 29 ton is 5663 L/s 4. Maximum motor kW for 23 ton unit is 7.5 (10 hp), 25 ton is 7.5 kW (10 hp), 29 ton is 11.2 kW (15 hp). Continued on the following page.
42
RT-PRC007-EN
Performance Data
50 Hz
Figure PD-4 — Supply Fan Performance — 23-29 Ton Supply Fan Performance 4.0 (996)
M F C O W % 0 5
8 0 0 R P M
3.5 (872)
M F C O W % 6 0
7 0 0 R P M
3.0 (747)
M C F O W % 7 0
2.5 (623) F M O C W % 8 0
6 0 0 R P M
) C W n I ( e r 2.0(498) u s e r P c i t a t S 1.5(374)
1 5 H P
5 0 0 R P M
1.0 (249)
1 0 H P 7 . 5 H P
4 0 0 R P M
M C F W O % 9 0
5 H P 3 H P
0.5 (125)
0.0 (0.0) 0
2000
4000
6000
8000
10000
12000
14000
16000
18000
20000
22000
24000
26000
Volumetric Airflow Rate(CFM) (0)
(.94)
(1.89)
(2.83)
(3.78)
(4.72)
(5.66)
(6.61)
(7.55)
(8.5)
(9.44)
(10.38)
(11.33)
(12.27)
L/S in 1000's
Table PD-25a – Supply Fan Performance – 23-29 Ton kW (SI) Continued Static Pressure (Pascals)
(L/s) 3148 3344 3539 3735 3931 4127 4323 4519 4715 4910 5106 5302 5498 5694
rpm
620.9 (kW)
733 735 736 737 739 740 740 740 741 742 741 742 745 747
4.18 4.37 4.57 4.77 5.00 5.21 5.41 5.62 5.84 6.07 6.27 6.52 6.79 7.06
RT-PRC007-EN
683.0 rpm (kW) 767 769 771 772 773 775 776 777 776 777 777 778 778 779
4.65 4.86 5.08 5.29 5.53 5.76 6.01 6.25 6.45 6.70 6.94 7.18 7.43 7.71
745.1 rpm (kW) 800 802 803 806 807 808 809 810 811 812 812 812 812 811
5.13 5.36 5.58 5.84 6.08 6.33 6.58 6.84 7.09 7.35 7.62 7.87 8.12 8.38
43
Performance Data
50 Hz
Table PD-26 – Supply Fan Performance – 33 and 42 Ton (I-P)
cfm
0.25 rpm bhp
0.50 rpm bhp
0.75 rpm bhp
1.00 rpm bhp
9996 10829 11662 12495 13328 14161 14994 15827 16660
273 287 301 315 329 344 358 373 388
324 336 348 360 373 387 401 415 429
372 383 390 401 412 424 437 449 463
417 422 432 442 450 459 470 482 495
1.46 1.78 2.14 2.53 2.96 3.45 3.99 4.58 5.24
1.95 2.30 2.69 3.12 3.60 4.14 4.77 5.45 6.19
2.49 2.87 3.27 3.74 4.27 4.85 5.48 6.17 6.93
3.04 3.44 3.91 4.41 4.94 5.55 6.23 6.98 7.78
Static Pressure (in. wg) 1.25 1.50 rpm bhp rpm bhp 458 464 469 476 486 495 503 513 525
3.64 4.06 4.53 5.07 5.67 6.31 6.98 7.75 8.61
495 501 506 512 518 527 538 546 554
4.25 4.71 5.21 5.76 6.38 7.08 7.83 8.61 9.43
1.75 rpm bhp
2.00 rpm bhp
2.25 rpm bhp
2.50 rpm bhp
535 535 541 546 551 557 565 576 586
572 572 573 578 584 589 594 602 613
605 606 607 609 614 619 625 630 637
636 638 639 639 642 648 653 659 664
4.92 5.38 5.91 6.49 7.12 7.83 8.61 9.46 10.36
5.59 6.11 6.64 7.24 7.91 8.62 9.41 10.30 11.26
6.23 6.81 7.41 8.03 8.71 9.45 10.27 11.14 12.13
6.90 7.53 8.17 8.82 9.52 10.31 11.13 1 2.04 1 3.04
Table PD-26 – Supply Fan Performance – 33 and 42 Ton (I-P) Continued
cfm
2.75 rpm bhp
Static Pressure (in. wg) 3.00 3.25 rpm bhp rpm bhp
3.50 rpm bhp
9996 10829 11662 12495 13328 14161 14994 15827 16660
665 669 671 670 671 674 680 686 691
691 697 699 700 700 702 706 711 717
743 748 751 755 756 757 757 761 765
7.63 8.24 8.97 9.66 10.38 11.16 12.03 12.99 13.97
8.35 8.99 9.73 10.49 11.27 12.08 12.96 13.92 14.94
717 722 727 728 729 730 731 737 742
9.10 9.77 10.47 11.33 12.17 13.01 13.87 14.90 15.96
9.87 10.57 11.26 12.13 13.04 13.96 14.88 15.87 16.94
Table PD-26a – Supply Fan Performance – 105-148 kW (SI)
(L/s)
62.1 rpm (kW)
124,2 rpm (kW)
186.3 rpm (kW)
248.1 rpm (kW)
4717 5111 5504 5897 6290 6683 7076 7469 7862
273 287 301 315 329 344 358 373 388
324 336 348 360 373 387 401 415 429
372 383 390 401 412 424 437 449 463
417 422 432 442 450 459 470 482 495
1.09 1.33 1.59 1.88 2.21 2.57 2.97 3.42 3.91
1.46 1.72 2.00 2.33 2.68 3.09 3.56 4.07 4.61
1.86 2.14 2.44 2.79 3.19 3.62 4.09 4.60 5.17
2.27 2.57 2.91 3.29 3.69 4.14 4.65 5.20 5.80
Static Pressure (Pascals) 310.4 372.5 rpm (kW) rpm (kW) 458 464 469 476 486 495 503 513 525
2.72 3.03 3.38 3.78 4.23 4.70 5.21 5.78 6.42
495 501 506 512 518 527 538 546 554
3.17 3.51 3.88 4.30 4.76 5.28 5.84 6.42 7.03
434.6 rpm (kW)
496.7 rpm (kW)
558.8 rpm (kW)
620.9 rpm (kW)
535 535 541 546 551 557 565 576 586
572 572 573 578 584 589 594 602 613
605 606 607 609 614 619 625 630 637
636 638 639 639 642 648 653 659 664
3.67 4.01 4.41 4.84 5.31 5.84 6.42 7.06 7.73
4.17 4.55 4.95 5.40 5.90 6.43 7.02 7.68 8.40
4.64 5.08 5.52 5.99 6.49 7.05 7.66 8.31 9.05
5.14 5.62 6.09 6.57 7.10 7.69 8.30 8.98 9.72
Table PD-26a – Supply Fan Performance – 105-148 kW (SI) Continued
(L/s)
683.0 rpm (kW)
Static Pressure (Pascals) 745.1 807.2 rpm (kW) rpm (kW)
869.3 rpm (kW)
4717 5111 5504 5897 6290 6683 7076 7469 7862
665 669 671 670 671 674 680 686 691
691 697 699 700 700 702 706 711 717
743 748 751 755 756 757 757 761 765
5.69 6.14 6.69 7.20 7.74 8.32 8.97 9.69 10.42
6.22 6.70 7.25 7.83 8.41 9.01 9.66 10.38 11.14
717 722 727 728 729 730 731 737 742
6.78 7.28 7.81 8.45 9.07 9.71 10.35 11.11 11.90
7.36 7.88 8.40 9.05 9.72 10.41 11.10 11.84 12.63
Notes: 1. Supply fan performance table includes internal resistance of rooftop. For total static pressure determination, system external static must be added to appropriate component static pressure drops, (evaporator coil, filters, optional economizer, optional heating system, optional roof curb). 2. The pressure drops from the supply fan to the space should not exceed 2.5” wg (620.9 Pa) positive. 3. Max cfm for 33 ton unit 6825 L/s, 42 ton -7860 L/s 4. Max motor hp for 33 ton unit-11.2 kW (15 hp), 42 ton 14.9 kW (20 hp)
44
RT-PRC007-EN
Performance Data
50 Hz
Figure PD-5 – Supply Fan Performance – 33 and 42 Ton (I-P)
5 (1245) M F C O W % 4 0
8 0 0 R P M
4 (996)
M C F O W % 5 0
F M O C W % 6 0
7 5 0 R P M 7 0 0 R P M
) 3 (747) C W n I ( e r u s e r P c i t a 2 (498) t S
6 5 0 R P M
F M O C W % 7 0
6 0 0 R P M 5 5 0 R P M
2 0 H P
5 0 0 R P M 4 5 0 R P M 4 0 0 R P M 3 5 0 R P M 3 0 0 R P M
1 (249)
