Short Circuit According To The Iec 60909 - Open Electrical

Short circuit

   EMBED


Share

Transcript

07/05/2016 Accor di ng to the IEC 60909 - Open Electr i cal According to the to the IEC 60909 From Open Electrical Contents Contents 1 Introduction Introduction 1.1 1.1 Why do the calculation? 1.2 1.2 When to do the calculation? 2 Calculation Calculation Methodology 2.1 Step 1: Construct Construct the System Model and Collect Equipment Parameters 2.2 2.2 Step 2: Calculate Equipment Short Circuit Impedances Impedances 2.2.1 Network Feeders 2.2.2 Synchronous Generators Generators and Motors 2.2.3 Transformers 2.2.4 Cables 2.2.5 Asynchronous Motors 2.2.6 Fault Limiting Limiting Reactors 2.2.7 Static Conver ters ters 2.2.8 Other Equipment 2.3 Ste p 3: Referring Impedances Impedances 2.4 Ste p 4: Determine Thévenin Determine Thévenin Equivalent Circuit at the Fault Location 2.5 Ste p 5: Calculate Balanced Three-Phase Three-Phase Short Circuit Currents 2.5.1 Initial Short Circuit Current 2.5.2 Peak Short Circuit Current 2.5.3 Symmetrical Symmetrical Breaking Current 2.5.4 DC Short Circuit Circuit Component 2.6 2.6 Step 6: Calculate Single-Phase Single-Phase to Earth Short Circuit Currents 3 Worked Example Example 3.1 Step 1: Construct the System Model and Collect Equipment Parameters 3.2 Step 2: Calculate Equipment Short Circuit Impedances 3.3 Step 3: Referring Impedances 3.4 Step 4: Determine Thévenin Equivalent Circuit at the Fault Location 3.5 Step 5: Calculate Balanced Three-Phase Short Circuit Currents 3.5.1 Initial Short Circuit Current 3.5.2 Peak Short Circuit Current 4 Computer Software 5 What Next? Introduction This article looks at the calculation of short circuit currents for bolted three-phase and single-phase to earth faults in a power system. A short circuit in a power system can cause very high currents to flow to the fault http://www.openel ectr i cal .or g/wi ki /index.php?titl e= Accor di ng_to_the_IEC_60909 1/14 07/05/2016 According to the IEC 60909 - Open Electrical location. The magnitude of the short circuit current depends on the impedance of system under short circuit conditions. In this calculation, the short circuit current is estimated using the guidelines presented in IEC 60909. Why do the calculation? Calculating the prospective short circuit levels in a  power system is important for a number of reasons, including: To specify fault ratings for electrical equipment (e.g. short circuit withstand ratings) To help identify potential problems and weaknesses in the system and assist in system planning To form the basis for protection coordination studies Figure 1. Lightning arc When to do the calculation? The calculation can be done after preliminary system design, with the following pre-requisite documents and design tasks completed: Key single line diagrams Major electrical equipment sized (e.g. generators, transformers, etc) Electrical load schedule Cable sizing (not absolutely necessary, but would be useful) Calculation Methodology This calculation is based on IEC 60909-0 (2001, c2002) (https://webstore.iec.ch/publication/3886) , "Shortcircuit currents in three-phase a.c. systems - Part 0: Calculation of currents" and uses the impedance method (as opposed to the per-unit method). In this method, it is assumed that all short circuits are of negligible impedance (i.e. no arc impedance is allowed for). There are six general steps in the calculation: Step 1: Construct the system model and collect the relevant equipment parameters Step 2: Calculate the short circuit impedances for all of the relevant equipment Step 3: Refer all impedances to the reference voltage Step 4: Determine the Thévenin equivalent circuit at the fault location Step 5: Calculate balanced three-phase short circuit currents Step 6: Calculate single-phase to earth short circuit currents Step 1: Construct the System Model and Collect Equipment Parameters http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 2/14 07/05/2016 According to the IEC 60909 - Open Electrical The first step is to construct a model of the system single line diagram, and then collect the relevant equipment parameters. The model of the single line diagram should show all of the major system buses, generation or network connection, transformers, fault limiters (e.g. reactors), large cable interconnections and large rotating loads (e.g. synchronous and asynchronous motors). The relevant equipment parameters to be collected are as follows:  Network feeders: fault capacity of the network (VA), X/R ratio of the network  Synchronous generators and motors: per-unit sub-transient reactance, rated generator capacity (VA), rated power factor (pu) Transformers: transformer impedance voltage (%), rated transformer capacity (VA), rated current (A), total copper loss (W) Cables: length of cable (m), resistance and reactance of cable ( ) Asynchronous motors: full load current (A), locked rotor current (A), rated power (W), full load power factor (pu), starting power factor (pu) Fault limiting reactors: reactor impedance voltage (%), rated current (A) Step 2: Calculate Equipment Short Circuit Impedances Using the collected parameters, each of the equipment item impedances can be calculated for later use in the motor starting