1 5 H P
7 . 5 H P
M C F W O % 0 8
1 0 H P
C F M W O 9 0 %
0 (0.0) 0 (0)
2000
4000
6000
(.94)
(1.89)
(2.83)
8000 (3.78)
10000 (4.72)
12000 14000 16000 Volumetric Airflow Rate(CFM) (5.66)
(6.61)
(7.55)
18000 (8.5)
20000 (9.44)
22000 (10.38)
24000 (11.33)
26000 (12.27)
28000 (13.22)
L/S in 1000's
RT-PRC007-EN
45
Performance Data
50 Hz
Table PD-27 – Component Static Pressure Drops — in. wg (I-P) Nominal Std Tons (kW)
23 (80)
25 (88)
29 (10 3)
33 (11 8)
42 (14 6)
CFM Std Air 6670 7500 8330 9170 10000 7500 8330 9170 10000 8750 9580 11200 12100 10000 10800 11700 12500 13300 14200 12500 13300 14200 15800 16700
Heating System Gas Heat Electric Heat Low High 1 Elem ent 2 Elem ent 0.07 0.05 0.04 0.05 0.08 0.07 0.06 0.06 0.1 0.08 0.07 0.08 0.13 0.1 0.08 0.09 0.15 0.12 0.1 0.11 0.08 0.07 0.06 0.06 0.1 0.08 0.07 0.08 0.13 0 .1 0.08 0.09 0.15 0.12 0.1 0.11 0.11 0.09 0.08 0.08 0.14 0.11 0.09 0.1 0.19 0.15 0.13 0.14 0.22 0.17 0.15 0.16 0.01 0.03 0.07 0.11 0.01 0.03 0.08 0.13 0.01 0.04 0.1 0.15 0 .01 0.04 0.11 0.17 0.02 0.05 0.12 0.19 0.02 0.06 0.14 0.22 0.01 0.04 0.11 0.17 0.02 0.05 0.12 0.19 0 .02 0.06 0.16 0.24 0.02 0.07 0.18 0.27 0.03 0.08 0.2 0.3
ID Coil Dry Wet 0.07 0 .09 0.08 0.1 0.09 0 .12 0.12 0 .14 0.13 0 .17 0.08 0.1 0.09 0 .12 0.12 0 .14 0.13 0 .17 0.16 0.2 0.18 0 .23 0.24 0.3 0.27 0 .33 0.15 0 .19 0.17 0 .22 0.2 0 .24 0.22 0.27 0.24 0.3 0.27 0 .33 0.29 0 .36 0.32 0.4 0.36 0.44 0.42 0 .53 0.46 0 .57
Filters Throwaway High Eff. Filters 2" 2” 4” 0.05 0.08 0.07 0.07 0.11 0.1 0.08 0.13 0.12 0.09 0.15 0.14 0.11 0.18 0.16 0.07 0.11 0.1 0.08 0.13 0.12 0.09 0.15 0.14 0.11 0.18 0.17 0.09 0.15 0.13 0.1 0.17 0.16 0.12 0.21 0.19 0.13 0.22 0.21 0.11 0.18 0.16 0.12 0.21 0.18 0.13 0.23 0.2 0.14 0.26 0.23 0.15 0.28 0.25 0.17 0.32 0.28 0.14 0.26 0.23 0.15 0.28 0.25 0.17 0.34 0.29 0.19 0.38 0.34 0.2 0.41 0.36
Inlet Guide Vanes Econom izer 0.04 0.331 0.06 0.04 0.07 0.049 0.08 0.059 0.1 0.07 0.06 0.04 0.07 0.049 0.08 0.059 0.12 0.07 0.08 0.054 0.11 0.065 0.13 0.077 0.15 0.091 0.03 70 0.04 0.076 0.04 0.085 0.05 0.096 0.06 0.107 0.07 0.12 0.05 0.095 0.06 0.108 0.07 0.12 0.08 0.136 0.09 0.155
Note: 1. Static pressure drops of accessory components must be added to external static pressure to enter fan performance tables.
46
RT-PRC007-EN
Performance Data
Table PD-27a – Component Static Pressure Drops — Pa Nominal Std Tons (kW)
80 (23)
88 (25)
103 (29)
118 (33)
146 (42)
L/s Std Air 3150 3540 3930 4320 4720 3540 3930 4320 5120 4130 4520 4920 5310 4720 5120 5510 5900 6290 6680 5900 6290 6680 7070 7470
50 Hz
(SI)
Heating System Gas Heat Electric Heat Low High 1 Element 2 Element 17 13 11 12 21 16 14 15 26 20 17 19 31 24 21 23 37 29 25 27 21 16 14 15 26 20 17 19 31 24 21 23 44 34 29 32 29 22 19 21 34 27 23 25 41 32 27 29 47 37 32 34 2 7 18 27 3 8 21 32 3 10 24 37 4 11 27 42 4 12 31 48 5 14 35 54 4 11 27 42 4 12 31 48 5 14 35 54 5 16 39 60 6 18 44 67
ID Coil Dry Wet 17 22 19 24 22 29 29 34 31 41 19 24 22 29 29 34 31 41 38 48 43 55 58 72 65 79 36 46 41 53 48 58 53 65 58 72 65 79 70 86 77 96 86 106 101 127 110 137
Filters Throwaway High Eff. Filters Inlet Guide Adder 50 mm 100 mm Vanes Economizer 12 19 17 11 0.05 17 26 24 14 0.07 19 31 29 17 0.08 22 36 34 21 0.1 26 43 38 25 0.12 17 26 24 14 0.07 19 31 29 17 0.08 22 36 34 25 0.12 26 43 41 29 0.14 22 36 31 19 0.09 24 41 38 23 0.11 29 50 46 27 0.13 31 53 50 32 0.15 26 43 38 8 0.12 29 50 43 10 0.14 31 55 48 11 0.16 34 62 55 13 0.18 36 67 60 15 0.21 41 77 67 16 0.24 34 62 55 13 0.18 36 67 60 15 0.21 41 82 72 16 0.24 46 91 82 18 0.27 48 98 86 21 0.3
Note: 1. Static pressure drops of accessory components must be added to external static pressure to enter fan performance tables.
RT-PRC007-EN
47
Performance Data
50 Hz
Table PD-28 – Supply Air Fan Drive Selections 5 hp Nominal Tons (kW)
23 (80)
25 (88)
29 (103)
33 (118)
42 (146)
rpm 458 500 541 583 625 458 500 541 583 625 500 541 583 658 664 417 437 479 521 562 604 437 479 521 562
7.5 hp Drive No A B C
rpm
10 hp Drive No
583 625*
D E
583 625
D E
541 583
C D
15 hp
rpm
Drive No
658** 664*
F G
521 562 604
L M N
521 562
L M
rpm
Drive No
604
N
A B C
B
417 437 479
437 479
H J K
J K
604 Note: *For YC gas/electrics only. **For TC and TE Cooling only and with electric Heat units only.
Table PD-29 – Power Exhaust Fan Performance (I-P) Exhaust Airflow (cfm) 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000 9500 10000
External Static Pressure – Inches of Water High Med Speed Speed ESP ESP 0.800 – 0.780 – 0.750 – 0.720 – 0.680 – 0.650 0.420 0.610 0.380 0.560 0.360 0.520 0.330 0.460 0.310 0.420 0.290 0.360 0.270 0.310 0.240 0.250 0.200 0.200 0.160 0.150 0.120 0.100 0.060 0.040 0.000 0.000
–
Table PD-29a – Power Exhaust Fan Performance (SI) Low Speed ESP – – 0.400 0.380 0.370 0.360 0.340 0.320 0.300 0.280 0.250 0.230 0.190 0.150 0.120 0.070 0.000 –
Exhaust Airflow (L/s) 470 710 940 1180 1420 1650 1890 2120 2360 2600 2830 3070 3300 3540 3780 4010 4250 4480
–
4720
External Static Pressure – Pa High Med Speed Speed ESP ESP 199.3 – 194.3 – 186.8 – 179.4 – 169.4 – 161.9 104.6 152.0 94.7 139.5 89.7 129.5 82.2 114.6 77.2 104.6 72.2 89.7 67.3 77.2 59.8 62.3 49.8 49.8 39.9 37.4 29.9 24.9 14.9 10.0 0.0 0.0
Low Speed ESP – – 99.6 94.7 92.2 89.7 84.7 79.7 74.7 69.7 62.3 57.3 47.3 37.4 29.9 17.4 0.0 –
–
–
Notes: 1. Performance in table is with both motors operating. 2. High speed = both motors on high speed. Medium speed is one motor on high speed and one on low speed. Low speed is both motors on low speed. 3. Power Exhaust option is not to be applied on systems that have more return air static pressure drop than the maximum shown in the table for each motor speed tap.