calculations. Network Feeders Given the approximate fault level of the network feeder at the connection point (or point of common coupling), the impedance, resistance and reactance of the network feeder is calculated as follows: Where is impedance of the network feeder (Ω)  is resistance of the network feeder (Ω)  is reactance of the network feeder (Ω)  is the nominal voltage at the connection point (Vac)  is the fault level of the network feeder (VA)  is a voltage factor which accounts for the maximum system voltage (1.05 for voltages <1kV, 1.1 for voltages >1kV)  is X/R ratio of the network feeder (pu) http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 3/14 07/05/2016 According to the IEC 60909 - Open Electrical Synchronous Generators and Motors The sub-transient reactance and resistance of a synchronous generator or motor (with voltage regulation) can be estimated by the following: Where is the sub-transient reactance of the generator (Ω)  is the resistance of the generator (Ω)  is a voltage correction factor - see IEC 60909-0 Clause 3.6.1 for more details (pu)  is the per-unit sub-transient reactance of the generator (pu)  is the nominal generator voltage (Vac)  is the nominal system voltage (Vac)  is the rated generator capacity (VA) is the X/R ratio, typically 20 for all generators with nominal voltage 100MVA, 14.29 for 100MVA, and 6.67 for  1kV  is a voltage factor which accounts for the maximum system voltage (1.05 for voltages <1kV, 1.1 for voltages >1kV)  is the power factor of the generator (pu) For the negative sequence impedance, the quadrature axis sub-transient reactance the above equation in place of the direct axis sub-transient reactance can be applied in . The zero-sequence impedances need to be derived from manufacturer data, though the voltage correction factor also applies for solid neutral earthing systems (refer to IEC 60909-0 Clause 3.6.1). Transformers The positive sequence impedance, resistance and reactance of two-winding distribution transformers can be calculated as follows: http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 4/14 07/05/2016 Where According to the IEC 60909 - Open Electrical is the positive sequence impedance of the transformer (Ω)  is the resistance of the transformer (Ω)  is the reactance of the transformer (Ω)  is the impedance voltage of the transformer (pu)  is the rated capacity of the transformer (VA)  is the nominal voltage of the transformer at the high or low voltage side (Vac)  is the rated current of the transformer at the high or low voltage side (I)  is the total copper loss in the transformer windings (W) For the calculation of impedances for three-winding transformers, refer to IEC 60909-0 Clause 3.3.2. For  network transformers (those that connect two separate networks at different voltages), an impedance correction factor must be applied (see IEC 60909-0 Clause 3.3.3). The negative sequence impedance is equal to positive sequence impedance calculated above. The zero sequence impedance needs to be derived from manufacturer data, but also depends on the winding connections and fault path available for zero-sequence current flow (e.g. different neutral earthing systems will affect zero-sequence impedance). Cables Cable impedances are usually quoted by manufacturers in terms of Ohms per km. These need to be converted to Ohms based on the length of the cables: Where is the resistance of the cable {Ω)  is the reactance of the cable {Ω)  is the quoted resistance of the cable {Ω / km)  is the quoted reactance of the cable {Ω / km)  is the length of the cable {m) The negative sequence impedance is equal to positive sequence impedance calculated above. The zero sequence impedance needs to be derived from manufacturer data. In the absence of manufacturer data, zero sequence impedances can be derived from positive sequence impedances via a multiplication factor (as suggested by SKM Systems Analysis Inc) for magnetic cables: Asynchronous Motors http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 5/14 07/05/2016 According to the IEC 60909 - Open Electrical An asynchronous motor's impedance, resistance and reactance is calculated as follows: Where is impedance of the motor (Ω)  is resistance of the motor (Ω)  is reactance of the motor (Ω)  is ratio of the locked rotor to full load current  is the motor locked rotor current (A)  is the motor nominal voltage (Vac)  is the motor rated power (W)  is the motor full load power factor (pu)  is the motor starting power factor (pu) The negative sequence impedance is equal to positive sequence impedance calculated above. The zero sequence impedance needs to be derived from manufacturer data. Fault Limiting Reactors The impedance of fault limiting reactors is as follows (note that the resistance is neglected): Where is impedance of the reactor (Ω)  is reactance of the reactor(Ω)  is the impedance voltage of the reactor (pu)  is the nominal voltage of the reactor (Vac)  is the rated current of the reactor (A) Positive, negative and zero sequence impedances are all equal (assuming geometric symmetry). Static Converters Static converters and converter-fed drivers (i.e. feeding rotating loads) should be considered for balanced three-phase short circuits. Per IEC 60909-0 Clause 3.9, static converters contribute to the initial and peak  short circuit currents only, and contribute 3 times the rated current of the converter. An R/X ratio of 0.1 should be used for the short circuit impedance. http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 6/14 07/05/2016 According to the IEC 60909 - Open Electrical Other Equipment Line capacitances, parallel admittances and non-rotating loads are generally neglected as per IEC 60909-0 Clause 3.10. Effects from series capacitors can also be neglected if voltage-limiting devices are connected in parallel. Step 3: Referring Impedances Where there are multiple voltage levels, the equipment impedances calculated earlier need to be converted to a reference voltage (typically the voltage at the fault location) in order for them to be used in a single equivalent circuit. The winding ratio of a transformer can be calculated as follows: Where is the transformer winding ratio  is the transformer nominal secondary voltage at the principal tap (Vac)  is the transformer nominal primary voltage (Vac)  is the specified tap setting (%) Using the winding ratio, impedances (as well as resistances and reactances) can be referred to the primary (HV) side of the transformer by the following relation: Where is the impedance referred to the primary (HV) side (Ω)  is the impedance at the secondary (LV) side (Ω)  is the transformer winding ratio (pu) Conversely, by re-arranging the equation above, impedances can be referred to the LV side: Step 4: Determine Thévenin Equivalent Circuit at the Fault Location The system model must first be simplified into an equivalent circuit as seen from the fault location, showing a voltage source and a set of complex impedances representing the power system equipment and load impedances (connected in series or parallel). The next step is to simplify the circuit into a Thévenin equivalent circuit (http://en.wikipedia.org/wiki/Th%C3%A9venin%27s_theorem) , which is a circuit containing only a voltage source ( ) and an equivalent short circuit impedance ( ). http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 7/14 07/05/2016 According to the IEC 60909 - Open Electrical This can be done using the standard formulae for series and  parallel impedances, keeping in mind that the rules of  complex arithmetic must be used throughout. If unbalanced short circuits (e.g. single phase to earth fault) will be analysed, then a separate Thévenin equivalent circuit should be constructed for each of the positive, negative and zero sequence networks (i.e. finding ( , and ). Step 5: Calculate Balanced Three-Phase Short Circuit Currents Figure 2. Thévenin equivalent circuit The positive sequence impedance calculated in Step 4 represents the equivalent source impedance seen by a balanced three-phase short circuit at the fault location. Using this impedance, the following currents at different stages of the short circuit cycle can be computed: Initial Short Circuit Current The initial symmetrical short circuit current is calculated from IEC 60909-0 Equation 29, as follows: Where is the initial symmetrical short circuit current (A)  is the voltage factor that accounts for the maximum system voltage (1.05 for voltages <1kV, 1.1 for voltages >1kV)  is the nominal system voltage at the fault location (V)  is the equivalent positive sequence short circuit impedance (Ω) Peak Short Circuit Current IEC 60909-0 Section 4.3 offers three methods for calculating peak short circuit currents, but for the sake of  simplicity, we will only focus on the X/R ratio at the fault location method. Using the real (R) and reactive (X) components of the equivalent positive sequence impedance , we can calculate the X/R ratio at the fault location, i.e. The peak short circuit current is then calculated as follows:  (for non-meshed networks) http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 8/14 07/05/2016 According to the IEC 60909 - Open Electrical or   (for meshed networks - see clause 4.3.12b) Where is the peak short circuit current (A)  is the initial symmetrical short circuit current (A)  is a constant factor, Symmetrical Breaking Current The symmetrical breaking current is the short circuit current at the point of circuit breaker opening (usually somewhere between 20ms to 300ms). This is the current that the circuit breaker must be rated to interrupt and is typically used for breaker sizing. IEC 60909-0 Equation 74 suggests that the symmetrical breaking current for meshed networks can be conservatively estimated as follows: Where is the symmetrical breaking current (A)  is the initial symmetrical short circuit current (A) For close to generator faults, the symmetrical breaking current will be higher. More detailed calculations can be made for increased accuracy in IEC 60909, but this is left to the reader to explore. DC Short Circuit Component The dc component of a short circuit can be calculated according to IEC 60909-0 Equation 64: Where is the dc component of the short circuit current (A)  is the initial symmetrical short circuit current (A)  is the nominal system frequency (Hz)  is the time (s)  is the X/R ratio - see more below The X/R ratio is calculated as follows: Where and are the reactance and resistance, respectively, of the equivalent