48
RT-PRC007-EN
Controls
VAV Units Only
Variable Frequency Drives (VFD) Control
Sequence of Operation
Variable frequency drives are driven by a modulating 2-10 vdc signal from the VAV module. A pressure transducer measures duct static pressure, and the VFD is modulated to maintain the supply air static pressure within an adjustable user-defined range. The range is determined by the supply air pressure setpoint and supply air pressure deadband, which are set through a unit mounted potentiometer. Variable frequency drives provide supply fan motor speed modulation. The drive will accelerate or decelerate as required to maintain the supply static pressure setpoint. When subjected to high ambient return conditions the VFD shall reduce its output frequency to maintain operation. Bypass control is offered to provide full nominal airflow in the event of drive failure.
1 Supply Air Pressure Control Inlet Guide Vane Control Inlet guide vanes are driven by a modulating 2-10 vdc signal from the VAV Module. A pressure transducer measures duct static pressure, and the inlet guide vanes are modulated to maintain the supply air static pressure within an adjustable user-defined range. The range is determined by the supply air pressure setpoint and supply air pressure deadband, which are set through a unit mounted potentiometer. Inlet guide vane assemblies installed on the supply fan inlets regulate fan capacity and limit horsepower at lower system air requirements. When in any position other than full open, the vanes pre-spin intake air in the same direction as supply fan rotation. As the vanes approach the full-closed position, the amount of “spin” induced by the vanes increases at the same time that intake airflow and fan horsepower diminish. The inlet guide vanes will close when the supply fan is shut down.
Supply Air Static Pressure Limit The opening of the inlet guide vanes and VAV boxes are coordinated, with respect to time, during unit start up and transition to/from Occupied/Unoccupied modes to prevent overpressurization of the supply air ductwork. However, if for any reason the supply air pressure exceeds the fixed supply air static pressure limit of 3.5” W.C., the supply fan is shut down and the inlet guide vanes are closed. The unit is then allowed to restart three times. If the overpressurization condition occurs on the fourth time, the unit is shut down and a manual reset diagnostic is set and displayed at any of the remote panels with LED status lights or communicated to the Integrated Comfort system.
RT-PRC007-EN
2 Supply Air Temperature Controls Cooling/Economizer During occupied cooling mode of operation, the economizer (if available) and primary cooling are used to control the supply air temperature. The supply air temperature setpoint is user-defined at the unit mounted VAV Setpoint Potentiometer or at the remote panel. If the enthalpy of the outside air is appropriate to use “free cooling,” the economizer will be used first to attempt to satisfy the supply setpoint. On units with economizer, a call for cooling will modulate the fresh air dampers open. The rate of economizer modulation is based on deviation of the discharge temperature from setpoint, i.e., the further away from setpoint, the faster the fresh air damper will open. Note that the economizer is only allowed to function freely if ambient conditions are below the enthalpy control setting or below the return air enthalpy if unit has comparative enthalpy installed. If outside
air is not suitable for “economizing,” the fresh air dampers drive to the minimum open position. A field adjustable potentiometer on the Economizer Actuator,Tracer™, or a remote potentiometer can provide the input to establish the minimum damper position. At outdoor air conditions above the enthalpy control setting, primary cooling only is used and the fresh air dampers remain at minimum position. If the unit does not include an economizer, primary cooling only is used to satisfy cooling requirements.
Supply Air Setpoint Reset Supply air reset can be used to adjust the supply air temperature setpoint on the basis of a zone temperature, return air temperature, or on outdoor air temperature. Supply air reset adjustment is available on the unit mounted VAV Setpoint Potentiometer for supply air cooling control.
a Reset Based on Outdoor Air Temperature Outdoor air cooling reset is sometimes used in applications where the outdoor temperature has a large effect on building load. When the outside air temperature is low and the building cooling load is low, the supply air setpoint can be raised, thereby preventing subcooling of critical zones. This reset can lower usage of primary cooling and result in a reduction in primary cooling energy usage. There are two user-defined parameters that are adjustable through the VAV Setpoint Potentiometer: reset temperature setpoint and reset amount. The amount of reset applied is dependent upon how far the outdoor air temperature is below the supply air reset setpoint.The amount is zero where they are equal and increases linearly toward the value set at the reset amount input. The maximum value is 20 F. If the outdoor
49
Controls
air temperature is more than 20 F below the reset temperature setpoint the amount of reset is equal to the reset amount setpoint.
returned to VAV cooling mode.The Morning Warm-up setpoint is set at the unit mounted VAV Setpoint potentiometer or at a remote panel.
b
Morning Warm-up (MWU)
Reset Based On Zone Or Return Temperature
Morning warm-up control (MWU) is activated whenever the unit switches from unoccupied to occupied and the zone temperature is at least 1.5 F below the MWU setpoint. When MWU is activated the VAV box output will be energized for at least 6 minutes to drive all boxes open, the inlet guide vanes are driven full open, and all stages of heat (gas or electric) are energized. When MWU is activated the economizer damper is driven fully closed. When the zone temperature meets or exceeds the MWU setpoint minus 1.5 F, the heat will be staged down. When the zone temperature meets or exceeds the MWU setpoint then MWU will be terminated and the unit will switch over to VAV cooling.
Zone or return reset is applied to the zone(s) in a building that tend to overcool or overheat. The supply air temperature setpoint is adjusted based on the temperature of the critical zone(s) or the return air temperature. This can have the effect of improving comfort and/or lowering energy usage. The userdefined parameters are the same as for outdoor air reset. Logic for zone or return reset control is the same except that the origins of the temperature inputs are the zone sensor or return sensor respectively. The amount of reset applied is dependent upon how far the zone or return air temperature is below the supply air reset setpoint. The amount is zero where they are equal and increases linearly toward the value set at the reset amount potentiometer on the VAV Setpoint potentiometer.The maximum value is 3 F. If the return or zone temperature is more than 3 F below the reset temperature setpoint the amount of reset is equal to the reset amount setpoint.
3 Zone Temperature Control Unoccupied Zone Heating and Cooling During Unoccupied mode, the unit is operated as a CV unit. Inlet guide vanes and VAV boxes are driven full open. The unit controls zone temperature to the Unoccupied zone cooling and heating (heating units only) setpoints.
Daytime Warm-up During occupied mode, if the zone temperature falls to a temperature three degrees below the Morning Warm-up setpoint, Daytime Warm-up is initiated. The system changes to CV heating (full unit airflow), the VAV boxes are fully opened and the CV heating algorithm is in control until the Morning Warm-up setpoint is reached. The unit is then
50
CV Units Only Sequence of Operation 1 Occupied Zone Temperature Control Cooling/Economizer During occupied cooling mode, the economizer (if provided) and primary cooling are used to control zone temperature. If the enthalpy of outside air is appropriate to use “free cooling”, the economizer will be used first to attempt to satisfy the cooling zone temperature setpoint; then primary cooling will be staged up as necessary. On units with economizer, a call for cooling will modulate the fresh air dampers open. The rate of economizer modulation is based on deviation of the zone temperature from setpoint, i.e., the further away from setpoint, the faster the fresh air damper will open. First stage of cooling will be allowed to start after the economizer reaches full open. Note that the economizer is allowed to function freely only if ambient conditions are below the enthalpy control setting or below the return air enthalpy if unit has
comparative enthalpy. If outside air is not suitable for “economizing,” the fresh air dampers drive to the minimum open position. A field adjustable potentiometer on the Economizer Actuator, Tracer or a remote potentiometer can provide the input to establish the minimum damper position. At outdoor air temperatures above the enthalpy control setting, primary cooling only is used and the outdoor air dampers remain at minimum position. If the unit does not include an economizer, primary cooling only is used to satisfy cooling requirements.