source impedance at the fault location (Ω) http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 9/14 07/05/2016 According to the IEC 60909 - Open Electrical  is a factor to account for the equivalent frequency of the fault. Per IEC 60909-0 Section 4.4, the following factors should be used based on the product of frequency and time ( <1 0.27 <2.5 0.15 <5 0.092 <12.5 0.055 ): Step 6: Calculate Single-Phase to Earth Short Circuit Currents For balanced short circuit calculations, the positive-sequence impedance is the only relevant impedance. However, for unbalanced short circuits (e.g. single phase to earth fault), symmetrical components come into  play. The initial short circuit current for a single phase to earth fault is as per IEC 60909-0 Equation 52: Where is the initial single phase to earth short circuit current (A)  is the voltage factor that accounts for the maximum system voltage (1.05 for voltages <1kV, 1.1 for voltages >1kV)  is the nominal voltage at the fault location (Vac)  is the equivalent positive sequence short circuit impedance (Ω)  is the equivalent negative sequence short circuit impedance (Ω)  is the equivalent zero sequence short circuit impedance (Ω) Worked Example In this example, short circuit currents will be calculated for a balanced three-phase fault at the main 11kV  bus of a simple radial system. Note that the single phase to earth fault currents will not be calculated in this example. Step 1: Construct the System Model and Collect Equipment Parameters The system to be modelled is a simple radial network with two voltage levels (11kV and 415V), and supplied by a single generator. The system model is shown in the figure to the right. The equipment and cable parameters were collected as follows: http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 10/14 07/05/2016 Equipment According to the IEC 60909 - Open Electrical Parameters  = 24,150 kVA Generator G1  = 11,000 V  = 0.255 pu  = 0.85 pu Generator Cable C1 Length = 30m Size = 2 parallel circuits of 3 x 1C x 500 mm2 (R = 0.0506 Ω\km, X = 0.0997 Ω\km) Motor M1  = 500 kW  = 11,000 V  = 200.7 A  = 6.5 pu Figure 3. System model for short circuit example  = 0.85 pu  = 0.30 pu Length = 150m Size = 3C+E 35 mm2 Motor Cable C2 (R = 0.668 Ω\km, X = 0.115 Ω \km) Transformer TX1 Transformer Cable C3  = 2,500 kVA  = 11,000 V  = 415 V  = 0.0625 pu  = 19,000 W = 0% Length = 100m Size = 3C+E 95 mm2 (R = 0.247 Ω\km, X = 0.0993 Ω\km) http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 11/14 07/05/2016 According to the IEC 60909 - Open Electrical Motor M2  = 90 kW  = 415 V  = 1,217.3 A  = 7 pu  = 0.8 pu  = 0.30 pu Motor M3  = 150 kW  = 415 V  = 1,595.8 A  = 6.5 pu  = 0.85 pu  = 0.30 pu Step 2: Calculate Equipment Short Circuit Impedances Using the patameters above and the equations outlined earlier in the methodology, the following impedances were calculated: Equipment Resistance (Ω) Reactance (Ω) Generator G1 0.08672 1.2390 Generator Cable C1 0.000759 0.001496 11kV Motor M1 9.4938 30.1885 Motor Cable C2 0.1002 0.01725 Transformer TX1 (Primary Side) 0.36784 3.0026 Transformer Cable C3 0.0247 0.00993 415V Motor M2 0.0656 0.2086 415V Motor M3 0.0450 0.1432 Step 3: Referring Impedances We will model a fault on the main 11kV bus, so all impedances must be referred to 11kV. The two low voltage motors need to be referred to this reference voltage. Knowing that the transformer is set at principal tap, we can calculate the winding ratio and apply it to refer the 415V motors to the 11kV side: http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 12/14 07/05/2016 According to the IEC 60909 - Open Electrical The 415V motor impedances referred to the 11kV side is therefore: Equipment Resistance (Ω) Reactance (Ω) 415V Motor M2 46.0952 146.5735 415V Motor M3 31.6462 100.6284 Step 4: Determine Thévenin Equivalent Circuit at the Fault Location Using standard network reduction techniques, the equivalent Thévenin circuit at the fault location (main 11kV bus) can be derived. The equivalent source impedance is: Step 5: Calculate Balanced Three-Phase Short Circuit Currents Initial Short Circuit Current The symmetrical initial short circuit current is: kA Peak Short Circuit Current The constant factor at the fault location is: Therefore as it is a simple radial system (non-meshed), the symmetrical peak short circuit current is: kA Computer Software http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 13/14 07/05/2016 According to the IEC 60909 - Open Electrical Short circuit calculations are a standard component of power systems analysis software (e.g. ETAP, PTW, DIgSILENT, etc) and the calculations are far easier to perform with software than by hand. However  manual calculations could be done as a form of verification to confirm that the software results are reasonable. What Next? The results from the short circuit calculations can be used to specify the fault ratings on electrical equipment (e.g. switchgear, protective devices, etc) and also for protection coordination studies. Short Circuit Calculation Retrieved from "http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909" This page was last modified on 9 May 2015, at 01:34. http://www.openelectrical.org/wiki/index.php?title=According_to_the_IEC_60909 14/14