Heating Gas Heating When heating is required the RTRM initiates the heating cycle through the ignition control module(s) (IGN).The IGN relay brings on the combustion fan motor. The ignition control module(s) begin the ignition process by preheating the hot surface ignitor(s). After the hot surface ignitor is preheated the gas valve is opened to ignite first stage. If ignition does not take place the IGN(s) will attempt to ignite 2 more times before locking out. When ignition does occur the hot surface ignitor is deenergized and then functions as a flame sensor. The RTRM will energize the supply fan contactor 45 seconds after the initiation of the heat cycle. If more capacity is needed to satisfy the heating setpoint, the RTRM will call for the second stage of heat by driving the combustion blower motor to high speed. When the space temperature rises above the heating setpoint, the RTRM terminates the heat cycle.
Electric Heating When heat is required, the RTRM initiates first stage heating by energizing the first stage electric heat contactor.The first stage electric heater bank(s) will be energized if the appropriate limits are closed. The RTRM will cycle first stage heat on and off as required to maintain zone temperature. If first stage cannot satisfy the requirement, the RTRM will energize the second stage electric heat contactor(s) if the appropriate limits are
RT-PRC007-EN
Controls
closed. The RTRM will cycle second stage on and off as required while keeping stage one energized. The supply fan is energized approximately 1 second before the electric heat contactors. When the space temperature rises above the heating setpoint, the RTRM deenergizes the supply fan and all electric heat contactors.
Supply AirTempering This feature is available only with Tracer™ or with systems using programmable zone sensors (CV only with economizer). For gas and electric heat units in the Heat mode but not actively heating, if the supply air temperature drops to 10 F below the occupied zone heating temperature setpoint, one stage of heat will be brought on to maintain a minimum supply air temperature. The heat stage is dropped if the supply air temperature rises to 10 F above the occupied zone heating temperature setpoint.
Auto Changeover When the System Mode is “Auto,” the mode will change to cooling or heating as necessary to satisfy the zone cooling and heating setpoints.The zone cooling and heating setpoints can be as close as 2 F apart.
Unoccupied Zone Temperature Control Cooling and Heating Both cooling or heating modes can be selected to maintain Unoccupied zone temperature setpoints. For Unoccupied periods, heating or primary cooling operation can be selectively locked out at the remote panels or TRACER.
Conventional Thermostat Interface ConventionalThermostat Interface (CTI) is a standard part of the RTRM. The CTI will allow only two steps of heating or cooling.The CTI provides zone temperature control only and is mutually
exclusive of the Trane Communications Interface (TCI).
Control Sequences of Operation Common to Both VAV and CV Units Ventilation override (VOM) Applying 24 volts to one of the three Ventilation Override inputs manually activates ventilation override. One input is provided to request the pressurize mode, the second input to request the purge mode, and the third input to request the exhaust mode. If more than one mode is requested at the same time, the pressurize request will have priority followed by purge. When any ventilation override mode is active, all heating and cooling is turned off. For the case where the unit is required to turn off, the emergency stop input is used. The ICS can also initiate any ventilation override mode.
Affected Function Pressurize 1 Heat/Cool IGV/VFD
RT-PRC007-EN
Mode and Priority Purge 2
Exhaust 3
off
off
off
open/full speed
open/full speed
open/full speed
Supply Fan
on
on
off
Exhaust Fan Economizer
off open
on open
on closed
VAV Boxes
forced open
forced open
normal operation
51
Controls
Coil Freeze Protection FROSTAT™ The FROSTAT system eliminates the need for hot gas bypass and adds a suction line surface temperature sensor to determine if the coil is in a condition of impending frost. If impending frost is detected primary cooling capacity is shed as necessary to prevent icing. All compressors are turned off after they have met their minimum 3 minute on times. The supply fan is forced on until the FROSTAT device no longer senses a frosting condition or for 60 seconds after the last compressor is shut off, whichever is longer.
Occupied/Unoccupied Switching
Night setback (unoccupied mode) is operated through the time clock provided in the sensors with night setback. When the time clock switches to night setback operation, the outdoor air dampers close and heating/cooling can be enabled or disabled. As the building load changes, the night setback sensor communicates the need for the rooftop heating/cooling (if enabled) function and the evaporator fan. The rooftop unit will cycle through the evening as heating/cooling (if enabled) is required in the space. When the time clock switches from night setback to occupied mode, all heating/cooling functions begin normal operation.
3
When using the night setback options with a VAV heating/cooling rooftop, airflow must be maintained through the rooftop unit. This can be accomplished by electrically tying the VAV boxes to the VAV heat relay contacts on the Low voltage terminal board or by using changeover thermostats. Either of these methods will assure adequate airflow through the unit and satisfactory temperature control of the building.
TRACER
Timed override Activation—ICS
Night Setback Sensors
When this function is initiated by pushing the override button on the ICS sensor, TRACER will switch the unit to the occupied mode. Unit operation (occupied mode) during timed override is terminated by a signal from TRACER.
There are 3 ways to switch Occupied/ Unoccupied:
1 NSB Panel
2 Electronic time clock or field-supplied contact closure
Trane’s night setback sensors are programmable with a time clock function that provides communication to the rooftop unit through a 2-wire communications link. The desired transition times are programmed at the night setback sensor and communicated to the unit.
52
Timed override Activation—Non-lCS When this function is initiated by the push of an override button on the programmable zone sensor, the unit will switch to the occupied mode. Automatic Cancellation of the Timed override Mode occurs after three hours of operation.
Comparative Enthalpy Control of Economizer The Economizer Actuator receives inputs from optional return air humidity and temperature sensors and determines whether or not it is feasible to economize. If the outdoor air enthalpy is greater than the return air enthalpy then it is not feasible to economize and the economizer damper will not open past its minimum position.
Fan Failure Switch The fan failure switch will disable all unit functions and “flash” the Service LED on the zone sensor.
Emergency Stop Input A binary input is provided on the RTRM for installation of field provided switch or contacts for immediate shutdown of all unit functions. The binary input is brought out to Low VoltageTerminal Board One (LTB1).
RT-PRC007-EN
Electrical Data
Electrical Service Sizing To correctly size electrical service wiring for your unit, find the appropriate calculations listed below. Each type of unit has its own set of calculations for MCA (Minimum Circuit Ampacity), MOP (Maximum Overcurrent Protection), and RDE (Recommended Dual Element fuse size). Read the load definitions that follow and then find the appropriate set of calculations based on your unit type. Set 1 is for cooling only and cooling with gas heat units, and set 2 is for cooling with electric heat units. Load Definitions: (To determine load values, see the Electrical Service Sizing Data Tables.) LOAD1 = CURRENT OF THE LARGEST MOTOR (COMPRESSOR OR FAN MOTOR) LOAD2 = SUM OF THE CURRENTS OF ALL REMAINING MOTORS LOAD3 = CURRENT OF ELECTRIC HEATERS LOAD4 = ANY OTHER LOAD RATED AT 1 AMP OR MORE
Set 1. Cooling Only Rooftop Units and Cooling with Gas Heat Rooftop Units MCA = (1.25 x LOAD1) + LOAD2 + LOAD4 MOP = (2.25 x LOAD1) + LOAD2 + LOAD4 Select a fuse rating equal to the MOP value. If the MOP value does not equal a standard fuse size as listed in NEC 240-6, select the next lower standard fuse rating. NOTE: If selected MOP is less than the MCA, then reselect the lowest standard maximum fuse size which is equal to or larger than the MCA, provided the reselected fuse size does not exceed 800 amps.
then reselect the RDE value to equal the MOP value. (Keep in mind when determining LOADS that crankcase heaters are disabled in the cooling mode). DSS = 1.15 x (LOAD1 + LOAD2 + LOAD4) Select a disconnect switch size equal to or larger than the DSS value calculated.
Set 2. Rooftop units with Electric Heat To arrive at the correct MCA, MOP, and RDE values for these units, you must perform two sets of calculations. First calculate the MCA, MOP, and RDE values as if the unit was in cooling mode (use the equations given in Set 1). Then calculate the MCA, MOP, and RDE values as if the unit was in the heating mode as follows. (Keep in mind when determining LOADS that the compressors and condenser fans don’t run while the unit is in the heating mode and crankcase heaters are disabled in the cooling mode.)
The selection MOP value will be the larger of the cooling mode MOP value or the heating mode MOP value calculated above. Select a fuse rating equal to the MOP value. If the MOP value does not equal a standard fuse size as listed in NEC 240-6, select the next lower standard fuse rating. NOTE: If selected MOP is less than the MCA, then reselect the lowest standard maximum fuse size which is equal to or larger than the MCA, provided the reselected fuse size does not exceed 800 amps. RDE = (1.5 x LOAD1) + LOAD2 + LOAD3 + LOAD4 The selection RDE value will be the larger of the cooling mode RDE value or the heating mode RDE value calculated above.
MCA = 1.25 x (LOAD1 + LOAD2 + LOAD4) + (1.25 x LOAD3)
Select a fuse rating equal to the RDE value. If the RDE value does not equal a standard fuse size as listed in NEC 240-6, select the next higher standard fuse rating. NOTE: If the selected RDE is greater than the selected MOP value, then reselect the RDE value to equal the MOP value.
For units using heaters equal to or greater than 50 kw.
DSS = 1.15 x (LOAD1 + LOAD2 + LOAD3 + LOAD4)
MCA = 1.25 x (LOAD1 + LOAD2 + LOAD4) + LOAD3
NOTE: Keep in mind when determining LOADS that the compressors and condenser fans don’t run while the unit is in the heating mode.
For units using heaters less than 50 kw.
The nameplate MCA value will be the larger of the cooling mode MCA value or the heating mode MCA value calculated above. MOP = (2.25 x LOAD1) + LOAD2 + LOAD3 + LOAD4
The selection DSS value will be the larger of the cooling mode DSS or the heating mode DSS calculated above. Select a disconnect switch size equal to or larger than the DSS value calculated.
Table ED-1 — Electrical Service Sizing Data — Electric Heat Module (Electric Heat Only) Models:TED/TEH 330 thru 600 Electric Heat FLA Nominal Unit Size (Tons)
Nominal Unit Voltage
RDE = (1.5 x LOAD1) + LOAD2 + LOAD4
27½
Select a fuse rating equal to the RDE value. If the RDE value does not equal a standard fuse size as listed in NEC 240-6, select the next higher standard fuse rating. NOTE: If the selected RDE is greater than the selected MOP value,
KW Heater 72 FLA —
208
36 FLA 74.9
54 FLA 112.4
30.0
230
86.6
129.9
—
—
—
35.0
460
43.3
65.0
86.6
108.3
—
40.0
575 208
— —
52.0 112.4
69.3 —
86.6 —
— —
50.0
108 FLA —
230
—
129.9
—
—
—
460
—
65.0
86.6
108.3
129.9
575
—
52.0
69.3
86.6
103.9
Notes: 1. All FLA in this table are based on heater operating at 208, 240, 480, and 600 volts.
RT-PRC007-EN
90 FLA —
53
Electrical Data
60 Hz
Table ED-2 — 27½-50 Ton Electrical Service Sizing Data 1 Compressor Allowable Electrical Voltage Model Characteristics Range TC/TE/YC*330 208/60/3 187-229
TC/TE/YC*360
TC/TE/YC*420
TC/TE/YC*480
TC/TE/YC*600
No/Ton 1/10,1/15
RLA (Ea.) 41.9/62.8
LRA (Ea.) 269/409
230/60/3
207-253
41.9/62.8
247/376
460/60/3
414-506
18.1/27.3
95/142
575/60/3
517-633
14.6/21.8
76/114
208/60/3
187-229
62.8
409
230/60/3
207-253
62.8
376
460/60/3
414-506
27.3
142
575/60/3
517-633
21.8
114
208/60/3
187-229
62.8
409
230/60/3
207-253
62.8
376
460/60/3
414-506
27.3
142
575/60/3
517-633
21.8
114
208/60/3
187-229
62.8/62.8/41.9
409/409/269
230/60/3
207-253
62.8/62.8/41.9
376/376/247
460/60/3
414-506
27.3/27.3/18.1
142/142/95
575/60/3
517-633
21.8/21.8/14.6
114/114/76
208/60/3
187-229
62.8
409
230/60/3
207-253
62.8
376
460/60/3
414-506
27.3
142
575/60/3
517-633
21.8
114
2/15
2/15
2/15,1/10
3/15
HP 7.5 10.0 7.5 10.0 7.5 10.0 7.5 10.0 7.5 10.0 7.5 10.0 7.5 10.0 7.5 10.0 7.5 10.0 15.0 7.5 10.0 15.0 7.5 10.0 15.0 7.5 10.0 15.0 10.0 15.0 10.0 15.0 10.0 15.0 10.0 15.0 10.0 15.0 20.0 10.0 15.0 20.0 10.0 15.0 20.0 10.0 15.0 20.0
Fan Motors Supply Condenser Standard/ Hi-Efficiency FLA FLA No. HP (Ea.) 22.3/21.5 3 1.1 7.0 29.7/29.0 19.6/18.8 7.0 26.4/25.2 9.8/9.4 3.5 13.2/12.6 7.8/7.5 2.8 10.3/10.1 22.3/21.5 3 1.1 7.0 29.7/29.0 19.6/18.8 7.0 26.4/25.2 9.8/9.4 3.5 13.2/12.6 7.8/7.5 2.8 10.3/10.1 22.3/21.5 3 1.1 7.0 29.7/29.0 44.4/41.5 19.6/18.8 7.0 26.4/25.2 38.6/36.0 9.8/9.4 3.5 13.2/12.6 19.3/18.0 7.8/7.5 2.8 10.3/10.1 15.4/14.5 29.7/29.0 4 1.1 7.0 44.4/41.5 26.4/25.2 7.0 38.6/36.0 13.2/12.6 3.5 19.3/18.0 10.3/10.1 2.8 15.4/14.5 29.7/29.0 4 1.1 7.0 44.4/41.5 58.7/56.1 26.4/25.2 7.0 38.6/36.0 51.0/49.4 13.2/12.6 3.5 19.3/18.0 25.5/24.7 10.3/10.1 2.8 15.4/14.5 20.4/19.6
Exhaust
No. 2
HP 1.0
FLA (Ea.) 6.7 6.7 2.9 2.3
2
1.0
6.7 6.7 2.9 2.3
2
1.0
6.7
6.7
2.9
2.3
2
1.0
6.7 6.7 2.9 2.3
2
1.0
6.7
6.7
2.9
2.3
Notes: 1. All customer wiring and devices must be installed in accordance with local and national electrical codes.
Table ED-3 — Electrical Service Sizing Data — Crankcase Heaters — Heating Mode Only) Nominal
FLA Add
Unit Size
54
Unit Voltage
(Tons)
200
230
460
575
27½ - 35
2
2
1
1
40, 50
3
3
2
2
RT-PRC007-EN
Electrical Data
50 Hz
Table ED-4 – Electrical Service Sizing Data
Model
Electrical2 Characteristics
TC/TE/YC*275 TC/TE/YC*305 TC/TE/YC*350 TC/TE/YC*400
380-415/50/3 380-415/50/3 380-415/50/3 380-415/50/3
TC/TE/YC*500
380-415/50/3
Compressor RLA No/Ton (Ea.) 1/10, 1/15 18.1/27.3 2/15 27.3 2/15 27.3 2/15, 27.3 1/10 18.1 3/15 27.3
Supply LRA (Ea.) 110/174 174 174 174 110 174
Fan Motors Condenser FLA No. HP (Ea.)
HP
FLA
5 5 5 7.5
13.1 13.1 13.1 16.6
3 3 3 4
.75 .75 .75 .75
7.5
16.6
4
.75
Exhaust No.
HP
FLA (Ea.)
MCA*
Max. Fuse Size
4.4 4.4 4.4 4.4
2 2 2 2
.75 .75 .75 .75
2.9 2.9 2.9 2.9
79 93 93 119
100 110 110 125
4.4
2
.75
2.9
128
150
Notes: 1. All customer wiring and devices must be installed in accordance with local and national electrical codes. 2. Allowable voltage range for the 380V unit is 342-418V, allowable voltage range for the 415V unit is 373-456. * Minimum Circuit Ampacity.
Table ED-5 – Electrical Service Sizing Data – Electric Heat Module (Electric Heat Units Only) Models: TED/TEH 275 thru 500 Electric Heat FLA Nominal Nominal Unit Size Unit (Tons) Voltage 23-29 380 415 33, 42 380 415
23/27 34.5 37.6 – –
KW Heater (380/415V) 34/40 45/54 56/67 51.1 68.9 85.5 55.6 – – 51.1 68.9 85.5
68/81 – – 103.4
55.6
112.7
75.1
93.2
Notes: 1. All FLA in this table are based on heater operating at 380 or 415 volts as shown above.
Table ED-6— Electrical Service Sizing Data — Crankcase Heaters — Heating Mode Only)
RT-PRC007-EN
Nominal
FLA Add
Unit Size
Unit Voltage
(Tons)
380
415
23 - 29
1
1
33 - 42
2
2
55
Dimensional Data
60/50 Hz
Figure DD-1— Fresh Air, Power Exhaust Hoods
SIDE VIEW SHOWING FRESH AIR AND POWER EXHAUST HOODS FOR DOWNFLOW CONFIGURATION
(62)
(814)
(959)
(62)
(814)
NOTE: The Two Horizontal Power Exhaust Hoods and the three Horizontal Fresh Air Hoods are located side by side. The Fresh Air Hoods (not shown) extend only 23 15/16” from the end of the unit.
56
RT-PRC007-EN
Dimensional Data
60/50 Hz
Figure DD-2 – 60 Hz 27½-35, 50 Hz 23-29 Tons (TC, TE, YC Low Heat)
Note: Dimensions in ( ) are mm 1” = 25.4 mm
RT-PRC007-EN
57
Dimensional Data
60/50 Hz
Figure DD-3– 60 Hz 27½-35, 50 Hz 23-29 Tons (YC High Heat)
Note: Dimensions in ( ) are mm 1” = 25.4 mm 58
RT-PRC007-EN
Dimensional Data
60/50 Hz
Figure DD-4 – 60 Hz 40-50, 50 Hz 33-42 Tons (TC, TE, YC Low & High Heat)
Note: Dimensions in ( ) are mm 1” = 25.4 mm RT-PRC007-EN
59
Dimensional Data
(Variable Air Volume VAV)
Field Installed Sensors SINGLE SETPOINT SENSOR WITH SYSTEM FUNCTION LIGHTS (BAYSENS021*)
PROGRAMMABLE NIGHT-SETBACK SENSOR (BAYSENS020*)
Note: 1. Remote sensors are available for use with all zone sensors to provide remote sensing capabilities.
60
RT-PRC007-EN
Dimensional Data
(Constant Volume CV)
Field Installed Sensors PROGRAMMABLE NIGHT-SETBACK SENSOR (BAYSENS019*)
DUAL SETPOINT, MANUAL/AUTOMATIC CHANGEOVER SENSOR WITH SYSTEM FUNCTION LIGHTS (BAYSENS010*) WITHOUT LED STATUS INDICATORS (BAYSENS008*) SINGLE SETPOINT WITHOUT LED STATUS INDICATORS (BAYSENS006*)
Note: 1. Remote sensors are available for use with all zone sensors to provide remote sensing capabilities.
RT-PRC007-EN
61
Dimensional Data
(CV and VAV)
Integrated Comfort™ System Sensors ZONE TEMPERATURE SENSOR W/TIMED OVERRIDE BUTTON AND LOCAL SETPOINT ADJUSTMENT (BAYSENS014) 1
ZONE TEMPERATURE SENSOR W/TIMED OVERRIDE BUTTONS (BAYSENS013*) ALSO AVAILABLE SENSOR ONLY (BAYSENS017*)
TEMPERATURE SENSOR (BAYSENS016*)
REMOTE MINIMUM POSITION POTENTIOMETER CONTROL (BAYSTAT023*)
Note: 1. Remote sensors are available for use with all zone sensors to provide remote sensing capabilities.
62
RT-PRC007-EN
Dimensional Data and Weights
Table W-1 — Approximate Operating Weights — Lbs. 2 Basic Unit Weights 1
WALL-MOUNTED CO 2 SENSOR (BAYCO2K005*) DUCT-MOUNTED CO 2 SENSOR (NOT PICTURED) (BAYC02K006*)
Unit Model
YC Low Heat
**D330/275 **H330/275 **D360/305 **H360/305 **D420/350 **H420/350 **D480/400 **H480/400 **D600/500 **H600/500
YC High Heat
3650 3650 3730 3730 3815 3815 4765 4790 4935 4960
4012 4077 4092 4142 4177 4227 4885 4915 5055 5085
TC
TE
3520 3565 3600 3600 3685 3685 4540 4540 4710 4710
3553 3598 3633 3633 3718 3718 4575 4575 4745 4745
Table W-1a — Approximate Operating Weights — kg Basic Unit Weights 1 Unit Model
Model
A
B
C
D
843 856 859 870 877 888 1026 1032 1062 1068
883 897 900 911 919 930 1075 1081 1112 1119
481 489 491 497 501 507 586 590 607 610
642 652 655 663 668 676 782 786 809 814
**D330/275 **H330/275 **D360/305 **H360/305 **D420/350 **H420/350 **D480/400 **H480/400 **D600/500 **H600/500
RT-PRC007-EN
A
382.38 388.28 389.64 394.63 397.81 402.80 465.39 468.12 481.72 484.44
B
400.53 406.88 408.24 413.23 416.86 421.85 487.62 490.34 504.40 507.58
C
218.18 221.81 222.72 225.44 227.25 229.98 265.81 267.62 275.34 276.70
D
291.21 295.75 297.11 30 0.74 303.00 306.63 354.72 356.53 366.96 369.23
TC
TE
1656 1656 1692 1692 1731 1731 2161 2161 2239
1820 1849 1856 1879 1895 1895 2216 2216 2293
1597 1617 1633 1633 1672 1672 2059 2059 2137
1612 1632 1648 1648 1687 1687 2075 2075 2152
**H600/500
2239
2293
2137
2152
E
F
682 693 696 704 710 719 830 836 859 864
481 489 491 497 501 507 586 590 607 610
E
F
309.36 314.34 315.71 319.33 322.06 326.14 376.49 379.21 389.64 391.91
218.18 221.81 222.72 225.44 227.25 229.98 265.81 267.62 275.34 276.70
Table W-2a— Point Loading Average Weight 3,4 — kg. Model
YC High Heat
**D330/275 **H330/275 **D360/305 **H360/305 **D420/350 **H420/350 **D480/400 **H480/400 **D600/500
Table W-2 — Point Loading Average Weight 3,4 — lbs.
**D330/275 **H330/275 **D360/305 **H360/305 **D420/350 **H420/350 **D480/400 **H480/400 **D600/500 **D600/500
YC Low Heat
Notes 1. Basic unit weight includes minimum HP Supply Fan motor. 2. Optional high static and high efficiency motor weights are in addition to the standard motor weight included in the basic unit weight. 3. Point Loading is identified with corner A being the corner with the compressors. As you move clockwise around the unit as viewed from the top, mid-point B, corner C, corner D, mid-point E and corner F. 4. Point load calculations provided are based on the unit weight for YC high heat models. To calculate point loads for a specific model, multiply the percentages given in Table W-5 by the unit weight listed in table W-1.
Table W-3— Point Loading Percentages of Total Unit Weight 1 A
21%
B
C
D
E
F
22%
12%
16%
17%
12%
1. To calculate point loads for a specific model, multiply percentages by unit weight listed in table Table W-1.
D
E
F TOP VIEW OF UNIT
COMPRS C
B
A
63
Weights
Table W-4— Approximate Operating Weights — lb — Weight of Optional Components
Unit Model **D330/275 **H330/300 **D360/305 **H330/305 **D420/350 **H420/350 **D480/400 **H480/400 **D600/500 **H600/500
Baro. Relief
Power Exhaust
Hi-Stat/ Hi Eff. Sup Fan Motor2
110 145 110 145 110 145 110 145 110 145
165 200 165 200 165 200 165 200 165 200
120 120 120 120 120 120 125 125 125 125
0-25% Man Damper
Econ.
50 50 50 50 50 50 50 50 50 50
260 285 260 285 260 285 290 300 290 300
Var. Freq. Inlet Drives (VFD’s) Guide W/O With Vanes BypassBypass 55 55 55 55 55 55 70 70 70 70
85 85 85 85 115 115 115 115 115 115
115 115 115 115 150 150 150 150 150 150
Serv Valves
Thru-the base Elec.
NonFused Discon. Switch
Fact. GFI with Roof Discon. Curb Switch Lo/Hi
11 11 11 11 11 11 18 18 18 18
6 6 6 6 6 6 6 6 6 6
30 30 30 30 30 30 30 30 30 30
85 85 85 85 85 85 85 85 85 85
310/330 310/330 310/330 310/330 310/330 310/330 365/368 365/365 365/365 365/365
Thru-the base Elec. 3 3 3 3 3 3 3 3 3 3
NonFused Discon. Switch 14 14 14 14 14 14 14 14 14 14
Fact. GFI with Discon. Switch 38 38 38 38 38 38 38 38 38 38
Roof Curb Lo/Hi 141/150 141/150 141/150 141/150 141/150 141/150 169 169 169 169
Table W-4a — Approximate Operating Weights — kg — Weight of Optional Components
Unit Model **D275 **H275 **D305 **H305 **D350 **H350 **D400 **H400 **D500 **H500
Baro. Relief 50 65 50 65 50 65 50 65 50 65
Power Exhaust 74 90 74 90 74 90 74 90 74 90
Hi-Stat/ Hi Eff. Sup Fan Motor2 54 54 54 54 54 54 56 56 56 56
0-25% Man Damper 23 23 23 23 23 23 23 23 23 23
Econ. 117 128 117 128 117 128 131 135 131 135
Var. Freq. Inlet Drives (VFD’s) Guide W/O With Vanes BypassBypass 25 38.6 52.2 25 38.6 52.2 25 38.6 52.2 25 38.6 52.2 25 52.268.04 25 52.268.04 32 52.268.04 32 52.268.04 32 52.268.04 32 52.268.04
Serv Valves 5 5 5 5 5 5 8 8 8 8
Notes: 1. Basic unit weight includes minimum hp Supply Fan Motor. 2. Optional high static and high efficiency motor weights are in addition to the standard motor weight included in the basic unit weight.
Table W-5— Minimum Operating Clearances for Unit Installation
Single Unit1
Econo / Exhaust End 6 Feet (1.82 m)
Condenser Coil2 End / Side 8 Feet / 4 Feet (2.43/1.21 m)
Service Side Access 4 Feet (1.21 m)
Multiple Unit1,3
12 Feet (3.65 m)
16 Feet / 8 Feet (4.87/2.43 m)
8 Feet (2.43 m)
Notes: 1. Horizontal and Downflow Units, all sizes. 2. Condenser coil is located at the end and side of the unit. 3. Clearances on multiple unit installations are distances between units.
64
RT-PRC007-EN
Mechanical Specifications
General The units shall be dedicated downflow or horizontal airflow.The operating range shall be between 115 F and 0 F in cooling as standard from the factory for all units. Cooling performance shall be rated in accordance with ARI testing procedures. All units shall be factory assembled, internally wired, fully charged with HCFC22 and 100% run tested to check cooling operation, fan and blower rotation and control sequence before leaving the factory. Wiring internal to the unit shall be numbered for simplified identification. Units shall be UL listed and labeled, classified in accordance to UL 1995/CAN/ CSA No. 236-M90 for Central Cooling Air Conditioners. Canadian units shall be CSA Certified. Casing Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. All components shall be mounted in a weather resistant steel cabinet with a painted exterior. Where top cover seams exist, they shall be double hemmed and gasket sealed to prevent water leakage. Cabinet construction shall allow for all maintenance on one side of the unit. Service panels shall have handles and shall be removable while providing a water and air tight seal. Control box access shall be hinged. The indoor air section shall be completely insulated with fire resistant, permanent, odorless, foil faced glass fiber material. The base of the unit shall have provisions for crane lifting. Filters Two inch, throwaway filters shall be standard on all size units. Two inch “high efficiency”, and four inch “high efficiency” filters shall be optional. Compressors Trane 3-D™ Scroll compressors have a simple mechanical design with only three major moving parts. Scroll type compression provides inherently low vibration. The 3-D Scroll provides a completely enclosed compression
RT-PRC007-EN
chamber which leads to increased efficiency. Exhaustive testing on the 3-D Scroll, including start up with the shell full of liquid, has proven that slugging does not fail involutes. Direct-drive, 3600 rpm, suction gas-cooled hermetic motor. Trane 3-D Scroll compressor includes centrifugal oil pump, oil level sightglass and oil charging valve. Each compressor shall have crankcase heaters installed, properly sized to minimize the amount of liquid refrigerant present in the oil sump during off cycles. Refrigerant Circuits Each refrigerant circuit shall have independent thermostatic expansion devices, service pressure ports and refrigerant line filter driers factoryinstalled as standard. An area shall be provided for replacement suction line driers. Evaporator and Condenser Coils Condenser coils shall have 3 / 8” copper tubes mechanically bonded to lanced aluminum plate fins. Evaporator coils shall be 1 / 2” internally finned copper tubes mechanically bonded to high performance aluminum plate fins. All coils shall be leak tested at the factory to ensure pressure integrity. All coils shall be leak tested to 200 psig and pressure tested to 450 psig. All dual circuit evaporator coils shall be of intermingled configuration. Sloped condensate drain pans are standard. Outdoor Fans The outdoor fan shall be direct-drive, statically and dynamically balanced, draw through in the vertical discharge position. The fan motor(s) shall be permanently lubricated and have built-in thermal overload protection. Indoor Fan Units shall have belt driven, FC, centrifugal fans with fixed motor sheaves. All motors shall be circuit breaker protected. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT).
Electric Heaters Electric heat shall be available for factory installation within basic unit. Electric heater elements shall be constructed of heavy-duty nickel chromium elements internally delta connected for 240 volt, wye connected for 480 and 600 volt. Staging shall be achieved through the rooftop refrigeration module (RTRM). Each heater package shall have automatically reset high limit control operating through heating element contactors. All heaters shall be individually fused from factory, where required, and meet all NEC and CEC requirements. Power assemblies shall provide single-point connection. Electric heat shall be UL listed or CSA certified. Gas Heating Section The heating section shall have a drum and tube heat exchanger(s) design with primary and secondary surfaces of corrosion resistant alumanized steel or optional stainless steel. A forced combustion blower shall supply premixed fuel to a single burner ignited by a pilotless hot surface ignition system. In order to provide reliable operation, a negative pressure gas valve shall be used that requires blower operation to initiate gas flow. On an initial call for heat, the combustion blower shall purge the heat exchanger(s) 45 seconds before ignition. After three unsuccessful ignition attempts, the entire heating system shall be locked out until manually reset at the thermostat. Units shall be suitable for use with natural gas or propane (field installed kit) and also comply with California requirements for low NOx emissions. All units shall have two stage heating. Controls Unit shall be completely factory wired with necessary controls and terminal block for power wiring. Units shall provide an external location for mounting fused disconnect device. ReliaTel controls
65
Mechanical Specifications
shall be provided for all 24 volt control functions. The resident control algorithms shall make all heating, cooling and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures. The control algorithm maintains accurate temperature control, minimizes drift from set point and provides better building comfort. Relia Tel controls shall provide anti-short cycle timing and time delay between compressors to provide a higher level of machine protection.
preset ventilation sequences, exhaust or pressurization. The two sequences shall be selectable based open a binary select input.
Control Options
RTRM Originated Data • Unit operating mode • Unit failure status Cooling failure Heating failure Emergency service stop indication Supply fan proving Timed override activation High temperature thermostat status • Zone temperature • Supply air temperature • Cooling status (all stages) • Stage activated or not • Stage locked out by RTRM • HPC status for that stage • Compressor disable inputs • Heating status • Number of stages activated • High temperature limit status • Economizer status • Enthalpy favorability status • Requested minimum position • Damper position • Dry bulb/enthalpy input status • Outside air temperature • Outside relative humidity • Sensor Failure Humidity sensor OAT sensor SAT sensor RAT sensor Zone temperature sensor Mode input Cooling/heating setpoints from sensors Static pressure transducer Unit mounted potentiometer SAT from potentiometer Air reset setpoint from potentiometer • Unit Configuration data Gas or electric heat Economizer present • High temp input status
Inlet Guide Vanes shall be installed on each fan inlet to regulate capacity and limit horsepower at lower system requirements. When in any position other than full open they shall pre-spin intake air in the same direction as fan rotation. The inlet guide vanes shall close when supply fan is off, except in night setback. The inlet guide vane actuator motor shall be driven by a modulating dc signal from the unit controls. A pressure transducer shall measure duct static pressure and modulate the inlet guide vanes to maintain the required supply air static pressure within a predetermined range. Variable Frequency Drives (VFDs) VFDs shall be factory installed and tested to provide supply fan motor speed modulation. The VFD shall receive a 210 VDC signal from the unit controls based upon supply static pressure and shall cause the drive to accelerate or decelerate as required to maintain the supply static pressure setpoint. When subjected to high ambient return conditions the VFD shall reduce its output frequency to maintain operation. Bypass control to provide full nominal air flow in the event of drive failure shall be optional. Ventilation Override Ventilation Override shall allow a binary input from the fire/life safety panel to cause the unit to override standard operation and assume one of two factory
66
Trane Communication Interface (TCI) Shall be provided to interface with the Trane Integrated Comfort™ System and shall be available field or factory-installed. TheTCI shall allow control and monitoring of the rooftop unit via a two-wire communication link. The following alarm and diagnostic information shall be available:
• • • • • •
Local setpoint Local mode setting Inlet Guide Vane position Clogged filter service indicator CO2 setpoint CO2 value
Tracer Originated Data • Command operating mode • Host controllable functions: Supply fan Economizer Cooling stages enabled Heating stages enabled Emergency shutdown • Minimum damper position • Heating setpoint • Cooling setpoint • Supply air tempering enable/disable • Slave mode (CV only) • Tracer/Local operation • SAT setpoint • Reset setpoint • Reset amount • MWU setpoint • MWU enable/disable • SAT Reset type select • Static pressure setpoint • Static pressure deadband • Daytime warm-up enable/disable • Power exhaust setpoint LonTalk Communication Interface (LCI-R) The field or factory-installed ReliaTel® LonTalk Communication Interface (LCI-R) will be provided to interface with the Trane Integrated Comfort System or LonTalk capable third party building management networks. The LCI-R will allow control and monitoring of the rooftrop unit via a two-wire communication link.
Outside Air Manual Outside Air A manually controllable outside air damper shall be adjustable for up to 25 percent outside air. Manual damper is set at desired position at unit start up. Economizer Economizer shall be factory installed. The assembly includes: fully modulating 0-100 percent motor and dampers, minimum position setting, preset linkage, wiring harness, and fixed dry bulb control. Solid state enthalpy and
RT-PRC007-EN
Mechanical Specifications
differential enthalpy control shall be a factory or field installed option.
Exhaust Air Barometric Relief The barometric relief damper shall be optional with the economizer. Option shall provide a pressure operated damper for the purpose of space pressure equalization and be gravity closing to prohibit entrance of outside air during the equipment “off” cycle.
Power Exhaust Fan Power exhaust shall be available on all units and shall be factory installed. It shall assist the barometric relief damper in maintaining building pressurization.
Unit Options Service Valves Service valves shall be provided factory installed and include suction, liquid, and discharge 3-way shutoff valves.
Through-The-Base Electrical Provision An electrical service entrance shall be provided which allows access to route all high and low voltage electrical wiring inside the curb, through the bottom of the outdoor section of the unit and into the control box area.
Non-Fused Disconnect Switch A factory installed non-fused disconnect switch with external handle shall be provided and shall satisfy NEC requirements for a service disconnect. The non-fused disconnect shall be mounted inside the unit control box.
GFI Convenience Outlet (Factory Powered) A 15A, 115V Ground Fault Interrupter convenience outlet shall be factory installed. It shall be wired and powered from a factory mounted transformer. Unit mounted non-fused disconnect with external handle shall be furnished with factory powered outlet.
GFI Convenience Outlet (Field Powered) A 15A, 115V Ground Fault Interrupter convenience outlet shall be factory installed and shall be powered by customer provided 115V circuit.
RT-PRC007-EN
Hinged Service Access Filter access panel and supply fan access panel shall be hinged for ease of unit service.
sensor and allow the unit to continue normal operation.
Roof Curb
Sloped stainless steel evaporator coil drain pans are durable, long-lasting and highly corrosion resistant.
The roof curb shall be designed to mate with the unit and provide support and a water tight installation when installed properly.The roof curb design shall allow field-fabricated rectangular supply/return ductwork to be connected directly to the curb when used with downflow units. Curb design shall comply with NRCA requirements. Curb shall ship knocked down for field assembly and include wood nailer strips.
Black Epoxy Coated Condenser Coil
Zone Sensors
The coil provides corrosion protection to condenser coils for seacoast application. The protection is a factory applied thermoset vinyl coating, bonded to normal aluminum fin stock.The uniform thickness of the bonded vinyl layer exhibits excellent corrosion protection in salt spray tests performed in accordance with ASTM B117.
Shall be provided to interface with the ReliaTel unit controls and shall be available in either manual, automatic programmable with night setback, with system malfunction lights or remote sensor options.
Condenser Coil Guards Factory installed condenser vinyl coated wire mesh coil guards shall be available to provide full area protection against debris and vandalism.
Stainless Steel Drain Pans
Black Epoxy Coated Condenser Coil The coil provides corrosion protection to condenser coils for seacoast application. The protection is a factory applied thermoset vinyl coating, bonded to normal aluminum fin stock.The uniform thickness of the bonded vinyl layer exhibits excellent corrosion protection in salt spray tests performed in accordance with ASTM B117.
Discharge Air Sensing Provides true discharge air sensing in heating and cooling models.This sensor is a status indicator readable through Tracer, Tracker or LCI-R. Discharge air sensing is standard with Variable Air Volume (VAV) units, optional with Constant Volume (CV) units.
Clogged Filter Indication This optional factory installed differential pressure switch allows dirty filter indication at the zone sensor with service LED. When closed, the dirty filter switch will light the service LED on the zone
Remote Potentiometer A remote potentiometer shall be available to remotely adjust the unit economizer minimum position.
High Temperature Thermostats Field installed, manually resettable high temperature thermostats shall provide input to the unit controls to shut down the system if the temperature sensed at the return is 135 F or at the discharge 240 F.
Reference Enthalpy Kit Field installed enthalpy kit shall provide inputs for economizer control based upon comparison of the outside air stream to a definable enthalpy reference point. May also be factory installed.
Comparative Enthalpy Kit Field installed enthalpy kit shall provide inputs for economizer control based upon comparison of the enthalpies of the return and outdoor air streams. Also available factory installed.
LP Conversion Kit Field installed conversion kit shall provide orifice(s) for simplified conversion to liquefied propane gas. No change of gas valve shall be required.
67
Mechanical Specifications
BAYCO2K005* — Wall-mounted CO2 sensor has the ability to monitor space occupancy levels within the building by measuring the parts per million of CO 2 (Carbon Dioxide) in the air. As the CO 2 levels increase, the outside air damper modulates to meet the CO2 space ventilation requirements. BAYCO2K006* — Duct-mounted CO2 sensor has the ability to monitor space occupancy levels within the building by measuring the parts per million of CO 2 (Carbon Dioxide) in the air. As the CO 2 levels increase, the outside air damper modulates to meet the CO2 space ventilation requirements. BAYICSI004* — Field-installed Trane Communication Interface (TCI). BAYLTCI001* — Field-installed LonTalk Communication Interface (LCI-R) for Constant Volume (CV) units. BAYLTCI004* — Field-installed LonTalk Communication Interface (LCI-R) for Variable Air Volume (VAV) units. BAYSENS006* — Zone Sensor has one temperature setpoint lever, heat, off or cool system switch, fan auto or fan on switch. Manual changeover.These sensors are for CV units only. BAYSENS008* — Zone Sensor has two temperature setpoint levers, heat, auto, off, or cool system switch, fan auto or fan on switch. Auto changeover.These sensors are used with CV units. BAYSENS010* — Zone Sensor has two temperature set point levers, heat, auto, off, or cool system switch, fan auto or fan on switch. Status indication LED lights, System on, Heat, Cool, and Service are provided.These sensors are used with CV units.
BAYSENS014* — Zone temperature sensor with local temperature adjustment control and timed override buttons used with Tracer Integrated Comfort system. May also be used for Morning Warm-up setpoint and sensor. BAYSENS016* — Temperature Sensor is a bullet or pencil type sensor that could be used for temperature input such as return air duct temperature. BAYSENS017* — Remote Sensor can be used for remote zone temperature sensing capabilities when zone sensors are used as remote panels or as a morning warm-up sensor for use with VAV units or as a zone sensor with Tracer Integrated Comfort system. BAYSENS019* and BAYSENS020* — Electronic programmable sensors with auto or manual changeover with seven day programming. Keyboard selection of heat, cool, auto fan or on. All programmable sensors have System on, Heat, Cool, Service LED/LCD indicators as standard. Night setback sensors have two occupied, and two unoccupied programs per day. Sensors are available for CV zone temperature control and VAV zone temperature control. BAYSENS021* — Zone Sensor with supply air single temperature setpoint and AUTO/OFF system switch. Status indication LED lights, System ON, Heat, Cool, and Service are provided. Sensors are available to be used with VAV units. BAYSTAT023* — Remote Minimum Position Potentiometer is used to remotely specify the minimum economizer position.
BAYSENS013* — Zone temperature sensor with timed override buttons used withTracer™ Integrated Comfort system.
68
RT-PRC007-EN
RT-PRC007-EN
69